Plan Review Details - Permit 05041961
Plan Review Stops For Permit 05041961
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2006-02-24 Cont ID  
Sent By lursu Date 2006-02-24 Time 10:38 Rev Time 0.00
Received By lursu Date 2006-02-24 Time 10:37 Sent To  
Notes
2006-02-24 00:00:00NEW ADDRESS HAS BEEN ASSIGNED : 427
 WILDER ST., PCN = 7443434409060002030
2006-02-10 00:00:00ADDRESSES NOT PROPERLY ASSIGNED; BOTH
 PARCELS HAVE AN ADDRESS OF 423 WILDER ST
 IN PAPA AND OUR SYSTEM.ROUTED TO
 ADDRESSING.SMH

Review Stop AD ADDRESSING
Rev No 1 Status N Date 2005-04-26 Cont ID  
Sent By dalvarez Date 2005-04-26 Time 15:21 Rev Time 0.00
Received By dalvarez Date 2005-04-26 Time 15:21 Sent To  
Notes
2005-04-26 00:00:00VERIFICATION OF ACTUAL ADDRESS & PCN
 PARCEL WAS SUBDIVIDED DA

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-06-12 Cont ID  
Sent By shill Date 2006-06-12 Time 12:48 Rev Time 0.00
Received By shill Date 2006-06-09 Time 15:35 Sent To  
Notes
2006-06-12 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ***PLAN CHECK ONLY***
  
 GOVERNING CODE IS FBC2004 EFFECTIVE
 OCTOBER 1, 2005.NO PERMIT WAS APPLIED
 FOR PRIOR TO THIS DATE.REVISE ALL
 INCORRECT CODE REFERENCES.
  
 COMMENTS FROM THE PREVIOUS REVIEWS;
 NUMBERING TO REMAIN THE SAME FOR
 CONSISTENCY.NOTE THAT CODE REFERENCE
 NUMBERS HAVE CHANGED AS THE FIRST REVIEW
 WAS DONE ON FBC2001, SECOND REVIEW ON
 FBC2004.
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY PRIOR TO PERMIT ISSUANCE.
 THE PLANS MUST BE STAMPED AND THE
 RECEIPT ATTACHED TO THE APPLICATION.
 561-233-5025
  
 3.-5.)ADDRESSED.
  
 6.)ENERGY CALCS REQUIRED, FBC11-101.2.
 SIGN THE OWNER/AGENT LINE OF THE ENERGY
 CALC, FBC11-103.1.2.
  
 (2ND REVIEW) ENERGY CALCS WERE
 SUBMITTED.THE
 CEILING/FLOOR ASSEMBLY BETWEEN THE
 UNCONDITIONED GARAGE AREA AND THE
 CONDITIONED SECOND FLOOR IS NOT ON THE
 ENERGY CALCS, FIRST PAGE.SECOND PAGE
 SHOWS RAISED WOOD FLOOR ADJACENT, PLANS
 SHOW CONCRETE FLOOR.THE PLAN DOES NOT
 SHOW INSULATION BETWEEN THE LAUNDRY AREA
 IN THE GARAGE AND THE UTILITY ROOM.
 INSULATION IS SHOWN GRAPHICALLY ON A2.0
 BETWEEN FIRST AND SECOND FLOOR.
 INSULATION SHOWN GRAPHICALLY BETWEEN
 GARAGE AND ENTRY.PLEASE SPECIFY.THE
 WOOD FRAME WALL IS NOT INCLUDED IN THE
 ENERGY CALCS.
  
 (3RD REVIEW) ENERGY CALCS NO LONGER IN
 THE PACKAGE.REQUIRED FOR PERMITTING.
  
 7.)THE WIND RESISTANCE NOTES ON T1
 WERE PREPARED BY ANOTHER DESIGN
 PROFESSIONAL, MAKES REFERENCE TO A
 COMMERCIAL STRUCTURE, AND STATE THAT
 THIS IS A PARTIALLY ENCLOSED BUILDING
 WHICH IS NOT TO BE SHUTTERED.OTHER
 SHEETS SPECIFY IMPACT GLASS.PLEASE
 CLARIFY.
  
 (2ND REVIEW) SHEET T1 STILL STATES THAT
 THIS IS A PARTIALLY ENCLOSED STRUCTURE.
 SEE FBC1609.2.
  
 (3RD REVIEW) REFERS TO 1606; WIND
 PROVISIONS ARE 1609.REVISE OR
 ELIMINATE INCORRECT CODE REFERENCES.
 ALSO ON A7.0.
  
 8.-10.)ADDRESSED.
  
 11.)LOCAL OR STATE PRODUCT APPROVAL
 REQUIRED FOR:
 SHINGLE OR METAL ROOF
 WINDOWS
 MULLIONS
 FIXED GLASS WINDOWS
 FRENCH DOORS
 CASEMENT WINDOW
 OVERHEAD DOOR
 SKYLIGHTS
 IMPACT PROTECTION IF REQUIRED
 GARAGE DOOR
 TEST REPORT AND INSTALLATION
 INSTRUCTIONS REQUIRED IN ADDITION TO THE
 FLORIDA OR LOCAL PRODUCT APPROVAL.
  
 SEPARATE PERMITS WILL BE REQUIRED FOR
 ANY PRODUCT APPROVALS NOT PROPERLY
 SUBMITTED AND REVIEWED PRIOR TO
 ISSUANCE.
  
 (2ND REVIEW) NONE SUBMITTED.PRODUCT
 APPROVALS TO BE REVIEWED BY DESIGNER OF
 RECORD FBC*106.3.3.
  
 (3RD REVIEW) TWO COPIES REQUIRED OF ALL
 DOCUMENTS.ONLY ONE ROOF PRODUCT
 APPROVAL SUBMITTED.
  
 FIVE DIFFERENT TYPES OF WINDOWS ARE
 SHOWN ON THE PLAN; ONLY ONE PRODUCT
 APPROVAL SUBMITTED.PLANS NOT CLEAR,
 SEE OTHER COMMENT REGARDING WINDOWS.
 IMPACT S/H, IMPACT FIXED, IMPACT
 CASEMENT, S/H, CASEMENT.
  
 THE PB COUNTY PRODUCT APPROVAL CHECKLIST
 IS AN ACCEPTABLE METHOD OF SHOWING
 COMPLIANCE WITH FBC*106.3.3, ARCHITECT
 REVIEW.PROVIDE ORIGINAL SIGNATURES ON
 THE FORM OR PROVIDE A REVIEW STAMP FOR
 ALL PRODUCT APPROVALS.IF ADDING
 PRODUCT APPROVALS, PLEASE REVISE THE
 PRODUCT APPROVAL LIST.
  
 COMPLETE THE ATTACHED HURRICANE SHUTTER
 INSTALLATION SCHEDULE, OR PROVIDE ALL
 REQUIRED INFORMATION IN A SIMILAR
 FORMAT.
  
 12-13.)ADDRESSED.
  
 14.) ADDRESSED.
  
 15-16.)ADDRESSED.
  
 17.)A7.0, PLYWOOD/GYPBOARD SHEATHING
 NOTES, ITEM 2 (NAILING PATTERN 6IN
 EDGES, 6IN FIELD) IS NON COMPLIANT, SEE
 FBC*TABLE 2306.1.THE RESPONSE LETTER
 STATES THAT THE SHEATHING NAILING WAS
 CORRECTED TO 6IN OC EDGES AND 12IN OC
 FIELD.
  
 (2ND REVIEW) NOT ADDRESSED.STILL
 STATES 6/6.6/12 WAS SPECIFIED IN THE
 RESPONSE LETTER. THIS IS ALSO NOT CODE
 COMPLIANT.SEE FBC TABLE 2304.9.1.
  
 (3RD REVIEW) NOT ADDRESSED, PLANS STILL
 SHOW 6/12.SUBFLOOR NAILING ALSO NOT
 COMPLIANT WITH FBC TABLE 2304.9.1.
  
 18.-19.)NOT ADDRESSED.
  
 20.)WHAT IS THE CONSTRUCTION OF THE
 CABANA WALLS?IT DOES NOT APPEAR TO BE
 BLOCK.PROVIDE A DETAIL.
  
 21.)PROVIDE A STRUCTURAL DETAIL FOR
 THE BAY WINDOWS.
  
 (2ND REVIEW) NOT ADDRESSED.A CROSS
 SECTION WAS PROVIDED SHOWING THE STAIR
 AND BAY WINDOW.THIS IS NOT A
 STRUCTURAL DETAIL AS SPACING, FASTENING,
 DESIGN LOADS WERE NOT PROVIDED.
  
