Plan Review Details - Permit 05050150
Plan Review Stops For Permit 05050150
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-11-30 Cont ID  
Sent By alange Date 2005-11-30 Time 16:44 Rev Time 0.25
Received By alange Date 2005-11-30 Time 16:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-11-22 Cont ID  
Sent By alange Date 2005-11-22 Time 15:54 Rev Time 0.66
Received By alange Date 2005-11-22 Time 15:54 Sent To  
Notes
2005-11-22 00:00:00DENIED
  
 1.BUILDING REVIEW OK.
  
 2.SUBMIT TWO COPIES OF PLANS FOR
 REVIEW.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-05-19 Cont ID  
Sent By alange Date 2005-05-19 Time 15:38 Rev Time 2.00
Received By alange Date 2005-05-19 Time 12:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-11-30 Cont ID  
Sent By dpalmer Date 2005-11-30 Time 16:00 Rev Time 0.00
Received By dpalmer Date 2005-11-30 Time 16:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-11-30 Cont ID  
Sent By dpalmer Date 2005-11-30 Time 08:17 Rev Time 0.00
Received By dpalmer Date 2005-11-30 Time 08:17 Sent To  
Notes
2005-11-30 00:00:00** UNSAT 2ND REVIEW **
  
 1)NOTE: PLEASE SEE NEW SHEET IS NOW
 SUBMITTED WITH CORRECTIONS OF REDLINES,
 HOWEVER PLEASE SEE ONLY ONE COPYWAS
 SUBMITTED FOR REVIEW AND STAMPING.
 PLEASE SUBMIT TWO COPIES OF PLANS.
  
  
 IF THERE ARE ANYQUESTIONS, PLEASE
 CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-05-18 Cont ID  
Sent By dpalmer Date 2005-05-18 Time 18:31 Rev Time 0.25
Received By dpalmer Date 2005-05-18 Time 18:25 Sent To I
Notes
2005-05-18 00:00:00********* PLANS REDLINED **********
  
 1)NOTE: PLEASE SEE OCP FOR 5KW HEAT IS
 SHOWN AT 20A'S WITH A 24A CONNECTED
 LOAD. PLEASE SEE 424.3B WHICH REQUIRED
 OCP TO BE A MIN OF 125%.
 THIS WAS REDLINED AND PLANS DO NOT NEED
 TO BE REVISED, HOWEVER IF PLANS COME
 BACK FOR ANY OTHER COMMENTS OR REVSIONS,
 PLEASE CORRECT AT THAT TIME.
  
 ***************************************

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-12-02 Cont ID  
Sent By mwennerg Date 2005-12-02 Time 15:22 Rev Time 0.00
Received By mwennerg Date 2005-12-02 Time 15:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-05-20 Cont ID  
Sent By mwennerg Date 2005-05-20 Time 13:52 Rev Time 0.00
Received By mwennerg Date 2005-05-20 Time 13:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-11-09 Cont ID  
Sent By adarroug Date 2005-11-09 Time 13:53 Rev Time 0.00
Received By adarroug Date 2005-11-09 Time 13:53 Sent To  
Notes
2005-11-22 00:00:00TO "COMM" BD#20
2005-11-09 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-17 Cont ID  
Sent By shill Date 2005-06-17 Time 07:46 Rev Time 0.00
Received By shill Date 2005-06-17 Time 07:46 Sent To PC
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-17 Cont ID  
Sent By shill Date 2005-06-17 Time 07:47 Rev Time 0.00
Received By shill Date 2005-05-04 Time 16:09 Sent To PC
Notes
2005-05-17 00:00:00TO "COMM" BD#27
2005-05-04 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-12-08 Cont ID  
Sent By pkrauss Date 2005-12-08 Time 06:50 Rev Time 0.35
Received By pkrauss Date 2005-12-08 Time 06:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-06-08 Cont ID  
Sent By pkrauss Date 2005-06-08 Time 10:34 Rev Time 0.40
Received By pkrauss Date 2005-06-08 Time 10:31 Sent To  
Notes
2005-06-08 00:00:00DENIED:
 1.PROVIDE DETAIL FOR THE CONDENSING
 UNIT RACK.
  
 2.INDICATE ELEVATION OF THE CONDESING
 UNIT.PER 2001 FBC(M)306.5, EQUIPMENT
 LOCATED AT A HEIGHT GREATER THAN 16 FT
 REQUIRE PERMANENT MEANS OF ACCESS.
  
 3.PROVIDE CLEARANCES BETWEEN THE
 CONDESING UNIT & THE EXTERIOR WALL.
 REFERENCE MANUFACTURER INSTALLATION
 INSTRUCTIONS FOR REQUIRED CLEARANCE.
 PLEASE NOTE, PER 2001 FBC(M)306.1,
 CLEARANCES AROUND EQUIPMENT INCLUDING
 OTHER INSTALLED EQUIPMENT (THE
 DISCONNECT).CLEARANCE SHALL BE
 SUFFICIENT TO ALLOW INSPECTION, SERVICE
 OR REPLACEMENT WITHOUT REMOVING ELEMENTS
 OF PERMANENT CONSTRUCTION.
  
 4.PLAN INDICATES FRESH AIR INTAKE 3 FT
 FROM THE CONDENSING UNIT IN WHICH THE
 FAN IS EXHAUSTING HEAT.THIS AIR SHOULD
 NOT BE RECIRCULATED PER 2001 FBC(M)
 501.3 & 401.5.1.PLEASE NOTE, THE
 OPENING LOCATION SHALL BE A MINIMUM OF
 10 FT FROM PARKING LOTS, STREETS OR
 ALLEYS.
  
 5.PROVIDE DETAIL FOR THE HANGING OF
 THE AHU.
  
 6.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001
 FBC(M)307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-12-08 Cont ID  
Sent By pschmitz Date 2005-12-08 Time 07:16 Rev Time 0.00
Received By pschmitz Date 2005-12-08 Time 07:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-06-17 Cont ID  
Sent By pschmitz Date 2005-06-17 Time 07:04 Rev Time 0.00
Received By pschmitz Date 2005-06-17 Time 07:04 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2005-12-08 Cont ID  
Sent By mmclean Date 2005-12-08 Time 14:45 Rev Time 0.00
Received By mmclean Date 2005-12-08 Time 14:45 Sent To M
Notes
2005-12-08 00:00:00DENIED,
 1. MUST PROVIDE TWO CURRENT COPY OF
 SURVEY OR SITEPLAN SHOWING THE LOCATION
 OF THE UNIT (A/C)
  
 NOTE: A/C UNIT CAN ONLY ENCROACH 4FT
 INTO A SETBACK.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2005-06-08 Cont ID  
Sent By mmclean Date 2005-06-08 Time 11:52 Rev Time 0.00
Received By mmclean Date 2005-06-08 Time 11:52 Sent To  
Notes
2005-06-08 00:00:00DENIED,
 1. NEED TO PROVIDE TWO COPY OF UPDATED
 SURVEY SHOWING THE LOCATION OF THE CM
 WALL TO COVER THE A/C
  
 MICHELLE MCLEAN
 ZONING TECHICIAN
 805-6720