Plan Review Details - Permit 05042186
Plan Review Stops For Permit 05042186
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-07-11 Cont ID  
Sent By alange Date 2005-07-11 Time 11:27 Rev Time 0.50
Received By alange Date 2005-07-11 Time 11:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-06-15 Cont ID  
Sent By alange Date 2005-06-15 Time 11:09 Rev Time 0.50
Received By alange Date 2005-06-15 Time 11:01 Sent To  
Notes
2005-06-15 00:00:00DENIED
  
 1.TRACO SINGLE HUNG WINDOW PRODUCT
 APPROVALS MISSING THE APPROPRIATE STATE
 APPROVAL PAGES. SEE NOTES ON PAGES
 SUBMITTED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2.IMPACT PROTECTION REQUIRED FOR
 WINDOW.SUBMIT PRODUCT APPROVALS.
 MIAMI-DADE PRODUCT APPROVAL SUBMITTED
 WAS INCOMPLETE ONLY PAGE 1 OF 13 WAS
 SUBMITTED.
  
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-16 Cont ID  
Sent By alange Date 2005-05-16 Time 07:49 Rev Time 0.75
Received By alange Date 2005-05-16 Time 07:23 Sent To  
Notes
2005-05-16 00:00:00DENIED
  
 1.TRACO SINGLE HUNG WINDOW PRODUCT
 APPROVALS MISSSING THE APPROPRIATE STATE
 APPROVAL PAGES.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2.IMPACT PROTECTION REQUIRED FOR
 WINDOW.SUBMIT PRODUCT APPROVALS.
  
 3.SUBMIT PRODUCT APPROVALS FOR STRAPS
 AND TIE-DOWNS.
  
 4.NAME AND SIGNATURE REQUIRED ON PLANS
 BY THE PERSON RESPOSIBLE FOR THE DESIGN.
 FBC 104.2.1
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-06-13 Cont ID  
Sent By dpalmer Date 2005-06-13 Time 18:26 Rev Time 0.20
Received By dpalmer Date 2005-06-13 Time 18:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-10 Cont ID  
Sent By dpalmer Date 2005-05-10 Time 06:36 Rev Time 0.25
Received By dpalmer Date 2005-05-10 Time 06:36 Sent To  
Notes
2005-05-10 00:00:00********* UNSAT *********
  
 1)NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF EM/EXT LTS.
 PLEASE SEE THAT THESE SHALL BE CONNECTED
 TO LOCAL BRACNH CIRCUITING FOR GEN
 LIGHTING.
  
 2)NOTE: PLEASE SEE FBC 104.2.1, ALL
 PLANS/DRAWING MUST CONTAIN THE PRINTED
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2005-05-18 Cont ID  
Sent By mmclean Date 2005-05-18 Time 08:04 Rev Time 0.00
Received By mmclean Date 2005-05-18 Time 08:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-06-14 Cont ID  
Sent By mwennerg Date 2005-06-14 Time 15:00 Rev Time 0.00
Received By mwennerg Date 2005-06-14 Time 15:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-05-17 Cont ID  
Sent By mwennerg Date 2005-05-17 Time 15:23 Rev Time 0.00
Received By mwennerg Date 2005-05-17 Time 15:23 Sent To  
Notes
2005-05-17 00:00:001) PLEASE REFER TO COMMENTS FROM OTHER
 REVIEWERS IN REGARDS TO REQUIREMENTS IN
 ACCORDANCE WITH FBC 104.2.1.
  
 2) PLEASE SHOW LOCATIONS OF EXIT SIGNS
 AND EMERGENCY LIGHTING FACILITIES.
  
 3) FIRE EXTINGUISHERS RATED 2A-10B,C ARE
 REQUIRED TO BE MOUNTED BETWEEN 3-5' FROM
 THE FLOOR WITH A TRAVEL DISTANCE NOT TO
 EXCEED 75'.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910 OR 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-06-23 Cont ID  
Sent By adarroug Date 2005-06-23 Time 11:05 Rev Time 0.00
Received By adarroug Date 2005-06-23 Time 11:05 Sent To B
Notes
2005-06-23 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-06-17 Cont ID  
Sent By shill Date 2005-06-17 Time 14:23 Rev Time 0.00
Received By shill Date 2005-06-17 Time 14:23 Sent To Z
Notes
2005-06-17 00:00:00ROUTED TO ZONING BOX
 ALL OTHER REVIEWS COMPLETE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-05-31 Cont ID  
Sent By adarroug Date 2005-05-31 Time 15:19 Rev Time 0.00
Received By shill Date 2005-05-31 Time 15:19 Sent To  
Notes
2005-06-07 00:00:00COMM BOARD #20
2005-05-31 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-17 Cont ID  
Sent By adarroug Date 2005-05-17 Time 16:50 Rev Time 0.00
Received By adarroug Date 2005-05-17 Time 16:50 Sent To Z
Notes
2005-05-17 00:00:00TAKEN OFF "COMM" BD/SENT TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-18 Cont ID  
Sent By adarroug Date 2005-05-18 Time 08:04 Rev Time 0.00
Received By mmclean Date 2005-04-29 Time 17:04 Sent To  
Notes
2005-05-09 00:00:00TO "COMM" BD#31
2005-05-03 00:00:00IN INCOMING/AWAITING SPACE ON "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-05-18 Cont ID  
Sent By mmclean Date 2005-05-18 Time 08:04 Rev Time 0.00
Received By mmclean Date 2005-05-18 Time 08:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-05-18 Cont ID  
Sent By mmclean Date 2005-05-18 Time 08:04 Rev Time 0.00
Received By mmclean Date 2005-05-18 Time 08:04 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2005-06-21 Cont ID  
Sent By jroach Date 2005-06-21 Time 13:07 Rev Time 0.00
Received By jroach Date 2005-06-21 Time 13:07 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2005-06-20 Cont ID  
Sent By mmclean Date 2005-06-20 Time 17:02 Rev Time 0.00
Received By mmclean Date 2005-06-20 Time 17:02 Sent To  
Notes
2005-06-20 00:00:00DENIED,
 1. NEED TO PROVIDE AN UPDATED FULL SIZE
 SURVEY/SITEPLAN SHOWING THE ADDITION
 WITH THE SETBACK **2ND REQUEST**
 2. PROPOSED FLOOR WILL NOT PROVIDE US
 THE INFORMATION NEEDED TO COMPLETE OUR
 REVIEW.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2005-05-18 Cont ID  
Sent By mmclean Date 2005-05-18 Time 07:55 Rev Time 0.00
Received By mmclean Date 2005-05-18 Time 07:55 Sent To  
Notes
2005-05-18 00:00:00DENIED,
 1. NEED TO PROVIDE A SURVEY OR SITEPLAN
 SHOWING THE LOCATION OF ENCLOSE PORCH
 FOR STORAGE AND SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720