 (3RD REVIEW) NOT ADDRESSED.PROVIDE
 DIMENSIONS, NONE SHOWN ON PLAN.SHOW
 COMPLIANCE WITH FBC R302.1,302.2 (MUST
 BE OVER 3' FROM PROPERTY LINE).
  
 22-26.)ADDRESSED.
  
 27.)SPECIFY INSULATION FOR THE
 ADJACENT WALL (BETWEEN GARAGE AND ENTRY
 HALL).
  
 (2ND REVIEW) NOT ADDRESSED.SHOWN
 GRAPHICALLY BUT NOT SPECIFIED.ALSO
 NEEDS INSULATION BETWEEN THE GARAGE AND
 UTILITY ROOM.
  
 (3RD REVIEW) NOT ADDRESSED.THE FRAME
 WALL WAS CHANGED TO BLOCK, STILL NEEDS
 INSULATION.THE FRAME WALL SHOWS "SOUND
 INSULATION", MUST HAVE R VALUE SPECIFIED
 FBC13-602.
  
 28.-32.)ADDRESSED.
  
 31.)PROVIDE A STRUCTURAL DETAIL FOR
 THE STAIRS, WITH ALL DIMENSIONS,
 INCLUDING THE LANDING AND FIREBLOCKING
 FBC2305.1.4(3).
  
 (2ND REVIEW) NOT ADDRESSED.
  
 (3RD REVIEW) NOT ADDRESSED.
  
 32.)ADDRESSED.
  
 33.)SAFETY GLASS REQUIRED AT TUBS AND
 SHOWER, FBC2405.1.
  
 (2ND REVIEW) ADDRESSED IF IMPACT WINDOWS
 ARE USED AS PER PLAN.
  
 (3RD REVIEW) UNSURE AS TO COMPLIANCE.
 CONFLICTING NOTES REGARDING IMPACT
 PROTECTION ON THE PLAN.
  
 34.)THE CANTILEVERED BALCONY DETAIL A6
 DOES NOT HAVE A SLAB DIMENSION.
  
 (2ND & 3RD REVIEWS) NOT ADDRESSED.
  
 35.)SPECIFY SOFFIT VENTING AND SHOW
 COMPLIANCE FBC2309.7.
  
 (2ND & 3RD REVIEWS) NOT ADDRESSED.
  
 36.)SPECIFY REACTION LOADS ON THE ROOF
 FRAMING PLAN A7.0.
  
 NOT ADDRESSED.
  
 37-39.) ADDRESSED.
  
 40.) REINFORCEMENT ABOVE OPENINGS HAS
 NOT BEEN SPECIFIED.PROVIDE A SCHEDULE.
  
 ADDRESSED BY STATING THAT LINTELS WILL
 BE INSTALLED.SEE COMMENT 46 BELOW.
  
 PROVIDE A LINTEL SCHEDULE.
  
 41.) A COPY OF THE PLANS HAS BEEN
 RETAINED.
  
 ***NEW COMMENTS***
  
 42.)SHOW POSITIVE DRAINAGE FBC R401.3,
 FBC*109.3.10.
  
 NOT ADDRESSED.
  
 43.)ADDRESSED.
  
 44.)ALL CHANGES TO THE PLAN ARE TO BE
 CLEARLY INDICATED WITH A CLOUD AND
 REVISION NUMBER.AS NONE OF THE CHANGES
 WERE CLOUDED AND OLD SHEETS WERE NOT
 SUBMITTED, THIS REQUIRED A COMPLETELY
 NEW PLAN REVIEW.TO AVOID DELAYS,
 CLEARLY INDICATE ALL CHANGES AND SUBMIT
 OLD SHEETS AS IS STANDARD INDUSTRY
 PRACTICE.
  
 45.)ADDRESSED.
  
 46.)PROVIDE INFORMATION IN REGARDS TO
 THE BEAM ABOVE THE GARAGE DOOR.YOU
 HAVE A 16? SPAN SUPPORTING CONCRETE
 FLOOR JOISTS, A CONCRETE BALCONY AND A
 CONCRETE BLOCK 2ND FLOOR WITH NO
 STRUCTURAL INFORMATION AS TO HOW THIS
 WILL BE ACCOMPLISHED.THERE IS A NOTE
 STATING THAT LINTELS WILL GO OVER ALL
 OPENINGS.PROVIDE MORE INFORMATION.
  
