Plan Review Details - Permit 05041991
Plan Review Stops For Permit 05041991
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2006-03-28 Cont ID  
Sent By alange Date 2006-03-28 Time 14:34 Rev Time 0.66
Received By alange Date 2006-03-28 Time 13:41 Sent To  
Notes
2006-03-28 00:00:00REVISION DENIED
  
 1.REVISED PAGES DONT MATCH UP WITH
 EXISTING APPROVED PAGES.
  
 2.IF YOU ARE NOT REVISING EXISTING
 WORK BUT ADD ADITIONAL WORK.CHANGE
 PERMIT VALUE, CHANGE SCOPE OF WORK AND
 NUMBER PAGES ACCORDINGLY.
  
 3.INSUFFICIENT INFORMATION TO DO A
 PLAN REVIEW.
  
 4.SEE PLAN REVIEW NOTES FROM OTHER
 REVIEWERS.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-11-22 Cont ID  
Sent By alange Date 2005-11-22 Time 15:44 Rev Time 0.50
Received By alange Date 2005-11-22 Time 14:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-06-20 Cont ID  
Sent By alange Date 2005-06-20 Time 11:22 Rev Time 0.66
Received By alange Date 2005-06-20 Time 11:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-06-09 Cont ID  
Sent By rbrown Date 2005-06-09 Time 12:42 Rev Time 0.00
Received By rbrown Date 2005-06-09 Time 12:15 Sent To  
Notes
2005-06-09 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 PLANS TO GO TO ART LANGE UPON
 RESUBMITTAL.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC 11-4.1.6(II)ALTERATIONS TO
 EXISTING BUILDINGS.AMEND/ANNOTATE THE
 PLANS TO DEMONSTRATE THAT THE USABILITY
 AND ACCESSIBILITY OF THE BATHROOM WILL
 NOT BE REDUCED BY THE PROPOSED
 ALTERATIONS.ITEMS REQUIRED TO BE SHOWN
 INCLUDE CLEAR WIDTH OF THE DOOR OPENING,
 5FT WHEELCHAIR TURNING CIRCLE AND
 APPROACH/HEIGHT/CLEARANCES AT THE
 LAVATORY.SEE ALSO FBC 11-4.1.6(1)(B)
 AND (C)
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-05-18 Cont ID  
Sent By alange Date 2005-05-18 Time 09:02 Rev Time 2.50
Received By alange Date 2005-05-17 Time 16:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-02-21 Cont ID  
Sent By dpalmer Date 2006-02-21 Time 13:10 Rev Time 0.00
Received By dpalmer Date 2006-02-21 Time 12:03 Sent To  
Notes
2006-02-21 00:00:00****** UNSAT ******
  
 1)NOTE: PLEASE SEE REVISION INDICATES TO
 INCLUDE FIRST FLR AREAS.
 PLEASE KNOW, PERMITTING WAS FOR
 RENOVATION OF ROOMS.
 PLEASE SEE VALUATION FOR COMPLETE SCOPE
 OF WORK AND CONTRACT OF JOB NEEDS TO BE
 UPDATED AS ORIGINAL SCOPE OF SEEMS TO
 PASSED ORIGINAL VALUE APPLIED FOR.
 FBC ADMINISTRATICE CODE 108.3 AS ADOPTED
 TO THE CITY OF WEST PALM BEACH.
 VALUE APPLIED FOR IS LOW.
  
 2)NOTE: PLEASE SUBMIT COMPLETE
 ELECTRICLA PLANS FOR SCOPE OF WORK.
 PLEASE SEE PLANS DO NOT INDICATE
 ELECTRICAL FOR REMODEL OF FIRST FLR
 ARES.
 ROOMS ARE SHOWN ON ONE SHEET, BUT IT IS
 UNCLEAR WHAT IS BEING DONE.
 PLEASE SUBMIT COMPLETE ELECTRICLA PLANS
 FOR ALL WORK AND REMODEL WHICH IS TAKING
 PLACE AT HOTEL. ORIG SCOPE FOR REPAIR OF
 EXISTING.
 PLEASE INCLUDE ALL CIRCUITING ON PLANS
 AND CORRELATE WITH PANEL SCHEDULES TO BE
 SUBMITTED.
 215.5
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-11-30 Cont ID  
Sent By dpalmer Date 2005-11-30 Time 16:16 Rev Time 0.00
Received By dpalmer Date 2005-11-30 Time 16:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-08-25 Cont ID  
Sent By dpalmer Date 2005-08-25 Time 09:19 Rev Time 0.50
Received By dpalmer Date 2005-08-25 Time 09:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-05-09 Cont ID  
Sent By dpalmer Date 2005-05-09 Time 12:12 Rev Time 0.30
Received By dpalmer Date 2005-05-09 Time 12:12 Sent To  
Notes
2005-05-09 00:00:00** REVIEWED FOR ELECTRICAL NEC
 COMPLIANCE.
 FIRE DEVICES, HORN/STROBES ETC TO BE
 VERIFIED BY FIRE PLAN REVIEW IF EXISTING
 MEET FIRE CODE COMPLIANCE.****
 IF LOCATIONS SHOWN DO NOT MEET CODE,
 VOID ELECTRICAL SHEETS AND REVISE.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status N Date 2006-03-15 Cont ID  
Sent By mwennerg Date 2006-03-15 Time 15:11 Rev Time 0.00
Received By mwennerg Date 2006-03-15 Time 15:11 Sent To  
Notes
2006-03-15 00:00:00******DENIED******
  
