Plan Review Details - Permit 05050117
Plan Review Stops For Permit 05050117
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-06-19 Cont ID  
Sent By alange Date 2006-06-19 Time 15:36 Rev Time 0.33
Received By alange Date 2006-06-19 Time 15:36 Sent To  
Notes
2006-06-19 00:00:00ENERGY CALC REV OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-08-29 Cont ID  
Sent By alange Date 2005-08-29 Time 13:39 Rev Time 2.00
Received By alange Date 2005-08-25 Time 07:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-07-26 Cont ID  
Sent By btrobaug Date 2005-08-23 Time 07:12 Rev Time 1.50
Received By alange Date 2005-07-26 Time 11:17 Sent To  
Notes
2005-07-26 00:00:00DENIED
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS WITH QUALITY ASSURANCE FOR THE
 FOLLOWING.STRAPS AND TIE-DOWNS,
 HARDIE PLANK SIDING AND LINTELS.
 ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING STATE APPROVAL TO BE ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6.SUBMIT ENERGY CALCS FORM 600C
 FBC CHAPTER 13
  
  
 9. SUBMIT FIRE RESTISTANT RATINGS FOR
 THE FOLLOWING DOORS AND WINDOWS.
 FBC 1006.2.4 EXTERIOR STAIRS SHALL
 BE SEPARATED FROM THE INTERIOR OF THE
 BUILDING BY WALLS WITH A FIRE
 RESISTANCE RATING OF NOT LESS THAN 1
 HOUR,
 WITH FIXED OR SELF-CLOSING OPENING
 PROTECTIVES AS REQUIRED FOR ENCLOSED
 STAIRS.THIS PROTECTION SHALL EXTEND
 VERTICALLY FROM THE GROUND TO A
 POINT 10 FT (3048 MM) ABOVE THE
 TOPMOST LANDING OR THE ROOF LINE,
 WHICHEVER IS LOWER, AND HORIZONTALLY
 10 FT (3048 MM) FROM EACH SIDE OF
 THE STAIRWAY.OPENINGS WITHIN THE 10
 FT (3048 MM) HORIZONTAL EXTENSION
 OF THE PROTECTED WALLS BEYOND THE
 STAIRWAY SHALL BE EQUIPPED WITH FIXED
 3/4 HOUR ASSEMBLIES.
  
 10.FBC 104.2.1 ALL INFORMATION,
 DRAWINGS AND SPCIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME
 AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-14 Cont ID  
Sent By alange Date 2005-06-14 Time 13:29 Rev Time 2.00
Received By alange Date 2005-06-14 Time 11:23 Sent To  
Notes
2005-06-14 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.SHOW SQUARE FOOTAGE ON PLAN. SHOW
 NEW AND EXISTING A/C AREAS AND OTHER
 AREAS.
  
 4.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS WITH QUALITY ASSURANCE FOR THE
 FOLLOWING.ROOFING, STRAPS AND
 TIE-DOWNS, HARDIE PLANK SIDING, IMPACT
 PROTECTION, LINTELS, EXTERIOR DOORS AND
 WINDOWS.
 ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING STATE APPROVAL TO BE ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5.SAFTEY GLAZING REQUIRED AT TUB
 LOCATIONS. FBC 2405.2.1.
  
 6.SUBMIT ENERGY CALCS FORM 600C
  
 7.SMOKE DETECTOR REQUIRED AT FIRST
 FLOOR STAIRS. FBC 905.2.2
  
 8.SHOW METHOD OF ATTIC VENTILATION
 FBC 2309.7.2
  
 9.FBC 1006.2.4 EXTERIOR STAIRS SHALL
 BE SEPARATED FROM THE INTERIOR OF THE
 BUILDING BY WALLS WITH A FIRE
 RESISTANCE RATING OF NOT LESS THAN 1
 HOUR,
 WITH FIXED OR SELF-CLOSING OPENING
 PROTECTIVES AS REQUIRED FOR ENCLOSED
 STAIRS.THIS PROTECTION SHALL EXTEND
 VERTICALLY FROM THE GROUND TO A
 POINT 10 FT (3048 MM) ABOVE THE
 TOPMOST LANDING OR THE ROOF LINE,
 WHICHEVER IS LOWER, AND HORIZONTALLY
 10 FT (3048 MM) FROM EACH SIDE OF
 THE STAIRWAY.OPENINGS WITHIN THE 10
 FT (3048 MM) HORIZONTAL EXTENSION
 OF THE PROTECTED WALLS BEYOND THE
 STAIRWAY SHALL BE EQUIPPED WITH FIXED
 3/4 HOUR ASSEMBLIES.
  
 10.FBC 104.2.1 ALL INFORMATION,
 DRAWINGS AND SPCIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME
 AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-05-25 Cont ID  
Sent By btrobaug Date 2006-05-25 Time 17:28 Rev Time 0.50
Received By btrobaug Date 2006-05-22 Time 06:45 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-08-23 Cont ID  
Sent By btrobaug Date 2005-08-23 Time 07:12 Rev Time 0.50
Received By btrobaug Date 2005-08-23 Time 06:57 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-07-18 Cont ID  
Sent By btrobaug Date 2005-07-18 Time 17:27 Rev Time 0.50
Received By btrobaug Date 2005-07-18 Time 14:08 Sent To P
Notes
2005-07-18 00:00:00ALL INFORMATION/DRAWINGS/SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPON-
 SIBLE FOR THE DESIGN. SECTION 104.2.1
 COMMENT WAS ON THE PREVIOUS REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-19 Cont ID  
Sent By btrobaug Date 2005-05-19 Time 11:37 Rev Time 0.50
Received By btrobaug Date 2005-05-19 Time 10:38 Sent To M
Notes
2005-05-17 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
  
 1} THE APPLICATION CONTAINS THE WRONG
 ADDRESS, OWNER INFORMATION AND PCN
 NUMBER NOT FILLED IN. ALSO THE SQUARE
 FOOTAGE WAS LEFT BLANK.PLEASE COMPLETE
 PROPERLY.
  
 2} THE DESIGNER OF RECORD MUST PRINT AND
 SIGN NAME ON PLANS PER 104.2.1. FBC.
  
 3} PLEASE PROVIDE A RISER DIAGRAM, LOAD
 CALCULATIONS AND PANEL SCHEDULES. 215.5.
  
 4} A SMOKE DETECTOR MUST BE ADDED AT THE
 STAIR ON THE 1ST.FLOOR PER 905.2.2 FBC.
  
 5} A RECEPTACLE MUST BE ADDED IN THE
 LIVING ROOM PER 210.52.
  
 6} THE FEED FOR THE SPA TUB MUST BE GFI
 PROTECTED PER 680.43(A)(3).
  
 7} INDICATE THE FOLLOWING REGARDING THE
 GARAGE/ GUEST BUILDING.
 A)THE PANEL LOCATION.
 B) THE DISCONNECTING MEANS PER 225.31 &
 32.
 C) GROUNDING PER 250.32.
 D) THE BATH RECEPTACLE MUST BE GFI. 210
 8(A)(1).
 NOTE:THE GARAGE OR ART STUDIO ON THE
 FIRST FLOOR MUST COMPLY WITH GFI
 REQUIREMENT OF 208 OR SPACING
 REQUIREMENTS OF 210.52. THE RECEPTACLES
 ON THIS PLAN COMPLY WITH NEITHER.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-07-18 Cont ID  
Sent By adarroug Date 2005-07-18 Time 09:34 Rev Time 0.00
Received By adarroug Date 2005-07-18 Time 09:34 Sent To E
Notes
2005-07-18 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-06 Cont ID  
Sent By adarroug Date 2005-07-06 Time 10:15 Rev Time 0.00
Received By adarroug Date 2005-07-06 Time 10:15 Sent To Z
Notes
2005-07-06 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-13 Cont ID  
Sent By adarroug Date 2005-05-13 Time 16:22 Rev Time 0.00
Received By adarroug Date 2005-05-13 Time 16:22 Sent To E
Notes
2005-05-13 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-14 Cont ID  
Sent By alange Date 2005-06-14 Time 13:54 Rev Time 0.00
Received By alange Date 2005-05-03 Time 18:23 Sent To  
Notes
2005-05-03 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-05-20 Cont ID  
Sent By prafter Date 2005-05-20 Time 08:15 Rev Time 0.75
Received By prafter Date 2005-05-20 Time 08:15 Sent To P
Notes
2005-05-20 00:00:00MECH. PLAN REVIEW:
  
  
 FL. ENERGY CALCULATIONS REPORT MUST BE
 SUBMITED, 600C FORM.
  
