Plan Review Details - Permit 05042113
Plan Review Stops For Permit 05042113
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-06-13 Cont ID  
Sent By lsmith Date 2005-06-13 Time 07:53 Rev Time 0.50
Received By lsmith Date 2005-06-13 Time 07:53 Sent To  
Notes
2005-06-13 00:00:00BUILDING PLAN REVIEW: PROVISO
  
 POOL PAVER DECK BY SEPARATE PERMIT WITH
 DRAWING SHOWING SQ. FOOTAGE.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-09-26 Cont ID  
Sent By btrobaug Date 2005-09-26 Time 07:42 Rev Time 0.33
Received By btrobaug Date 2005-09-26 Time 07:24 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-09-03 Cont ID  
Sent By dpalmer Date 2005-09-03 Time 10:55 Rev Time 0.30
Received By dpalmer Date 2005-09-03 Time 10:55 Sent To P
Notes
2005-09-03 00:00:00****** UNSAT 3RD REVIEW ********
  
 1)NOTE: PLEASE SEE SAME COMMENTS AS TWO
 PREVIOUS REVIEWS BY MR. BILL TROBAUGH.
  
 PLEASE PROVIDE INFORMATION ON NEW SUB
 PANEL SHOWN ON ELECTRICAL WIRING
 DIAGRAM.
 PLEASE SEE ATTACHED SHEET IS THE SAME AS
 PREVIOUSLY NOTED AND NO CHANGES HAVE
 BEEN MADE TO ELECTRICAL PLANS.
 PLEASE INCLUDE NEW FEEDERS, CONDUIT, OCP
 TO NEW PANEL AND WHERE POWER COMES FROM.
 PLEASE PROVIDE LOADS FOR NEW.
  
 2)NOTE: PLEASE SEE A 4X FEE IS NOW
 ACCESSED DUE TO REPEAT COMMENTS FOR THE
 SAME CODE COMPLIANCE COMMENTS. THIS FEE
 IS REQUIRED PER 553.80(2)(B) WITH
 RESPECT TO THE DESIGN PROFESSIONAL.
 PLEASE KNOW IF PLANS COME BACK WITH
 ANY OF THE CODE COMMENTS NOT ADDRESSED
 ON NEXT REVIEW THE FEE WILL BE ACCESSED
 ONCE AGAIN.
 PLEASE SEE THE AMOUNT OF $356.40 IS
 REQUIRED TO BE PAID BEFORE RE-SUBMITTIAL
 OF PLANS.
 PLEASE BE SURE THE COMMENTS ARE
 ADDRESSED BEFORE RESUBMITTING PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-06-08 Cont ID  
Sent By btrobaug Date 2005-06-08 Time 11:51 Rev Time 0.33
Received By btrobaug Date 2005-06-08 Time 11:48 Sent To PC
Notes
2005-06-08 00:00:00 
 PLEASE SEE NOTES FROM PRIOR REVIEW. THE
 "EXAMPLE" RESUBMITTED NEEDS TO GO TO THE
 ENGINEER OF RECORD SO THE PLANS DRAWN
 MAY BE CORRECTED TO REFLECT ACTUAL FIELD
 CONDITIONS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-10 Cont ID  
Sent By btrobaug Date 2005-05-10 Time 13:34 Rev Time 0.33
Received By btrobaug Date 2005-05-10 Time 13:32 Sent To P
Notes
2005-05-10 00:00:00 
 PLEASE SUBMIT DETAILS FOR THE PANEL
 SHOWN ON THE SCHEMATIC, FEEDER AND
 CONDUIT SIZE AND TYPE, PANEL RATING AND
 OCP, PANEL SCHEDULE AND COMPUTED LOAD,
 ETC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-09-23 Cont ID  
Sent By adarroug Date 2005-09-23 Time 15:02 Rev Time 0.00
Received By adarroug Date 2005-09-23 Time 15:02 Sent To E
Notes
2005-09-23 00:00:00TO "BTROBAUG" DESK/RESUB/NEW SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-30 Cont ID  
Sent By adarroug Date 2005-08-30 Time 15:46 Rev Time 0.00
Received By adarroug Date 2005-08-30 Time 15:46 Sent To E
Notes
2005-08-30 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-08 Cont ID  
Sent By shill Date 2005-06-08 Time 09:10 Rev Time 0.00
Received By shill Date 2005-06-08 Time 09:10 Sent To DEMO
Notes
2005-06-08 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-04-29 Cont ID  
Sent By adarroug Date 2005-04-29 Time 17:52 Rev Time 0.00
Received By adarroug Date 2005-04-29 Time 17:52 Sent To Z
Notes
2005-04-29 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-09-13 Cont ID  
Sent By jleech Date 2005-09-13 Time 07:21 Rev Time 0.33
Received By jleech Date 2005-09-13 Time 07:21 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-05-21 Cont ID  
Sent By pschmitz Date 2005-05-21 Time 10:39 Rev Time 0.00
Received By pschmitz Date 2005-05-21 Time 10:39 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-05-06 Cont ID  
Sent By mmclean Date 2005-05-06 Time 16:46 Rev Time 0.00
Received By mmclean Date 2005-05-06 Time 16:46 Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy