Plan Review Details - Permit 05050168
Plan Review Stops For Permit 05050168
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-03 Cont ID  
Sent By shill Date 2005-06-03 Time 08:29 Rev Time 3.00
Received By shill Date 2005-06-01 Time 17:31 Sent To  
Notes
2005-06-03 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.
  
 2.)FBC11-4.1.6(1)(F) ACCESSIBLE
 BUILDINGS, ALTERATIONS, VERTICAL
 ACCESSIBILITY REQUIRED.
  
 3.)PROVIDE THE REMAINING 2ND FLOOR
 LAYOUT SO THAT CODE COMPLIANCE CAN BE
 DETERMINED.INCLUDE SQUARE FOOTAGE.
  
 4.)SHOW THE TWO MEANS OF EGRESS FROM
 THE 2ND FLOOR, NOTE 1, SHEET 1 OF 3.
 PROVIDE AN EXITING PLAN.IF THIS
 STAIRWAY IS A REQUIRED MEANS OF EGRESS,
 SHOW COMPLIANCE WITH FBC1006 AND
 FBC1007.
  
 5.)ALL DOCUMENTS PREPARED BY AND
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD
 ARE TO BE SIGNED, SEALED ORIGINALS,
 FAC61G15-23.002.A PHOTOCOPY WAS
 SUBMITTED.
  
 6.)FBC1007.2, STAIRS REQUIRED TO BE
 ACCESSIBLE SHALL COMPLY WITH FBC11-4.9.
  
 7.)FIRST FLOOR PLAN SHOWS THE STAIR
 WIDTH AS 3?3 OUTSIDE DIMENSION, SECOND
 FLOOR PLAN SHOWS AS INSIDE DIMENSION.
 CLEARLY SHOW STAIR WIDTH AND FRAMING
 DIMENSIONS, FBC1007.6.
  
 8.)FBC1007.5.5, EXTENSIONS REQUIRED AT
 THE TOP AND BOTTOM OF STAIRS ARE NOT
 SHOWN.ALSO SEE FBC11 FIGURE 19,
 FBC11-4.9.4.
  
 9.)SHOW MANEUVERING CLEARANCE FOR
 DOORS, FBC11 FIGURE 25.
  
 10.)A H/C BATH IS SHOWN; SHOW
 COMPLIANCE FBC11.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-19 Cont ID  
Sent By dpalmer Date 2005-05-19 Time 06:04 Rev Time 0.25
Received By dpalmer Date 2005-05-19 Time 05:59 Sent To I
Notes
2005-05-19 00:00:00************ UNSAT ************
  
 1)NOTE: PLEASE SEE PLANS ARE PHOTOCOPY
 OF SIGNED AND SEALED PLANS.
 PLEASE SEE PER FBC 104.2.2, PLEASE ALSO
 SEE FS 481.221.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-05-27 Cont ID  
Sent By mwennerg Date 2005-05-27 Time 15:33 Rev Time 0.00
Received By mwennerg Date 2005-05-27 Time 15:33 Sent To  
Notes
2005-05-27 00:00:00****DENIED****
  
 PLEASE REFER TO ELECTRICAL PLANS REVIEW
 COMMENT IN REGARDS TO FBC AND FS
 REQUIREMENTS.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2951 OR 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-21 Cont ID  
Sent By shill Date 2005-06-04 Time 08:46 Rev Time 0.00
Received By shill Date 2005-05-05 Time 12:28 Sent To  
Notes
2005-05-17 00:00:00TO "COMM" BD#14
2005-05-05 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-06-04 Cont ID  
Sent By hmoser Date 2005-06-04 Time 09:45 Rev Time 0.00
Received By hmoser Date 2005-06-04 Time 09:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved