| Plan Review Stops For Permit 05041991 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2006-03-28 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-03-28 |
Time |
14:34 |
Rev Time |
0.66 |
| Received By |
alange |
Date |
2006-03-28 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2006-03-28 00:00:00 | REVISION DENIED | | | | | | 1.REVISED PAGES DONT MATCH UP WITH | | | EXISTING APPROVED PAGES. | | | | | | 2.IF YOU ARE NOT REVISING EXISTING | | | WORK BUT ADD ADITIONAL WORK.CHANGE | | | PERMIT VALUE, CHANGE SCOPE OF WORK AND | | | NUMBER PAGES ACCORDINGLY. | | | | | | 3.INSUFFICIENT INFORMATION TO DO A | | | PLAN REVIEW. | | | | | | 4.SEE PLAN REVIEW NOTES FROM OTHER | | | REVIEWERS. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2005-11-22 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-11-22 |
Time |
15:44 |
Rev Time |
0.50 |
| Received By |
alange |
Date |
2005-11-22 |
Time |
14:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2005-06-20 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-06-20 |
Time |
11:22 |
Rev Time |
0.66 |
| Received By |
alange |
Date |
2005-06-20 |
Time |
11:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-06-09 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2005-06-09 |
Time |
12:42 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2005-06-09 |
Time |
12:15 |
Sent To |
|
|
| Notes |
| 2005-06-09 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | PLANS TO GO TO ART LANGE UPON | | | RESUBMITTAL. | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | F.S.= FLORIDA (STATE) STATUTE | | | | | | 1) FBC 11-4.1.6(II)ALTERATIONS TO | | | EXISTING BUILDINGS.AMEND/ANNOTATE THE | | | PLANS TO DEMONSTRATE THAT THE USABILITY | | | AND ACCESSIBILITY OF THE BATHROOM WILL | | | NOT BE REDUCED BY THE PROPOSED | | | ALTERATIONS.ITEMS REQUIRED TO BE SHOWN | | | INCLUDE CLEAR WIDTH OF THE DOOR OPENING, | | | 5FT WHEELCHAIR TURNING CIRCLE AND | | | APPROACH/HEIGHT/CLEARANCES AT THE | | | LAVATORY.SEE ALSO FBC 11-4.1.6(1)(B) | | | AND (C) | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | TELEPHONE: (561) 805 6716ROBERT BROWN | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2005-05-18 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-05-18 |
Time |
09:02 |
Rev Time |
2.50 |
| Received By |
alange |
Date |
2005-05-17 |
Time |
16:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2006-02-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-02-21 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-02-21 |
Time |
12:03 |
Sent To |
|
|
| Notes |
| 2006-02-21 00:00:00 | ****** UNSAT ****** | | | | | | 1)NOTE: PLEASE SEE REVISION INDICATES TO | | | INCLUDE FIRST FLR AREAS. | | | PLEASE KNOW, PERMITTING WAS FOR | | | RENOVATION OF ROOMS. | | | PLEASE SEE VALUATION FOR COMPLETE SCOPE | | | OF WORK AND CONTRACT OF JOB NEEDS TO BE | | | UPDATED AS ORIGINAL SCOPE OF SEEMS TO | | | PASSED ORIGINAL VALUE APPLIED FOR. | | | FBC ADMINISTRATICE CODE 108.3 AS ADOPTED | | | TO THE CITY OF WEST PALM BEACH. | | | VALUE APPLIED FOR IS LOW. | | | | | | 2)NOTE: PLEASE SUBMIT COMPLETE | | | ELECTRICLA PLANS FOR SCOPE OF WORK. | | | PLEASE SEE PLANS DO NOT INDICATE | | | ELECTRICAL FOR REMODEL OF FIRST FLR | | | ARES. | | | ROOMS ARE SHOWN ON ONE SHEET, BUT IT IS | | | UNCLEAR WHAT IS BEING DONE. | | | PLEASE SUBMIT COMPLETE ELECTRICLA PLANS | | | FOR ALL WORK AND REMODEL WHICH IS TAKING | | | PLACE AT HOTEL. ORIG SCOPE FOR REPAIR OF | | | EXISTING. | | | PLEASE INCLUDE ALL CIRCUITING ON PLANS | | | AND CORRELATE WITH PANEL SCHEDULES TO BE | | | SUBMITTED. | | | 215.5 | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2005-11-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-11-30 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-11-30 |
Time |
16:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2005-08-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-08-25 |
Time |
09:19 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2005-08-25 |
Time |
09:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2005-05-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-05-09 |
Time |
12:12 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-05-09 |
Time |
12:12 |
Sent To |
|
|
| Notes |
| 2005-05-09 00:00:00 | ** REVIEWED FOR ELECTRICAL NEC | | | COMPLIANCE. | | | FIRE DEVICES, HORN/STROBES ETC TO BE | | | VERIFIED BY FIRE PLAN REVIEW IF EXISTING | | | MEET FIRE CODE COMPLIANCE.**** | | | IF LOCATIONS SHOWN DO NOT MEET CODE, | | | VOID ELECTRICAL SHEETS AND REVISE. | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
N |
Date |
2006-03-15 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-03-15 |
Time |
15:11 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-03-15 |
Time |
15:11 |
Sent To |
|
|
| Notes |
| 2006-03-15 00:00:00 | ******DENIED****** | | | | | | | | | 1) REVISION SUBMITTAL FORM INDICATES | | | THAT CHANGES ARE IDENTIFIED BY CLOUDS?? | | | | | | 2) ARE THERE CHANGES THAT WOULD AFFECT | | | PREVIOUS FIRE REVIEWS? PLEASE INDICATE | | | ON SUBMITTAL FORM UNDER FIRE IF | | | APPLICABLE. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLANS REVIEW (561) 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2005-12-02 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-12-02 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-12-02 |
Time |
15:53 |
Sent To |
|
|
| Notes |
| 2005-12-02 00:00:00 | REVISION DATED 10/8/05 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2005-06-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2005-06-20 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2005-06-20 |
Time |
11:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-05-10 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-05-10 |
Time |
13:51 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-05-10 |
Time |
13:23 |
Sent To |
|
|
| Notes |
| 2005-05-10 00:00:00 | 1) PLEASE ILLUSTRATE THE LOCATIONS OF | | | EXISTING EXIT SIGNS AND EMERGENCY | | | LIGHTS. | | | | | | 2) WILL THE NEW FRAMED ARCHES IN THE | | | CORRIDORS IMPACT THE VISIBILITY OF | | | EXISTING EXIT SIGNS? | | | | | | 3) WILL THE FRAMED ARCHES EFFECT THE | | | OPERATION OF EXISTING SMOKE DETECTORS? | | | | | | 4) ALL CONSTRUCTION, ALTERATION, AND | | | DEMOLITION TO COMPLY WITH NFPA 241. | | | | | | 5) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR FIRE ALARM AND FIRE | | | SPRINKLER REMODELS. | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 835-2910 OR 805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-01-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-01-27 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-01-27 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2006-02-17 00:00:00 | TO "COMM" BD#22 | | 2006-01-27 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-10-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-10-22 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-10-22 |
Time |
11:14 |
Sent To |
|
|
| Notes |
| 2005-11-21 00:00:00 | TO "COMM" BD#33 | | 2005-10-22 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-08-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-19 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-19 |
Time |
09:45 |
Sent To |
E |
|
| Notes |
| 2005-08-19 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-06-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-06-15 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-06-15 |
Time |
15:38 |
Sent To |
|
|
| Notes |
| 2005-06-15 00:00:00 | WAITING FOR COMM BOARD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-06-09 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2005-06-09 |
Time |
12:42 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2005-04-27 |
Time |
17:00 |
Sent To |
|
|
| Notes |
