Plan Review Details - Permit 05042221
Plan Review Stops For Permit 05042221
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status N Date 2005-08-17 Cont ID  
Sent By rmcdouga Date 2005-08-17 Time 10:55 Rev Time 0.00
Received By rmcdouga Date 2005-08-17 Time 10:55 Sent To  
Notes
2005-08-17 00:00:00THE STORM KEY PLAN AND INSTALLATION
 SCHEDULE SUBMITTED FOR THE STORM PANEL
 IS DENIED. THE PROVISO STATES THAT A
 SEPARATE PERMIT IS REQUIRED FOR THE
 STORM PANELS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-08-09 Cont ID  
Sent By rmcdouga Date 2005-08-09 Time 09:01 Rev Time 0.00
Received By rmcdouga Date 2005-08-09 Time 09:01 Sent To  
Notes
2005-08-09 00:00:00PROVISO
  
 1) THE POSITIVE PRESSURE LISTED ON THE
 PLANS FOR THE SMALL OVERHEAD GARAGE DOOR
 EXCEEDS THE POSITIVE DESIGN PRESSURE IN
 THE PRODUCT APPROVAL. SUBMIT PRODUCT
 APPROVAL WITH ADEQUATE DESIGN PRESSURES.
  
 2) SUBMITTAL FOR STORM PANELS IS
 INCOMPLETE. A SEPARATE PERMIT IS
 REQUIRED FOR THE STORM PANELS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-25 Cont ID  
Sent By rmcdouga Date 2005-05-25 Time 12:15 Rev Time 0.00
Received By rmcdouga Date 2005-05-25 Time 7:18 Sent To  
Notes
2005-05-25 00:00:00DENIED
  
 1) SUBMIT A COPY OF THE PAID RECEIPT FOR
 THE COUNTY IMPACT FEES.
  
 2) THE 2650 CASEMENT WINDOW IN BEDROOM
 #2 IS REQUIRED TO COMPLY WITH EMERGENCY
 EGRESS CLEAR OPENING SIZE. SEE FBC
 1005.4
  
 3) THE ANCHOR SCHEDULE ON A6 SPECIFIES
 USP THD210 HANGERS USING TAPCON
 FASTENERS. THESE CONNECTORS ARE NOT
 DESIGNED OR TESTED WITH THESE FASTENERS.
 PLEASE SPECIFY AN APPROPRIATE MASONRY
 HANGER.
  
 3) THE PRODUCT APPROVAL SUBMITTED FOR
 THE GLAZED FIBERGLASS DOOR IS LIMITED TO
 A HEIGHT OF 6'8". THE PLANS SPECIFY
 DOORS 8' IN HEIGHT. SUBMIT CORRECT
 PRODUCT APPROVAL.
  
 4) THE NOA SUBMITTED FOR THE SERIES 640
 CASEMENT WINDOWS WITH FL# 2766 DOES NOT
 HAVE THE CORRECT NOA NUMBER. SUBMIT THE
 NOA WITH THE NUMBER LISTED ON THE FL
 PRODUCT APPROVAL.
  
 5) SUBMIT THE MANUFACTURER'S SPECS. AND
 LISTING INFORMATION FOR THE ONE HOUR
 FIRE RATED GLASS BLOCK.
  
 6) SUBMIT THE FL PRODUCT APPROVAL AND
 INSTALLATION DRAWINGS FOR THE 6'X 8'
 OVER HEAD GARAGE DOOR.
  
 7) SUBMIT THE SBCCI EVALUATION REPORT
 FOR THE STORM PANELS.
  
 8) SUBMIT (2) COPIES OF A KEY PLAN AND
 AN INSTALLATION SCHEDULE FOR THE STORM
 PANELS. INDICATE THE MOUNT TYPE,
 FASTENERS, FASTENER SPACING, ETC.
  
 9) ADDITIONAL FEES ARE DUE FOR RADON AND
 INCREASE IN CALCULATED VALUE OF THE
 STRUCTURE.
  