 (2ND REVIEW) BEAM HAS BEEN CHANGED TO
 8X20 W/2#6.PROVIDE CALCULATIONS; IT IS
 NOT CLEAR HOW YOU ARE MAKING THESE
 CHANGES TO ACCOMODATE THE 16' SPAN
 SUPPORTING A SECOND STORY WHICH IS
 BLOCK.
  
 47.)PROVIDE A DETAIL FOR THE BEARING
 WALL, INTERIOR NON BEARING WALLS, AND
 THE CABANA WALL.
  
 NOT ADDRESSED.
  
 NEW COMMENTS, 3RD REVIEW:
  
 48.)A7.0 REFERS TO ASCE7-98, CORRECT
 REFERENCE IS ASCE7-02, FBC35.
  
 49.)THE PLANS STATE THAT ALL WINDOWS
 WILL BE IMPACT CASEMENT, SCHEDULE SHOWS
 FIXED AND SINGLE HUNG, IMPACT 2ND
 FLOOR,SHUTTERS 1ST FLOOR, AND SHUTTER
 PRODUCT APPROVALS AND S/H NON IMPACT
 WINDOW PRODUCT APPROVALS SUBMITTED.
 ADDRESS.
  
 50.)PROVIDE A SURVEY AND SOILS
 INVESTIGATION REPORT FOR THIS JOB, TWO
 ORIGINALS.I BELIEVE THAT THEY WERE IN
 THE PACKAGE AT ONE TIME.
  
 51.)THE ATTIC LIVE LOAD IS TO COMPLY
 WITH FBC TABLE 1607.1 (MIN 10PSF ATTICS
 WITHOUT STORAGE, 20 W/STORAGE).
  
 52.)NOTE THAT THIS IS A PLAN CHECK
 ONLY, PERMIT APPLICATION REQUIRED.
  
 53.)PROVIDE ONE SET OF THE OLD PLANS
 WHEN RESUBMITTING FOR REFERENCE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-02-10 Cont ID  
Sent By shill Date 2006-02-10 Time 15:48 Rev Time 5.00
Received By shill Date 2006-02-09 Time 16:26 Sent To  
Notes
2006-02-10 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ***PLAN CHECK ONLY***
  
 GOVERNING CODE IS FBC2004 EFFECTIVE
 OCTOBER 1, 2005.NO PERMIT WAS APPLIED
 FOR PRIOR TO THIS DATE.REVISE ALL
 INCORRECT CODE REFERENCES.
  
 COMMENTS FROM THE PREVIOUS REVIEW;
 NUMBERING TO REMAIN THE SAME FOR
 CONSISTENCY.NOTE THAT CODE REFERENCE
 NUMBERS HAVE CHANGED AS THE FIRST REVIEW
 WAS DONE ON FBC2001, SECOND REVIEW ON
 FBC2004.
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY PRIOR TO PERMIT ISSUANCE.
 THE PLANS MUST BE STAMPED AND THE
 RECEIPT ATTACHED TO THE APPLICATION.
 561-233-5025
  
 3.)ADDRESSED.
  
 4.)ADDRESSED.
  
 5.)THE ARCHITECT FIRM IS TO HAVE A CA
 NUMBER.TITLE BLOCK TO BE IN
 CONFORMANCE WITH FAC61G1-16.003,004.
  
 NOT ADDRESSED.NO CA NUMBER PROVIDED
 FOR FLORIDA KEY WEST DESIGN OR FLORIDA
 DESIGN ARCHITECTS.A COPY OF THE TITLE
 BLOCKS HAVE BEEN SENT TO THE ATTORNEY
 FOR THE FLORIDA BOARD OF ARCHITECTS.
  
 6.)ENERGY CALCS REQUIRED, FBC11-101.2.
 SIGN THE OWNER/AGENT LINE OF THE ENERGY
 CALC, FBC11-103.1.2.
  
  
 ENERGY CALCS WERE SUBMITTED.THE
 CEILING/FLOOR ASSEMBLY BETWEEN THE
 UNCONDITIONED GARAGE AREA AND THE
 CONDITIONED SECOND FLOOR IS NOT ON THE
 ENERGY CALCS, FIRST PAGE.SECOND PAGE
 SHOWS RAISED WOOD FLOOR ADJACENT, PLANS
 SHOW CONCRETE FLOOR.THE PLAN DOES NOT
 SHOW INSULATION BETWEEN THE LAUNDRY AREA
 IN THE GARAGE AND THE UTILITY ROOM.
 INSULATION IS SHOWN GRAPHICALLY ON A2.0
 BETWEEN FIRST AND SECOND FLOOR.
 INSULATION SHOWN GRAPHICALLY BETWEEN
 GARAGE AND ENTRY.PLEASE SPECIFY.THE
 WOOD FRAME WALL IS NOT INCLUDED IN THE
 ENERGY CALCS.
  