| 2005-05-05 00:00:00 | 5/5/05-TO "COMM" BD#57 | | 2005-05-03 00:00:00 | IN INCOMING/AWAITING SPACE ON "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2006-02-23 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2006-02-23 |
Time |
07:17 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2006-02-23 |
Time |
07:17 |
Sent To |
|
|
| Notes |
| 2006-02-23 00:00:00 | NO MECHANICAL PLANS TO BE REVIEWED.HM | | | 2/23/06 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2006-01-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-01-10 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-01-10 |
Time |
11:33 |
Sent To |
|
|
| Notes |
| 2006-01-10 00:00:00 | NEW PLAN SHEET P/M-2 SUBMITTED FOR | | | APPROVAL.MECHANICAL ONLY |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2006-03-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-03-22 |
Time |
07:16 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-03-21 |
Time |
19:00 |
Sent To |
|
|
| Notes |
| 2006-03-22 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | 1. ORIGINAL PERMIT APPLICATION INDICATES | | | THAT FIRST FLOOR WILL BE ADDRESSED IN | | | FUTURE PERMIT. THE VALUE OF THE FIRST | | | FLOOR SHALL BE ADDED TO THE PERMIT COST. | | | 2. PER SECTION 11-4.1.6(2) 20% OF COST | | | OF ALTERATIONS SHALL BE FOR ACCESSIBLITY | | | UPGRADES AND ARE REQUIRED. SEE SECTIONS | | | 11-9.1.2, 11-9.1.3, 11-9.1.4 AND | | | 11-9.2.3. INDICATE HOW THESE CODE | | | SECTIONS ARE IN COMPLIANCE. | | | 3. SHT A.05 DETAILS 1 & 2 SHOW THE CLEAR | | | FLOOR SPACE FOR THE SHOWER 11-4.21.2 AND | | | FOR THE TUB 11-4.20.2. | | | 4. SHT A.06 ALL WATER CLOSETS INSTALLED | | | ADJACENT TO A WALL SHALL BE 1'6" TO THE | | | CENTERLINE OF THE FIXTURE OFF THE WALL. | | | PLEASE INDICATE ON DETAILS. TOILET PAPER | | | DISPENSERS SHALL BE LOCATED 19" MINIMUM | | | OFF THE FLOOR. SECTION 11-4.16.6. | | | 5. SHT A.06 ALL LAVS SHALL COMPLY WITH | | | THE FOLLOWING: | | | A. 11-4.19.2 HEIGHT & CLEARANCES | | | B. 11-4.19.4 EXPOSED PIPES & SURFACES | | | C. 11-4.19.5 FAUCETS | | | PLEASE INDICATE ON DETAILS. | | | 6. SHT A.06 SHOW MEASUREMENTS FOR THE | | | CONTROLS FOR THE TUB 11-4.20.5 (DETAILS | | | 4.3 & 6.1), AND FOR THE SHOWER 11-4.21.5 | | | (DETAILS 3.1 & 5.1). | | | 7. SUBMIT A SANITARY RISER ISOMETRIC | | | DIAGRAM FOR ALL NEW WORK SHOWING ALL | | | PIPE SIZES, TRAPS, AND VENTING PER | | | SECTION 104.3.1.1. | | | 8. SUBMIT A WATER RISER ISOMETRIC | | | DIAGRAM SHOWING ALL PIPE SIZES, VALVES | | | AND, IF REQUIRED BY SECTION 604.9, (W/M) | | | WATER HAMMER ARRESTORS LOCATED NEAR THE | | | FIXTURES IN AN "EFFECTIVE RANGE" NOT IN | | | THE CEILING. SECTION 104.3.1.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2006-01-21 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-01-21 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-01-21 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2006-01-21 00:00:00 | PROVISO: | | | PREVIOUS NOTES BT KEN STEVENS. | | | | | | NO PLUMBING PLANS SUBMITTED/REQUIRED | | | FIXTURES BEING TAKEN UP AND RESET IN | | | SAME LOCATION EXCEPT FOR LAVS IN | | | DESIGNATED UNITS BEING RELOCATED TO THE | | | OPPOSITE SIDE OF THE WALL. LAVS SHALL | | | COMPLY WITH 11-4.19 AND ALL SUBSECTIONS. | | | SEE SHT A.02 FOR LAVS TO BE RELOCATED | | | END OF COMMENTS, QUESTIONS 561-805-6692 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2005-06-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-06-04 |
Time |
12:29 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2005-06-04 |
Time |
12:01 |
Sent To |
|
|
| Notes |
| 2005-06-04 00:00:00 | NO PLUMBING PLANS SUBMITTED/REQUIRED | | | FIXTURES BEING TAKEN UP AND RESET IN | | | SAME LOCATION EXCEPT FOR LAVS IN | | | DESIGNATED UNITS BEING RELOCATED TO THE | | | OPPOSITE SIDE OF THE WALL. LAVS SHALL | | | COMPLY WITH 11-4.19 AND ALL SUBSECTIONS. | | | SEE SHT A.02 FOR LAVS TO BE RELOCATED |
|
|