| Plan Review Stops For Permit 05042186 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2005-07-11 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-07-11 |
Time |
11:27 |
Rev Time |
0.50 |
| Received By |
alange |
Date |
2005-07-11 |
Time |
11:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-06-15 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-06-15 |
Time |
11:09 |
Rev Time |
0.50 |
| Received By |
alange |
Date |
2005-06-15 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2005-06-15 00:00:00 | DENIED | | | | | | 1.TRACO SINGLE HUNG WINDOW PRODUCT | | | APPROVALS MISSING THE APPROPRIATE STATE | | | APPROVAL PAGES. SEE NOTES ON PAGES | | | SUBMITTED. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 2.IMPACT PROTECTION REQUIRED FOR | | | WINDOW.SUBMIT PRODUCT APPROVALS. | | | MIAMI-DADE PRODUCT APPROVAL SUBMITTED | | | WAS INCOMPLETE ONLY PAGE 1 OF 13 WAS | | | SUBMITTED. | | | | | | | | | ANY QUESTIONS CALL ME | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-05-16 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-05-16 |
Time |
07:49 |
Rev Time |
0.75 |
| Received By |
alange |
Date |
2005-05-16 |
Time |
07:23 |
Sent To |
|
|
| Notes |
| 2005-05-16 00:00:00 | DENIED | | | | | | 1.TRACO SINGLE HUNG WINDOW PRODUCT | | | APPROVALS MISSSING THE APPROPRIATE STATE | | | APPROVAL PAGES. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 2.IMPACT PROTECTION REQUIRED FOR | | | WINDOW.SUBMIT PRODUCT APPROVALS. | | | | | | 3.SUBMIT PRODUCT APPROVALS FOR STRAPS | | | AND TIE-DOWNS. | | | | | | 4.NAME AND SIGNATURE REQUIRED ON PLANS | | | BY THE PERSON RESPOSIBLE FOR THE DESIGN. | | | FBC 104.2.1 | | | | | | ANY QUESTIONS CALL ME | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2005-06-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-06-13 |
Time |
18:26 |
Rev Time |
0.20 |
| Received By |
dpalmer |
Date |
2005-06-13 |
Time |
18:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-05-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-05-10 |
Time |
06:36 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2005-05-10 |
Time |
06:36 |
Sent To |
|
|
| Notes |
| 2005-05-10 00:00:00 | ********* UNSAT ********* | | | | | | 1)NOTE: PLEASE SEE 700.12E FOR | | | CIRCUITING OF EM/EXT LTS. | | | PLEASE SEE THAT THESE SHALL BE CONNECTED | | | TO LOCAL BRACNH CIRCUITING FOR GEN | | | LIGHTING. | | | | | | 2)NOTE: PLEASE SEE FBC 104.2.1, ALL | | | PLANS/DRAWING MUST CONTAIN THE PRINTED | | | NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | [email protected] |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2005-05-18 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-05-18 |
Time |
08:04 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-05-18 |
Time |
08:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2005-06-14 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-06-14 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-06-14 |
Time |
15:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-05-17 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-05-17 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-05-17 |
Time |
15:23 |
Sent To |
|
|
| Notes |
| 2005-05-17 00:00:00 | 1) PLEASE REFER TO COMMENTS FROM OTHER | | | REVIEWERS IN REGARDS TO REQUIREMENTS IN | | | ACCORDANCE WITH FBC 104.2.1. | | | | | | 2) PLEASE SHOW LOCATIONS OF EXIT SIGNS | | | AND EMERGENCY LIGHTING FACILITIES. | | | | | | 3) FIRE EXTINGUISHERS RATED 2A-10B,C ARE | | | REQUIRED TO BE MOUNTED BETWEEN 3-5' FROM | | | THE FLOOR WITH A TRAVEL DISTANCE NOT TO | | | EXCEED 75'. | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 835-2910 OR 805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-06-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-06-23 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-06-23 |
Time |
11:05 |
Sent To |
B |
|
| Notes |
| 2005-06-23 00:00:00 | TO "ALANGE" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-06-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-06-17 |
Time |
14:23 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-06-17 |
Time |
14:23 |
Sent To |
Z |
|
| Notes |
| 2005-06-17 00:00:00 | ROUTED TO ZONING BOX | | | ALL OTHER REVIEWS COMPLETE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-05-31 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-05-31 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-05-31 |
Time |
15:19 |
Sent To |
|
|
| Notes |
| 2005-06-07 00:00:00 | COMM BOARD #20 | | 2005-05-31 00:00:00 | IN INCOMING AWAITING SPACE ON "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-05-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-05-17 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-05-17 |
Time |
16:50 |
Sent To |
Z |
|
| Notes |
| 2005-05-17 00:00:00 | TAKEN OFF "COMM" BD/SENT TO ZONING |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-05-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-05-18 |
Time |
08:04 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-04-29 |
Time |
17:04 |
Sent To |
|
|
| Notes |
| 2005-05-09 00:00:00 | TO "COMM" BD#31 | | 2005-05-03 00:00:00 | IN INCOMING/AWAITING SPACE ON "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2005-05-18 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-05-18 |
Time |
08:04 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-05-18 |
Time |
08:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2005-05-18 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-05-18 |
Time |
08:04 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-05-18 |
Time |
08:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2005-06-21 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2005-06-21 |
Time |
13:07 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2005-06-21 |
Time |
13:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2005-06-20 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-06-20 |
Time |
17:02 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-06-20 |
Time |
17:02 |
Sent To |
|
|
| Notes |
| 2005-06-20 00:00:00 | DENIED, | | | 1. NEED TO PROVIDE AN UPDATED FULL SIZE | | | SURVEY/SITEPLAN SHOWING THE ADDITION | | | WITH THE SETBACK **2ND REQUEST** | | | 2. PROPOSED FLOOR WILL NOT PROVIDE US | | | THE INFORMATION NEEDED TO COMPLETE OUR | | | REVIEW. | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2005-05-18 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-05-18 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-05-18 |
Time |
07:55 |
Sent To |
|
|
| Notes |
| 2005-05-18 00:00:00 | DENIED, | | | 1. NEED TO PROVIDE A SURVEY OR SITEPLAN | | | SHOWING THE LOCATION OF ENCLOSE PORCH | | | FOR STORAGE AND SETBACK. | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|