  
 1) REVISION SUBMITTAL FORM INDICATES
 THAT CHANGES ARE IDENTIFIED BY CLOUDS??
  
 2) ARE THERE CHANGES THAT WOULD AFFECT
 PREVIOUS FIRE REVIEWS? PLEASE INDICATE
 ON SUBMITTAL FORM UNDER FIRE IF
 APPLICABLE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-12-02 Cont ID  
Sent By mwennerg Date 2005-12-02 Time 15:53 Rev Time 0.00
Received By mwennerg Date 2005-12-02 Time 15:53 Sent To  
Notes
2005-12-02 00:00:00REVISION DATED 10/8/05

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-06-20 Cont ID  
Sent By mcarsill Date 2005-06-20 Time 11:18 Rev Time 0.00
Received By mcarsill Date 2005-06-20 Time 11:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-05-10 Cont ID  
Sent By mwennerg Date 2005-05-10 Time 13:51 Rev Time 0.00
Received By mwennerg Date 2005-05-10 Time 13:23 Sent To  
Notes
2005-05-10 00:00:001) PLEASE ILLUSTRATE THE LOCATIONS OF
 EXISTING EXIT SIGNS AND EMERGENCY
 LIGHTS.
  
 2) WILL THE NEW FRAMED ARCHES IN THE
 CORRIDORS IMPACT THE VISIBILITY OF
 EXISTING EXIT SIGNS?
  
 3) WILL THE FRAMED ARCHES EFFECT THE
 OPERATION OF EXISTING SMOKE DETECTORS?
  
 4) ALL CONSTRUCTION, ALTERATION, AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 5) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE ALARM AND FIRE
 SPRINKLER REMODELS.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910 OR 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-01-27 Cont ID  
Sent By adarroug Date 2006-01-27 Time 11:29 Rev Time 0.00
Received By adarroug Date 2006-01-27 Time 11:29 Sent To  
Notes
2006-02-17 00:00:00TO "COMM" BD#22
2006-01-27 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-10-22 Cont ID  
Sent By adarroug Date 2005-10-22 Time 11:14 Rev Time 0.00
Received By adarroug Date 2005-10-22 Time 11:14 Sent To  
Notes
2005-11-21 00:00:00TO "COMM" BD#33
2005-10-22 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-19 Cont ID  
Sent By adarroug Date 2005-08-19 Time 09:45 Rev Time 0.00
Received By adarroug Date 2005-08-19 Time 09:45 Sent To E
Notes
2005-08-19 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-15 Cont ID  
Sent By shill Date 2005-06-15 Time 15:38 Rev Time 0.00
Received By shill Date 2005-06-15 Time 15:38 Sent To  
Notes
2005-06-15 00:00:00WAITING FOR COMM BOARD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-09 Cont ID  
Sent By rbrown Date 2005-06-09 Time 12:42 Rev Time 0.00
Received By rbrown Date 2005-04-27 Time 17:00 Sent To  
Notes
2005-05-05 00:00:005/5/05-TO "COMM" BD#57
2005-05-03 00:00:00IN INCOMING/AWAITING SPACE ON "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2006-02-23 Cont ID  
Sent By hmoser Date 2006-02-23 Time 07:17 Rev Time 0.00
Received By hmoser Date 2006-02-23 Time 07:17 Sent To  
Notes
2006-02-23 00:00:00NO MECHANICAL PLANS TO BE REVIEWED.HM
 2/23/06

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-01-10 Cont ID  
Sent By pkrauss Date 2006-01-10 Time 11:33 Rev Time 0.00
Received By pkrauss Date 2006-01-10 Time 11:33 Sent To  
Notes
2006-01-10 00:00:00NEW PLAN SHEET P/M-2 SUBMITTED FOR
 APPROVAL.MECHANICAL ONLY

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-03-22 Cont ID  
Sent By kstevens Date 2006-03-22 Time 07:16 Rev Time 0.00
Received By kstevens Date 2006-03-21 Time 19:00 Sent To  
Notes
2006-03-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1. ORIGINAL PERMIT APPLICATION INDICATES
 THAT FIRST FLOOR WILL BE ADDRESSED IN
 FUTURE PERMIT. THE VALUE OF THE FIRST
 FLOOR SHALL BE ADDED TO THE PERMIT COST.
 2. PER SECTION 11-4.1.6(2) 20% OF COST
 OF ALTERATIONS SHALL BE FOR ACCESSIBLITY
 UPGRADES AND ARE REQUIRED. SEE SECTIONS
 11-9.1.2, 11-9.1.3, 11-9.1.4 AND
 11-9.2.3. INDICATE HOW THESE CODE
 SECTIONS ARE IN COMPLIANCE.
 3. SHT A.05 DETAILS 1 & 2 SHOW THE CLEAR
 FLOOR SPACE FOR THE SHOWER 11-4.21.2 AND
 FOR THE TUB 11-4.20.2.
 4. SHT A.06 ALL WATER CLOSETS INSTALLED
 ADJACENT TO A WALL SHALL BE 1'6" TO THE
 CENTERLINE OF THE FIXTURE OFF THE WALL.
 PLEASE INDICATE ON DETAILS. TOILET PAPER
 DISPENSERS SHALL BE LOCATED 19" MINIMUM
 OFF THE FLOOR. SECTION 11-4.16.6.
 5. SHT A.06 ALL LAVS SHALL COMPLY WITH
 THE FOLLOWING:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 PLEASE INDICATE ON DETAILS.
 6. SHT A.06 SHOW MEASUREMENTS FOR THE
 CONTROLS FOR THE TUB 11-4.20.5 (DETAILS
 4.3 & 6.1), AND FOR THE SHOWER 11-4.21.5
 (DETAILS 3.1 & 5.1).
 7. SUBMIT A SANITARY RISER ISOMETRIC
 DIAGRAM FOR ALL NEW WORK SHOWING ALL
 PIPE SIZES, TRAPS, AND VENTING PER
 SECTION 104.3.1.1.
 8. SUBMIT A WATER RISER ISOMETRIC
 DIAGRAM SHOWING ALL PIPE SIZES, VALVES
 AND, IF REQUIRED BY SECTION 604.9, (W/M)
 WATER HAMMER ARRESTORS LOCATED NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE" NOT IN
 THE CEILING. SECTION 104.3.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-01-21 Cont ID  
Sent By pschmitz Date 2006-01-21 Time 11:27 Rev Time 0.00
Received By pschmitz Date 2006-01-21 Time 11:26 Sent To  
Notes
2006-01-21 00:00:00PROVISO:
 PREVIOUS NOTES BT KEN STEVENS.
  
 NO PLUMBING PLANS SUBMITTED/REQUIRED
 FIXTURES BEING TAKEN UP AND RESET IN
 SAME LOCATION EXCEPT FOR LAVS IN
 DESIGNATED UNITS BEING RELOCATED TO THE
 OPPOSITE SIDE OF THE WALL. LAVS SHALL
 COMPLY WITH 11-4.19 AND ALL SUBSECTIONS.
 SEE SHT A.02 FOR LAVS TO BE RELOCATED
 END OF COMMENTS, QUESTIONS 561-805-6692
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-06-04 Cont ID  
Sent By kstevens Date 2005-06-04 Time 12:29 Rev Time 0.50
Received By kstevens Date 2005-06-04 Time 12:01 Sent To  
Notes
2005-06-04 00:00:00NO PLUMBING PLANS SUBMITTED/REQUIRED
 FIXTURES BEING TAKEN UP AND RESET IN
 SAME LOCATION EXCEPT FOR LAVS IN
 DESIGNATED UNITS BEING RELOCATED TO THE
 OPPOSITE SIDE OF THE WALL. LAVS SHALL
 COMPLY WITH 11-4.19 AND ALL SUBSECTIONS.
 SEE SHT A.02 FOR LAVS TO BE RELOCATED