 A/C CONTRACTOR TO SUBMIT A/C PLANS AND
 EQUIPMENT INFORMATION AT PERMIT TIME.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-07-25 Cont ID  
Sent By jleech Date 2005-07-25 Time 13:12 Rev Time 0.33
Received By jleech Date 2005-07-25 Time 13:12 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-05-25 Cont ID  
Sent By kstevens Date 2005-05-25 Time 18:37 Rev Time 0.85
Received By kstevens Date 2005-05-25 Time 18:37 Sent To B1
Notes
2005-05-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 A. SHT A-3 OF 6 SANITARY RISER DIAGRAM
 DOES NOT REFLECT THE FLOOR PLAN, NOR
 DOES IT MEET CODE REQUIREMENTS. THE
 FOLLOWING CORRECTIONS TO RISER WILL BE
 REQUIRED:
 1. POWDER ROOM NOT SHOWN ON RISER.
 SECTION 104.2.1.
 2. KITCHEN SINK NOT VENTED. SECTIONS
 901.2.1 & 908.3
 3. WASH MACHINE SHALL BE SHOWN TO THE
 RIGHT AND DOWNSTREAM OF BATH ROOM.
 SECTION 104.2.1.
 4. SHOWER MASTER BATH SHAL BE
 DOWNSTREAM OF THE WATER CLOSET.
 B. SHT A-1 OF 3 SANITARY RISER DIAGRAM
 DOES NOT REFLECT THE FLOOR PLAN, NOR
 DOES IT MEET CODE REQUIREMENTS. THE
 FOLLOWING CORRECTIONS TO RISER WILL BE
 REQUIRED.
 1. RISER SHOWS SHOWERS, BUT FLOOR PLAN
 SHOWS TUBS. SECTION 104.2.1.
 2. FIXTURES FROM 2ND FLOOR BATHROOM
 SHALL NOT DRAIN INTO THE VENT OF THE
 FIXTURES ON THE 1ST FLOOR. SECTION 908.3
 3. FIXTURE LAYOUT ON RISER DOES NOT
 REFLECT THE FIXTURE LAYOUT ON THE FLOOR
 PLAN. SECTION 104.2.1
 C. SEE ATTACHED SHEET FOR EXAMPLES OF
 RISER DIAGRAMS THAT REFLECT THE FLOOR
 PLAN AND MEET CODE REQUIREMENTS. THIS IS
 INFORMATIONAL ONLY.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2005-07-15 Cont ID  
Sent By mmclean Date 2005-07-15 Time 13:00 Rev Time 0.00
Received By mmclean Date 2005-07-15 Time 13:00 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-05-12 Cont ID  
Sent By mmclean Date 2005-05-12 Time 16:09 Rev Time 0.00
Received By mmclean Date 2005-05-12 Time 16:09 Sent To I
Notes
2005-05-12 00:00:00DENIED,
 1. MUST PROVIDE A SITEPLAN THAT SHOWS
 ALL THE SETBACKS
 (FRONT/SIDE/REAR/BUILDING SEPERATION).
 2. SITEPLAN MUST SHOW/INDICATE ALL THE
 NEW WORK.
 3. TRELLIS CANNOT BE BUILT IN THE FRONT
 SETBACK.NEED TO REMOVE FROM PLANS.
 4. NO TWO UNITS ARE ALLOWED.
 5. TWO BATHROOMS WILL BE CONSIDER TWO
 UNITS, MUST REMOVE ONE OF BATHROOM.
 6. NEED SHOW PARKING FOR THE UNIT IN
 BACK AND FRONT STRUCTURE (1 PARKING FOR
 ACCESSORY STRUCTURE AND TWO FOR THE
 FRONT STRUCTURE).
 7. MUST PROVIDE DIMENSION OF DRIVEWAY
 (WIDTH & LENGTH).
 8. NEED TO CHANGE DESCRIPTION OF THE
 TYPE OF UNIT ON THE PLANS FOR THE 2
 STORY (GARAGE/GUEST HOUSE). THE BELOW
 STRUCTURE DOORS ARE TOO SMALL FOR A
 GARAGE.
 9. THE NEW 2 STORY STRUCTURE IN REAR
 MUST MEET THE REAR & SIDE SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved