Plan Review Details - Permit 05042220
Plan Review Stops For Permit 05042220
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-09-09 Cont ID  
Sent By alange Date 2005-09-09 Time 12:15 Rev Time 0.66
Received By alange Date 2005-09-09 Time 12:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-07-14 Cont ID  
Sent By alange Date 2005-07-14 Time 09:15 Rev Time 1.75
Received By alange Date 2005-07-14 Time 08:19 Sent To  
Notes
2005-07-14 00:00:00DENIED
  
 1.BUILDING IS OF TYPE 1 CONSTRUCTION.
 ALL WOOD USED TO BE FRT.PLEASE SHOW ON
 PLANS.
  
 2.SUBMIT FIRE RESITANT RATINGS FOR THE
 FOLLOWING.SIKA CARBODUR AND SIKADUR 30
 PRODUCTS.
  
 3.HEADROOM CLEARANCE ON STAIRS SHALL
 BE A MINIMUM OF 6FT 8INCHES. SEE A OF
 A/3 STAIR NUMBER 15. FBC1007.7
  
 4.ENGINEER SEALING PLANS SHALL HAVE
 HIS PRINTED NAME AND COMPANY NAME WITH
 LICENSE NUMBER ON PLANS. FAC 61G-16.004
  
 5.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-05-18 Cont ID  
Sent By alange Date 2005-05-18 Time 13:49 Rev Time 1.25
Received By alange Date 2005-05-18 Time 13:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-09-10 Cont ID  
Sent By dpalmer Date 2005-09-10 Time 22:29 Rev Time 0.30
Received By dpalmer Date 2005-09-10 Time 22:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-07-15 Cont ID  
Sent By dpalmer Date 2005-07-15 Time 17:10 Rev Time 0.30
Received By dpalmer Date 2005-07-14 Time 20:53 Sent To  
Notes
2005-07-15 00:00:00*********** UNSAT **********
  
  
 1)NOTE: PLEASE SEE COMPLETE SCOPE OF
 WORK HAS CHANGED, HOWEVER PLEASE SEE NO
 NEW ELECTRICAL PLANS/DRAWINGS WERE
 SUBMITTED.
  
 2)NOTE:PLEASE SEE 2002 NEC
 ,210.52,210.70 ETC FOR MIN REQUIRED.
  
 3)NOTE: PLEASE ALSO SEE NFPA-72
 8-1.4.1.6.2
  
 4)NOTE: PLEASE INCLUDE ANY NEW
 CIRCUITING AND CORRELATE WITH A PANEL
 SCHEDULE TO BE SUBMITTED.
  
 5)NOTE:PLEASE SEE NEW PLANS ALSO DO NOT
 INCLUDE ORIGINAL SCOPE OF WORK FOR
 ELECTRICAL, PLEASE CLARIFY AND SHOW WORK
 IS THAT WORK IS STILL IN SCOPE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-07-14 00:00:00IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-05-09 Cont ID  
Sent By dpalmer Date 2005-05-09 Time 13:15 Rev Time 0.25
Received By dpalmer Date 2005-05-09 Time 13:15 Sent To  
Notes
2005-05-09 00:00:00*** REDLINED GFI PROTECTION REQUIRED FOR
 FOUNTAIN PUMP.
 NEC 680.51A

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-09-14 Cont ID  
Sent By mwennerg Date 2005-09-14 Time 10:48 Rev Time 0.00
Received By mwennerg Date 2005-09-14 Time 10:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-08-04 Cont ID  
Sent By mwennerg Date 2005-08-04 Time 10:02 Rev Time 0.00
Received By mwennerg Date 2005-08-04 Time 10:02 Sent To  
Notes
2005-08-04 00:00:00******DENIED******
  
 1) PLEASE SEE BUILDING REVIEW COMMENT IN
 REGARDS TO MINIMUM HEADROOM REQUIREMENT
 FOR STAIRS. NOT LESS THAN 80". NFPA 101,
 SECTION 7.1.5.3.
  
 2) PLEASE SHOW LOCATION OF NEW OR
 EXISTING SMOKE DETECTORS.
  
 3) AS INDICATED ON LAST REVIEW, IF WORK
 IMPACTS FIRE SPRINKLER SYSTEM OR ANY
 OTHER LIFE SAFETY EQUIPMENT, SEPARATE
 SHOP DRAWINGS AND PERMITS WILL BE
 REQUIRED FOR REMODEL.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 804-4756
 PLAN REVIEW(561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-05-10 Cont ID  
Sent By mwennerg Date 2005-05-10 Time 14:21 Rev Time 0.00
Received By mwennerg Date 2005-05-10 Time 14:08 Sent To  
Notes
2005-05-10 00:00:001) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR THE FIRE ALARM AND FIRE
 SPRINKLER REMODELS IF APPLICABLE.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910 OR 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-08 Cont ID  
Sent By adarroug Date 2005-09-08 Time 18:46 Rev Time 0.00
Received By adarroug Date 2005-09-08 Time 18:46 Sent To  
Notes
2005-09-08 00:00:00TO "COMM" BD#49

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-06 Cont ID  
Sent By adarroug Date 2005-07-06 Time 15:39 Rev Time 0.00
Received By adarroug Date 2005-07-06 Time 15:39 Sent To  
Notes
2005-07-06 00:00:00TO "COMM" BD#30

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-04 Cont ID  
Sent By kstevens Date 2005-06-04 Time 16:16 Rev Time 0.00
Received By kstevens Date 2005-04-29 Time 17:05 Sent To  
Notes
2005-05-09 00:00:00TO "COMM" BD#41
2005-05-03 00:00:00IN INCOMING/AWAITING SPACE ON "COMM" BD

Review Stop P PLUMBING
Rev No 3 Status N Date 2005-10-12 Cont ID  
Sent By kstevens Date 2005-10-12 Time 13:12 Rev Time 1.00
Received By kstevens Date 2005-10-12 Time 13:12 Sent To  
Notes
2005-10-12 00:00:00DWV FOR LAV FROM STACK BEHIND W/M AND
 EXISTING LAV WRAPS AROUND FROM THAT
 STACK. NO RISER DIAGRAMS REQUIRED.

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-08-05 Cont ID  
Sent By kstevens Date 2005-08-05 Time 08:07 Rev Time 0.75
Received By kstevens Date 2005-08-05 Time 08:07 Sent To  
Notes
2005-08-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. PLUMBING SHEET HAS BEEN DELETED, BUT
 ARCHITECTURAL SHEETS STILL SHOW PLUMBING
 CHANGES. IF PLUMBING WORK IS TO BE DONE,
 A SANT. RISER DIAGRAM SHOWING CHANGES AS
 WELL AS A WATER RISER DIAGRAM. SECTIONS
 104.2.1 & 104.3.1.1.
 2. ARCHITECTURAL SHEETS DO NOT SHOW THE
 WATER WALL OR SOFFIT AS SHOWN IN THE
 ORIGINAL PLANS. PLEASE INDICATE IF THIS
 WORK IS STILL GOING TO BE DONE. SECTION
 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-06-04 Cont ID  
Sent By kstevens Date 2005-06-04 Time 16:03 Rev Time 0.55
Received By kstevens Date 2005-06-04 Time 16:03 Sent To  
Notes
2005-06-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. MORE INFORMATION IS REQUIRED ON THE
 WATER WALL. PLEASE INDICATE THE METHOD
 FOR SUPPLYING THE WATER TO THE SYSTEM.
 SECTION 104.2.1. IF A SUPPLY LINE IS
 CONNECTED TO THE POTABLE WATER, SOME
 METHOD OF BACKFLOW PREVENTION IS
 REQUIRED.
 SHT P-1 INDICATES NO DRAIN REQUIRED FOR
 THE WATER FEATURE, BUT DETAIL ON SHT A-3
 INDICATES AND 1-1/4" OVERFLOW DRAIN.
 PLEASE CLAIRFY. WHERE WOULD THE 1-1/4"
 OVERFLOW DRAIN CONNECT TO THE SANT.
 SYSTEM. SECTION 104.2.1.
 2. APPLICATION STATES "DESCRIBE PROJECT
 IN DETAIL" BUT NO MENTION OF THE WATER
 WALL, MOVING OF THE POWDER ROOM FIXTURES
 OR BUILDING THE SOFFIT IS INDICATED.
 PLEASE CLARIFY.
 3. SEPARATE PERMIT REQUIRED FOR
 PLUMBING.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]