 10) CONTRACTOR NEEDS TO UPDATE INSURANCE
 INFORMATION WITH THE CITY.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-03-10 Cont ID  
Sent By btrobaug Date 2006-03-10 Time 08:21 Rev Time 0.33
Received By btrobaug Date 2006-03-10 Time 08:20 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-03-10 Cont ID  
Sent By btrobaug Date 2005-12-21 Time 09:06 Rev Time 0.00
Received By btrobaug Date 2005-12-21 Time 06:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-07-20 Cont ID  
Sent By btrobaug Date 2005-07-20 Time 14:37 Rev Time 0.50
Received By btrobaug Date 2005-07-20 Time 14:37 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-10 Cont ID  
Sent By btrobaug Date 2005-05-10 Time 07:47 Rev Time 0.50
Received By btrobaug Date 2005-05-10 Time 07:26 Sent To M
Notes
2005-05-10 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE THE LOCATION OF PANEL "B".
  
 2} INDICATE LOCATION OF OVERCURRENT
 PROTECTION FOR PANELS "A" & "B".
  
 3} THE OCP FOR CIRCUITS 12,13 PANEL "A",
 12,13,14,15 PANEL "B" IS TOO LARGE FOR
 THE CONDUCTORS PER 210.16.
  
 4} BEDROOM #3 REQUIRES A RECEPTACLE FOR
 SPACING PER 210.52(A)(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-03-09 Cont ID  
Sent By adarroug Date 2006-03-09 Time 15:50 Rev Time 0.00
Received By adarroug Date 2006-03-09 Time 15:50 Sent To E
Notes
2006-03-09 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-12-20 Cont ID  
Sent By adarroug Date 2005-12-20 Time 09:30 Rev Time 0.00
Received By adarroug Date 2005-12-20 Time 09:30 Sent To E
Notes
2005-12-20 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-08-16 Cont ID  
Sent By adarroug Date 2005-08-16 Time 08:22 Rev Time 0.00
Received By adarroug Date 2005-08-16 Time 08:22 Sent To B
Notes
2005-08-16 00:00:00TO "RMCDOUGAL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-18 Cont ID  
Sent By adarroug Date 2005-07-18 Time 11:52 Rev Time 0.00
Received By adarroug Date 2005-07-18 Time 11:52 Sent To E
Notes
2005-07-18 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-09 Cont ID  
Sent By adarroug Date 2005-05-09 Time 10:52 Rev Time 0.00
Received By adarroug Date 2005-05-09 Time 10:52 Sent To E
Notes
2005-05-09 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-25 Cont ID  
Sent By rmcdouga Date 2005-05-25 Time 14:18 Rev Time 0.00
Received By rmcdouga Date 2005-04-29 Time 17:58 Sent To  
Notes
2005-04-29 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2005-07-23 Cont ID  
Sent By rregueir Date 2005-07-23 Time 08:59 Rev Time 0.00
Received By rregueir Date 2005-07-23 Time 08:59 Sent To B
Notes
2005-07-23 00:00:00NO A/C PLANS SUBMITTED WITH APPLICATION.
 TWO SETS OF ENERGY CALCULATIONS AND
 MANUAL J HAVE BEEN SUBMITTED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-05-16 Cont ID  
Sent By prafter Date 2005-05-16 Time 11:40 Rev Time 0.75
Received By prafter Date 2005-05-16 Time 11:40 Sent To P
Notes
2005-05-16 00:00:00MECH. PLAN REVIEW:
  
 NO A/C PLANS OR EQUIPMENT INFORMATION.
  
 COUSINS AIR INC. IS LISTED ON PERMIT
 APP.
  
 PAT RAFTERE 561/805/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-05-25 Cont ID  
Sent By rmcdouga Date 2005-05-25 Time 14:17 Rev Time 0.00
Received By rmcdouga Date 2005-05-25 Time 14:16 Sent To  
Notes
2005-05-25 00:00:00PASSED BY JOHN LEECH ON 5/17/05

Review Stop Z ZONING
Rev No 1 Status P Date 2005-05-06 Cont ID  
Sent By mmclean Date 2005-05-06 Time 18:39 Rev Time 0.00
Received By mmclean Date 2005-05-06 Time 18:39 Sent To I
Notes
***NONE***