Plan Review Details - Permit 05050201
Plan Review Stops For Permit 05050201
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-09-19 Cont ID  
Sent By rmcdouga Date 2005-09-19 Time 13:24 Rev Time 0.00
Received By rmcdouga Date 2005-09-19 Time 13:24 Sent To  
Notes
2005-09-19 00:00:00PROVISO
  
 1) A SEPARATE PERMIT WITH ADDITIONAL
 FEES WILL BE REQUIRED FOR THE STORM
 PANELS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-03 Cont ID  
Sent By rmcdouga Date 2005-06-03 Time 15:47 Rev Time 0.00
Received By rmcdouga Date 2005-06-03 Time 12:01 Sent To  
Notes
2005-06-03 00:00:00DENIED
  
 1) PLEASE INDICATE ON THE PLAN THAT THE
 GLASS BLOCK IN THE CABANA BATH IS ONE
 HOUR FIRE RATED. FBC TABLE 600 DOES NOT
 ALLOW OPENINGS ON THE ZERO LOT LINE.
  
 2) THE ANCHOR SCHEDULE ON A6 SPECIFIES
 USP THD 210 HANGERS USING TAPCON
 FASTENERS. THESE CONNECTORS ARE NOT
 DESIGNED OR TESTED FOR USE WITH THESE
 FASTENERS. PLEASE SPECIFY AN APPROPRIATE
 MASONRY HANGERS.
  
 3) SUBMIT MANUFACTURER'S SPECS. AND
 LISTING INFORMATION FOR THE ONE HOUR
 FIRE RATED GLASS BLOCK.
  
 4) THE 12' STRUCTURAL MULLION BETWEEN
 THE SLIDING GLASS DOOR AND THE FIXED
 GLASS TRANSOM EXCEEDS THE MAXIMUM
 PRESSURE ALLOWED BY THE PRODUCT
 APPROVAL.
  
 5) THE 12' WIDE FIXED GLASS TRANSOM
 ABOVE THE SGD EXCEEDS THE MAXIMUM WIDTH
 ALLOWED BY THE PRODUCT APPROVAL.
  
 6) THE 9' WIDE FIXED GLASS WINDOW ABOVE
 THE (3) 25 SH WINDOWS IN THE DEN EXCEEDS
 THE MAXIMUM WIDTH ALLOWED BY THE PRODUCT
 APPROVAL.
  
 7) SUBMIT THE EVALUATION/TEST REPORT FOR
 THE ROBICO STORM PANELS.
  
 8) SUBMIT (2) COPIES OF A KEY PLAN AND
 INSTALLATION SCHEDULE FOR THE STORM
 PANELS. SPECIFY THE MOUNT TYPE, FASTENER
 TYPE AND FASTENER SPACING.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop E ELECTRICAL
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By btrobaug Date 2006-05-09 Time 15:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-03-10 Cont ID  
Sent By btrobaug Date 2006-03-10 Time 08:40 Rev Time 0.50
Received By btrobaug Date 2006-03-10 Time 08:40 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-02-24 Cont ID  
Sent By btrobaug Date 2006-02-24 Time 09:12 Rev Time 0.75
Received By btrobaug Date 2006-02-24 Time 06:52 Sent To PC
Notes
2006-02-24 00:00:00 
 THESE COMMENTS WERE MADE ON 9/8/05 AND
 HAVE NOT BEEN CORRECTED ON THE PLAN. IF
 THESE ISSUES WERE CORRECTED IN THE FIELD
 PLEASE CORRELATE THE DPAWINGS, IF NOT
 CORRECTED IN THE FIELD, CORRECT SAME FOR
 CODE COMPLIANCE.
  
 1} KITCHEN COUNTERTOP RECEPTACLE PER
 210.52(C)(1), 210.8(A)(6).
  
 2} POWDER ROOM RECEPTACLE PER 210.52(D),
 210.11(C)(3) AND 210.8(A)(1).
  
 3} THE GROUNDING ELECTRODE CONDUCTOR
 DOES NOT MEET THE MINIMUM SIZE REQUIRED
 WHICH IS 1/0 CU PER 250.66.
  
 4} MISSING RECEPTACLES FOR WALL SPACE
 PER 210.52. SEE THE DEN AND BREAKFAST
 ROOM ON REVIEWED PLAN FOR EXAMPLE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-09-08 Cont ID  
Sent By dpalmer Date 2005-09-08 Time 17:05 Rev Time 0.50
Received By dpalmer Date 2005-09-08 Time 16:31 Sent To P
Notes
2005-09-08 00:00:00REDLINEDTHE FOLLOWING MISSING.
  
  
 210.52C1 FOR MISSING GFI ALONG KITCHEN
 COUNTERSPACE.
 210.52D,210.11C3,210.8 FOR MISSING GFI
 IN PWDR RM.
 210.52 FOR MISSING RECETPS FOR WALL
 SPACE.
 250.66,310.15B6 FOR MIN GROUNDING
 ELECTRODE CONDUCTOR. MIN 1/0.
  
 THE ABOVE SHOULD BE REVISED WITH ANY
 OTHER REVISIONS BEFORE ROUGH ELECTRICAL
 INSPECTION.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-16 Cont ID  
Sent By btrobaug Date 2005-05-16 Time 17:28 Rev Time 0.50
Received By btrobaug Date 2005-05-16 Time 17:17 Sent To M
Notes
2005-05-16 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE THE LOCATION OF PANEL "B".
  
 2} INDICATE LOCATION OF OVERCURRENT
 PROTECTION FOR PANELS "A" & "B".
  
 3} THE OCP FOR CIRCUITS 12,13 PANEL "A",
 12,13,14,15 PANEL "B" IS TOO LARGE FOR
 THE CONDUCTORS PER 210.16.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-05-06 Cont ID  
Sent By adarroug Date 2006-05-06 Time 14:50 Rev Time 0.00
Received By adarroug Date 2006-05-06 Time 14:50 Sent To E
Notes
2006-05-06 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-03-09 Cont ID  
Sent By adarroug Date 2006-03-09 Time 15:51 Rev Time 0.00
Received By adarroug Date 2006-03-09 Time 15:51 Sent To E
Notes
2006-03-09 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-03-06 Cont ID  
Sent By adarroug Date 2006-03-06 Time 09:18 Rev Time 0.00
Received By adarroug Date 2006-03-06 Time 09:18 Sent To E
Notes
2006-03-06 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-02-21 Cont ID  
Sent By adarroug Date 2006-02-21 Time 08:32 Rev Time 0.00
Received By adarroug Date 2006-02-21 Time 08:32 Sent To E
Notes
2006-02-21 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-06 Cont ID  
Sent By adarroug Date 2005-09-06 Time 15:26 Rev Time 0.00
Received By adarroug Date 2005-09-06 Time 15:26 Sent To E
Notes
2005-09-06 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-16 Cont ID  
Sent By adarroug Date 2005-05-16 Time 08:34 Rev Time 0.00
Received By adarroug Date 2005-05-16 Time 08:34 Sent To E
Notes
2005-05-16 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-06 Cont ID  
Sent By rmcdouga Date 2005-06-03 Time 15:47 Rev Time 0.00
Received By adarroug Date 2005-05-06 Time 14:45 Sent To  
Notes
2005-05-06 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2005-09-12 Cont ID  
Sent By tgordon Date 2005-09-12 Time 13:48 Rev Time 0.20
Received By tgordon Date 2005-09-12 Time 13:48 Sent To B
Notes
2005-09-12 00:00:009-12-05 RECIVED ENERGY CALCULATIONS.
 MECH. CONTRACTOR TO SUPPLY MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-05-18 Cont ID  
Sent By prafter Date 2005-05-18 Time 07:42 Rev Time 0.50
Received By prafter Date 2005-05-18 Time 07:42 Sent To P
Notes
2005-05-18 00:00:00MECH. PLAN REVIEW:
  
 NO A/C PLAN OR EQUIPMENT INFORMATION.
  
 NO FL. ENERGY CALCULATIONS FOR
 BUILDING.
  
 COUSIN AIR INC. LISTED ON PERMIT APP.
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-09-10 Cont ID  
Sent By jleech Date 2005-09-10 Time 07:09 Rev Time 0.33
Received By jleech Date 2005-09-10 Time 07:09 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-05-26 Cont ID  
Sent By kstevens Date 2005-05-26 Time 08:19 Rev Time 0.50
Received By kstevens Date 2005-05-26 Time 08:19 Sent To B
Notes
2005-05-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHT A-7 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE, NOR DOES IT REFLECT THE
 FLOOR PLAN. PLEASE CORRECT THE
 FOLLOWING:
 A. THE GARAGE SINK SHALL NOT DRAIN
 THROUGH THE HORIZONTAL WET VENT OF THE
 BATHROOM FIXTURES. THIS SINK SHALL
 DISCHARGE DOWNSTREAM OF THE BATHROOM
 FIXTURES. SECTION 909.1
 B. THE CABANA BATH SHOWN ON THE FLOOR
 PLAN IS NOT SHOWN ON THE SANT. RISER
 DIAGRAM. SECTION 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2005-05-13 Cont ID  
Sent By mmclean Date 2005-05-13 Time 15:54 Rev Time 0.00
Received By mmclean Date 2005-05-13 Time 15:53 Sent To I
Notes
***NONE***