Plan Review Details - Permit 05050049
Plan Review Stops For Permit 05050049
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-07-14 Cont ID  
Sent By jleahy Date 2005-07-14 Time 09:07 Rev Time 1.00
Received By jleahy Date 2005-07-14 Time 09:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-06-10 Cont ID  
Sent By btrobaug Date 2005-06-10 Time 06:42 Rev Time 2.00
Received By btrobaug Date 2005-06-09 Time 14:31 Sent To PC
Notes
2005-06-10 00:00:00 
  
 GIVEN THE FACT THAT THE TRANSFORMER
 INSTALLATION ON THESE UNITS IS BEING
 PERMITTED AS A RETROFIT, AND THEREFORE
 BECOMES AN INTEGRAL PART OF THE
 EQUIPMENT, PLEASE PROVIDE A LISTING FROM
 A NATIONALLY RECOGNIZED TESTING
 LABORATORY WITH CUT SHEETS SHOWING
 ACCEPTABLE MOUNTING METHODS, HARDWARE,
 AND LOCATION ON THE UNIT.
  
 ALSO PLEASE PROVIDE THE DESIGNATION OF
 THE SPECIFIC UNITS INVOLVED, ALONG WITH
 THE PANEL DESIGNATION AND CIRCUIT
 NUMBERS FOR THE UNITS.
  
 RESUBMIT THIS ALONG WITH THE PREVIOUSLY
 SUBMITTED DRAWING AND SIGNED LETTER FOR
 REVIEW.
  
 IWILL REVIEW THESE ITEMS IMMEDIATELY
 UPON RESUBMITTAL IN AN ATTEMT TO PREVENT
 ANY FURTHER DELAY OF THIS ISSUE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2005-05-16 Cont ID  
Sent By dpalmer Date 2005-05-16 Time 10:04 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2005-05-16 00:00:00PLEASE SEE PERMIT DISCRIPTION, THIS CAN
 NOT BE A "FACTORY INSTALLED" CHANGED
 SYSTEM.
 IF PART OF FACTORY, THEJN ALL EQUIPMENT
 MUST BE RE-CERTIFIED BY THE NRTL.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-11 Cont ID  
Sent By btrobaug Date 2005-05-11 Time 17:21 Rev Time 0.33
Received By btrobaug Date 2005-05-11 Time 17:02 Sent To  
Notes
2005-05-11 00:00:00 
 THE "RETROFIT " NEEDS TO BE ENGINEERED
 (SIGNED AND SEALED) AND RESUBMITTED FOR
 REVIEW.553.79(6)(A) FAC.
 ALSO SUBMIT FACTORY SPECS INDICATING THE
 LISTING FOR MOUNTING THE TRANSFORMER ON
 THE UNIT.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-03 Cont ID  
Sent By adarroug Date 2005-05-03 Time 17:29 Rev Time 0.00
Received By adarroug Date 2005-05-03 Time 17:29 Sent To E
Notes
2005-05-03 00:00:00TO "E" BOX