Plan Review Details - Permit 05050193
Plan Review Stops For Permit 05050193
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-08-26 Cont ID  
Sent By jwitmer Date 2005-08-26 Time 17:12 Rev Time 0.88
Received By jwitmer Date 2005-08-26 Time 16:23 Sent To FIRE
Notes
2005-08-26 00:00:00PERMIT: 05050193
 ADD: 2301 OKEECHOBEE BLVD
 CONT: ANDOVER CONST
 TEL: (561)756-2085
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2A) PROVIDE EITHER A SURVEY WITH
 IMPROVEMENTS OR A SITE PLAN WITH
 DIMENSIONS TO PROPERTY LINE. RESPONSE
 LETTER INDICATES THE SUBMITTAL OF SITE
 PLAN BUT NOT SUBMITTED.
  
 2B)FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
 SUBMITTED A SINGLE "COPY" OF A SOILS
 REPORT, 2 ORIGINAL SIGNED SEALED ARE
 REQUIRED.
  
 3) BLDG TYPE TABLE 500 & 600.BREAKDOWN
 OF SQ FT FOR EACH USE (MIXED OCCUPANCY)
 & TOTAL SQ FT OF BUILDING.PROVIDE MIN
 BUILDING TYPE DESIGN, IF AREA INCREASE
 WERE TAKEN INDICATE PROVIDE
 DOCUMENTATION. THIS CAN NOT BE
 DETERMINED WITHOUT USE OF A SITE PLAN.
  
 4) 1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOW
 B) STOREFRONT SYSTEMS
 C) EXTERIOR DOORS
 D) PANEL WALL SYSTEMS
 E) ROOFING ASSEMBLIES
 F) EXTERIOR HANDRAILS
  
 5) 11-4.3.8 CHANGES IN LEVEL. CHANGES IN
 LEVELS ALONG AN ACCESSIBLE ROUTE SHALL
 COMPLY WITH ?11-4.5.2.IF AN ACCESSIBLE
 ROUTE HAS CHANGES INLEVEL GREATER
 THAN 1/2 IN (13 MM), THEN A CURB RAMP,
 RAMP, ELEVATOR, OR PLATFORM LIFT (AS
 PERMITTED IN 11-4.1.3 AND 11-4.1.6)
 SHALL BE PROVIDED THAT COMPLIES WITH
 11-4.7, 11-4.8, 11-4.10, OR 11-4.11,
 RESPECTIVELY. AN ACCESSIBLE ROUTE DOES
 NOT INCLUDE STAIRS, STEPS, OR
 ESCALATORS.SEEDEFINITION OF "EGRESS,
 MEANS OF" IN 11-3.5 (SEE FIGURE 11-7(C)
 AND FIGURE 11-7(D)).PROVIDE VERTICAL
 ACCESSIBILITY.
 11-4.1.5 ACCESSIBLE BUILDINGS:
 ADDITIONS. EACH ADDITION TO AN EXISTING
 BUILDING OR FACILITY SHALL BE REGARDED
 AS AN ALTERATION.EACH SPACE OR
 ELEMENT ADDED TO THE EXISTING BUILDING
 OR FACILITY SHALL COMPLY WITH THE
 APPLICABLE PROVISIONS OF 11-4.1.1 TO
 11-4.1.3, MINIMUM REQUIREMENTS(FOR
 NEW CONSTRUCTION) AND THE APPLICABLE
 TECHNICAL SPECIFICATIONS OF
 11-4.2 THROUGH 11-4.35 AND 11-5
 THROUGH 11-10.EACH ADDITION THAT
 AFFECTS OR COULD AFFECT THE USABILITY OF
 AN AREA CONTAINING A PRIMARY FUNCTION
 SHALL COMPLY WITH 11-4.1.6(2).
 PROVIDE SITE PLAN.
  
 6)ENTRY'S TO COMPLY WITH11-4.1.6(H) IF
 A PARTICULAR ENTRANCE IS NOT MADE
 ACCESSIBLE, APPROPRIATE ACCESSIBLE
 SIGNAGE INDICATING THE LOCATION OF THE
 NEAREST ACCESSIBLE ENTRANCE(S) SHALL BE
 INSTALLED AT OR NEAR THE INACCESSIBLE
 ENTRANCE, SUCH THAT A PERSON WITH
 DISABILITIES WILL NOT BE REQUIRED TO
 RETRACE THE APPROACH ROUTE FROM THE
 INNACCESSIBLE ENTRANCE.PROVIDE SITE PLAN
  
  
 7) THE NEW ENTRY EAST SIDE TO COMPLY
 WITH 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL. REQUIRES 18" CLEAR ON THE
 PULL SIDE OF DOOR.
  
 8)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-26 Cont ID  
Sent By pschmitz Date 2005-06-27 Time 06:56 Rev Time 2.22
Received By jwitmer Date 2005-06-26 Time 07:48 Sent To P
Notes
2005-06-26 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05050193
 ADD: 2301 OKEECHOBEE BLVD
 CONT: ANDOVER CONST
 TEL: (561)756-2085
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2A) PROVIDE EITHER A SURVEY WITH
 IMPROVEMENTS OR A SITE PLAN WITH
 DIMENSIONS TO PROPERTY LINE.
  
 2B)FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3A) BLDG TYPE TABLE 500 & 600.BREAKDOWN
 OF SQ FT FOR EACH USE (MIXED OCCUPANCY)
 & TOTAL SQ FT OF BUILDING.PROVIDE MIN
 BUILDING TYPE DESIGN, IF AREA INCREASE
 WERE TAKEN INDICATE PROVIDE
 DOCUMENTATION.
  
 4A) WITH THE ABOVE AN UNKNOWN THIS
 REVIEW WILL BE COMPLETED AAS A TYPE V
 UNPROTECTED STRUCTURE. THE CRITEREA MAY
 CHANGE WITH ADDITIONAL INFORMATION,
 REQUIRING ADDITONAL COMMENTS.
 3401.7.1.1.3 WHERE THE EXISTING BUILDING
 AND THE ADDITION ARE NOT SEPARATED BY A
 FIRE WALL AND THE AREA OF THE ADDITION
 IS LESS THAN 25 PERCENT OF THE AREA OF
 THE EXISTING BUILDING, THE ADDITION
 SHALL CONFORM TO ALL REQUIREMENTS OF
 THIS CODE APPLICABLE TO THE BUILDING
 OF THE COMBINED AREA OF THE EXISTING
 BUILDING AND THE ADDITION; AND THE
 EXISTING BUILDING SHALL CONFORM TO THE
 REQUIREMENTS OF THIS CODE APPLICABLE TO
 FACILITIES FOR MEANS OF EGRESS AND
 AUTOMATIC FIRE EXTINGUISHING SYSTEMS FOR
 A BUILDING OF THE COMBINED AREA OF THE
 ADDITION AND EXISTING BUILDING.
  
 4B) DEPENDING ON INFORMATION THAT WILL
 BE RECEIVED ABOVE A3 INDICATES THE USE
 OF 5/8" PLYWOOD AS A PART OF THE
 EXTERIOR WALL. TYPE V BUILDINGS
 NONCOMBUSTIBLE WALLS.
  
  
 5) FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 6) 1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOW
 B) STOREFRONT SYSTEMS
 C) EXTERIOR DOORS
 D) PANEL WALL SYSTEMS
 E) ROOFING ASSEMBLIES
 F) EXTERIOR HANDRAILS
  
 7) 11-4.3.8 CHANGES IN LEVEL. CHANGES IN
 LEVELS ALONG AN ACCESSIBLE ROUTE SHALL
 COMPLY WITH ?11-4.5.2.IF AN ACCESSIBLE
 ROUTE HAS CHANGES INLEVEL GREATER
 THAN 1/2 IN (13 MM), THEN A CURB RAMP,
 RAMP, ELEVATOR, OR PLATFORM LIFT (AS
 PERMITTED IN ?11-4.1.3 AND ?11-4.1.6)
 SHALL BE PROVIDED THAT COMPLIES WITH
 ?11-4.7, ?11-4.8, ?11-4.10, OR ?11-4.11,
 RESPECTIVELY. AN ACCESSIBLE ROUTE DOES
 NOT INCLUDE STAIRS, STEPS, OR
 ESCALATORS.SEEDEFINITION OF "EGRESS,
 MEANS OF" IN ?11-3.5 (SEE FIGURE 11-7(C)
 AND FIGURE 11-7(D)).PROVIDE VERTICAL
 ACCESSIBILITY.
 11-4.1.5 ACCESSIBLE BUILDINGS:
 ADDITIONS. EACH ADDITION TO AN EXISTING
 BUILDING OR FACILITY SHALL BE REGARDED
 AS AN ALTERATION.EACH SPACE OR
 ELEMENT ADDED TO THE EXISTING BUILDING
 OR FACILITY SHALL COMPLY WITH THE
 APPLICABLE PROVISIONS OF 11-4.1.1 TO
 11-4.1.3, MINIMUM REQUIREMENTS(FOR
 NEW CONSTRUCTION) AND THE APPLICABLE
 TECHNICAL SPECIFICATIONS OF
 11-4.2 THROUGH 11-4.35 AND 11-5
 THROUGH 11-10.EACH ADDITION THAT
 AFFECTS OR COULD AFFECT THE USABILITY OF
 AN AREA CONTAINING A PRIMARY FUNCTION
 SHALL COMPLY WITH 11-4.1.6(2).
  
 8)ENTRY'S TO COMPLY WITH11-4.1.6(H) IF
 A PARTICULAR ENTRANCE IS NOT MADE
 ACCESSIBLE, APPROPRIATE ACCESSIBLE
 SIGNAGE INDICATING THE LOCATION OF THE
 NEAREST ACCESSIBLE ENTRANCE(S) SHALL BE
 INSTALLED AT OR NEAR THE INACCESSIBLE
 ENTRANCE, SUCH THAT A PERSON WITH
 DISABILITIES WILL NOT BE REQUIRED TO
 RETRACE THE APPROACH ROUTE FROM THE
 INNACCESSIBLE ENTRANCE.
  
 9) THE NEW ENTRY EAST SIDE TO COMPLY
 WITH 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL. REQUIRES 18" CLEAR ON THE
  
 PULL SIDE OF DOOR.
  
 10) A-1 HANDRAIL DETAIL INDICATE A
 MINIMUM OF 1 1/2" AWAY FROM THE WALL,
 THIS IS AN ABSOLUTE 1 1/2".
 11-4.26.2 SIZE AND SPACING OF GRAB BARS
 AND HANDRAILS. THE DIAMETER OR WIDTH OF
 THE GRIPPING SURFACES OF A HANDRAIL OR
 GRAB BAR SHALL BE 1-1/4 IN. TO 1-1/2 IN.
 (32 MM TO 38 MM), OR THE SHAPE SHALL
 PROVIDE ANEQUIVALENT GRIPPING SURFACE.
 IF HANDRAILS OR GRAB BARS ARE MOUNTED
 ADJACENT TO A WALL, THE SPACE BETWEEN
 THE WALL AND THE GRAB BAR SHALL BE
 1-1/2 IN. (38 MM) (SEE FIGURE 11-39(A),
 FIGURE 11-39(B), FIGURE 11-39(C),
 AND FIGURE 11-39(E)
  
 11)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-08-18 Cont ID  
Sent By dpalmer Date 2005-08-18 Time 06:47 Rev Time 0.30
Received By dpalmer Date 2005-08-18 Time 06:47 Sent To  
Notes
2005-08-18 00:00:00*********** UNSAT 2ND REVEIEW *********
  
 1)NOTE: PLEASE SEE NOTES FROM PREVIOUS
 REVIEW.
 PLEASE SEE NO NEW ELECTRICAL PLANS
 SUBMITTED FOR ELECTRICAL COMMENTS?
  
 2)NOTE: PLEASE SEE AS REQUESTED ON
 PREVIOUS REVIEW, ALL OLD/VOIDED SHEETS
 ARE TO BE REMOVED FROM SETS AND ONLY NEW
 REVISED SHEETS ARE TO BE INSERTED INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SEE NEW REVISED SHEETS WERE NOT
 INSERTED INTO SETS.
 WHEN OLD/VOIDED SHEETS ARE REMOVED, ONE
 SET OOF OLD/VOIDED SHEETS SHOULD
 ACCOMPANY NEW SETS WHEN RE-SUBMITTING.
  
  
 3)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) ATTACHED WITHRESPECT TO
 DESIGN PROFESSIONAL AND PLANS WITH
 REPEAT COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-15 Cont ID  
Sent By dpalmer Date 2005-06-15 Time 18:49 Rev Time 0.33
Received By dpalmer Date 2005-06-15 Time 18:49 Sent To  
Notes
2005-06-15 00:00:00************UNSAT ***********
  
 1)NOTE: PLEASE SEE PERMIT APPLICATION
 DISCRIPTION MENTIONS AN ADDITON OF AN
 EXTERIOR SLAB?
 PLEASE UNDERSTAND THAT DUE TO THE
 DISCRIPTION, THIS PERMIT WAS OPENED AS A
 MISC PERMIT TYPE, WHEN INFACT THIS
 SHOULD HAVE BEEN OPENED AS A COMMERCIAL
 PERMIT. A FIRE REVIEW HAS SINCE BEEN
 ADDED AND PERMIT TYPE WILL NEED TO BE
 CHANGED.
  
 2)NOTE: PLEASE SEE PLANS SUBMITTED DOES
 NOT MATCH APPLICATION FOR SCOPE PF WORK
 TO BE DONE.
 PLEASE SEE BLSG REVIEW COMMENTS FOR
 STOREFRONT AREA, PRODUCT APPROVALSETC.
  
 3)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS FOR NEW EELCTRICAL AND CORRELATE
 WITH A PANEL SCHEDULE TO BE SUBMITTED.
 215.5
 PLEASE SEE 700.12E FOR CIRCUITING OF
 EM/EXT LTS.
  
 PLEASE BE SURE TO ANY COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-08-30 Cont ID  
Sent By mcarsill Date 2005-08-30 Time 08:19 Rev Time 0.00
Received By mcarsill Date 2005-08-30 Time 08:19 Sent To  
Notes
2005-08-30 00:00:001. ENSURE THAT EMERGENCY LIGHTS ARE
 PROVIDED FOR THE INTERIOR DISPLAY AREA.
  
 2. BUILDING ADDRESS REQUIRED. A MINIMUM
 OF AT LEAST 6" HIGH NUMBERS ARE
 REQUIRED.
  
 THE EXISTING AND NEW PORTION SHALL
 COMPLY WITH ALL APPLICABLE BUILDING AND
 FIRE CODE REGULATIONS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER.
 (561) 804-4709

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-06-20 Cont ID  
Sent By mcarsill Date 2005-06-20 Time 10:59 Rev Time 0.00
Received By mcarsill Date 2005-06-20 Time 10:59 Sent To  
Notes
2005-06-20 00:00:001. BUILDING ADDRESS REQUIRED ON PROPER
 ELEVATION. MINIMU OF AT LEAST 6" HIGH
 NUMBERS ARE REQUIRED.
  
 2. PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR ALL HANDRAILS AND
 GUARDRAILS.
  
 3. PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION FOR NEW SUSPENDED
 CEILING.
  
 4. PLEASE EXPLAIN OUTDOOR STORAGE
 AREA.
  
 MIKE CARSILLO, FIRE MARSHAL
 835-237

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-16 Cont ID  
Sent By adarroug Date 2005-08-16 Time 16:46 Rev Time 0.00
Received By adarroug Date 2005-08-16 Time 16:46 Sent To  
Notes
2005-08-17 00:00:00TO "COMM" BD#52
2005-08-16 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-14 Cont ID  
Sent By shill Date 2005-06-14 Time 14:28 Rev Time 0.00
Received By shill Date 2005-06-14 Time 14:28 Sent To  
Notes
2005-06-15 00:00:00COMM BOARD 34
2005-06-14 00:00:00WAITING FOR COMM BOARD
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-06 Cont ID  
Sent By adarroug Date 2005-05-06 Time 12:57 Rev Time 0.00
Received By adarroug Date 2005-05-06 Time 12:57 Sent To Z
Notes
2005-05-06 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-06-27 Cont ID  
Sent By pschmitz Date 2005-06-21 Time 14:41 Rev Time 0.00
Received By pschmitz Date 2005-06-21 Time 14:33 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-06-20 Cont ID  
Sent By mmclean Date 2005-05-17 Time 14:26 Rev Time 0.00
Received By jlong Date 2005-06-20 Time 08:29 Sent To  
Notes
2005-06-20 00:00:00APPLICANT HAS SATISFIED MINOR DSI
 REQUIREMENT.SUBMITTED PB CASE NO.
 1401A WHICH WAS APPROVED ON 6/17/05.
2005-05-17 00:00:00DENIED,
 1. MUST APPLY FOR A MINOR DSI AMEND.
 **APPROVED SITEPLAN HAVE BEEN ALTERED.**
  
 ANY QUESTIONS, PLEASE CALL JOSH LONG,
 PLANNER 822-1435