 7.)THE WIND RESISTANCE NOTES ON T1
 WERE PREPARED BY ANOTHER DESIGN
 PROFESSIONAL, MAKES REFERENCE TO A
 COMMERCIAL STRUCTURE, AND STATE THAT
 THIS IS A PARTIALLY ENCLOSED BUILDING
 WHICH IS NOT TO BE SHUTTERED.OTHER
 SHEETS SPECIFY IMPACT GLASS.PLEASE
 CLARIFY.
  
 SHEET T1 STILL STATES THAT THIS IS A
 PARTIALLY ENCLOSED STRUCTURE.SEE
 FBC1609.2.
  
 8.)ADDRESSED.
  
 9.)ADDRESSED.
  
 10.)ADDRESSED.
  
 11.)LOCAL OR STATE PRODUCT APPROVAL
 REQUIRED FOR:
 SHINGLE OR METAL ROOF
 WINDOWS
 MULLIONS
 FIXED GLASS WINDOWS
 FRENCH DOORS
 CASEMENT WINDOW
 OVERHEAD DOOR
 SKYLIGHTS
 IMPACT PROTECTION IF REQUIRED
 TEST REPORT AND INSTALLATION
 INSTRUCTIONS REQUIRED IN ADDITION TO THE
 FLORIDA OR LOCAL PRODUCT APPROVAL.
  
 SEPARATE PERMITS WILL BE REQUIRED FOR
 ANY PRODUCT APPROVALS NOT PROPERLY
 SUBMITTED AND REVIEWED PRIOR TO
 ISSUANCE.
  
 NONE SUBMITTED.PRODUCT APPROVALS TO BE
 REVIEWED BY DESIGNER OF RECORD
 FBC*106.3.3.
  
 12.)PLEASE READ FBC35 IN REGARDS TO
 STANDARDS.YOU MAKE REFERENCE TO
 ACI318-63 ON SHEET A3.(ALSO SPECIFIES
 300PSI CONCRETE.)THAT REFERENCE IS
 VERY OUTDATED.CHECK ALL REFERENCES.
  
 NOT ADDRESSED.PLANS STILL STATE
 ACI318-63.CHECK ALL REFERENCES.
  
 13.)ADDRESSED.
  
 14.)PROVIDE DESIGN CRITERIA REQUIRED
 BY FBC1606.1.7.NO DESIGN PRESSURES FOR
 ROOF OR COMPONENTS AND CLADDING WERE
 PROVIDED.
  
 NOT ADDRESSED.WIND SPEED AND EXPOSURE
 PROVIDED, NO COMPONENTS AND CLADDING
 DESIGN PRESSURES AND PLANS STILL STATE
 THAT THIS IS A PARTIALLY ENCLOSED
 STRUCTURE.
  
 15.)A7.0 SPECIFIES HUGHES CONNECTORS.
 THEY HAVE BEEN OUT OF BUSINESS FOR MANY
 YEARS.SPECIFY AVAILABLE, CODE
 COMPLIANT PRODUCTS ONLY.
  
 SWITCHED TO SIMPSON, BUT I AM UNABLE TO
 FIND TA STRAPS IN THE SIMPSON CATALOG.
  
 16.)A7.0 MAKES REFERENCE TO BOCA 1996.
 GOVERNING CODE IS FBC2001.
  
 NOT ADDRESSED.BOCA CODE REFERENCE
 STILL ON THE PLAN.GOVERNING CODE IS
 NOW FBC2004.
  
 17.)A7.0, PLYWOOD/GYPBOARD SHEATHING
 NOTES, ITEM 2 (NAILING PATTERN 6IN
 EDGES,
 6IN FIELD) IS NON COMPLIANT, SEE
 FBC*TABLE 2306.1.THE RESPONSE LETTER
 STATES THAT THE SHEATHING NAILING WAS
 CORRECTED TO 6IN OC EDGES AND 12IN OC
 FIELD.
  
 NOT ADDRESSED.STILL STATES 6/6.6/12
 WAS SPECIFIED IN THE RESPONSE LETTER.
 THIS IS ALSO NOT CODE COMPLIANT.SEE
 FBC TABLE 2304.9.1.
  
 18.)PROVIDE A WALL SECTION CONTINUOUS
 FOUNDATION THROUGH ROOF, INCLUDING GRADE
 IN RELATION TO FINISH FLOOR AND BOTTOM
 OF FOOTER, FBC*104.3.1.1, FBC*1804.1.7.
  
 NOT ADDRESSED.NO INFORMATION GIVEN IN
 REGARDS TO THE FIRST FLOOR BEAM.
  
 19.)WATERSTOP REQUIRED FBC2111.1.9,
 FIRST AND SECOND FLOOR.
  
 NOT ADDRESSED.THIS SHOULD BE SHOWN ON
 THE WALL SECTION WHICH WAS NOT PROVIDED.
  
 20.)WHAT IS THE CONSTRUCTION OF THE
 CABANA WALLS?IT DOES NOT APPEAR TO BE
 BLOCK.PROVIDE A DETAIL.
  
 21.)PROVIDE A STRUCTURAL DETAIL FOR
 THE BAY WINDOWS.
  
 NOT ADDRESSED.A CROSS SECTION WAS
 PROVIDED SHOWING THE STAIR AND BAY
 WINDOW.THIS IS NOT A STRUCTURAL DETAIL
 AS SPACING, FASTENING, DESIGN LOADS WERE
 NOT PROVIDED.
  
 22.)ADDRESSED.
  
 23.) PROVIDE CALCULATIONS FOR THE FILLED
 CELLS SET AT EVERY 10FT.
  
 RESPONSE LETTER STATES THAT THEY WILL BE
 EVERY 8FT, BUT THE NOTE ON A3 STATES
 10FT.2ND FLOOR, BEDROOM 3 HAS A
 DISTANCE OF OVER 12FT.
  
 24.)ADDRESSED.
  
 25.)PROVIDE WINDOW AND DOOR BUCK
 DETAILS.
  
 NOT ADDRESSED.
  
 26.)ADDRESSED.
 26.)ADDRESSED.
  
 27.)SPECIFY INSULATION FOR THE
 ADJACENT WALL (BETWEEN GARAGE AND ENTRY
 HALL).
  
 NOT ADDRESSED.SHOWN GRAPHICALLY BUT
 NOT SPECIFIED.ALSO NEEDS INSULATION
 BETWEEN THE GARAGE AND UTILITY ROOM.
  
 28.)ADDRESSED.
  
 29.)ADDRESSED.
  
 30.)APPARENTLY ADDRESSED.
  
 31.)ADDRESSED.
  
 32.)DETAILS SHOWN ON A6.0 ARE NOT
 CLEAR.COMPLETE DIMENSIONS AND
 MATERIALS ARE NOT SHOWN.
  
 AS OLD SHEETS NOT SUBMITTED, UNSURE AS
 TO WHAT THIS COMMENT REFERRED TO.
  
 31.)PROVIDE A STRUCTURAL DETAIL FOR
 THE STAIRS, WITH ALL DIMENSIONS,
 INCLUDING THE LANDING AND FIREBLOCKING
 FBC2305.1.4(3).
  
 NOT ADDRESSED.
  
 32.)SHOW ATTIC ACCESS LOCATIONS AND
 SIZE FBC2309.
  
 SPECIFY SIZE.
  
 33.)SAFETY GLASS REQUIRED AT TUBS AND
 SHOWER, FBC2405.1.
  
 ADDRESSED IF IMPACT WINDOWS ARE USED AS
 PER PLAN.
  
 34.)THE CANTILEVERED BALCONY DETAIL A6
 DOES NOT HAVE A SLAB DIMENSION.
  
 NOT ADDRESSED.
  
 35.)SPECIFY SOFFIT VENTING AND SHOW
 COMPLIANCE FBC2309.7.
  
 NOT ADDRESSED.
  
 36.)SPECIFY REACTION LOADS ON THE ROOF
 FRAMING PLAN A7.0.
  
 NOT ADDRESSED.
  
 37.)PROVIDE CALCULATIONS FOR THE BOND
 BEAM, ONE 8X8 WITH TWO #4S.
  
 NOT ADDRESSED.STILL SHOWS ONE 8X8 WITH
 TWO #4S.
  
 38.)PROVIDE DESIGN CRITERIA FOR
 HANDRAILS AND GUARDRAILS, FBC1608.2,
 FBC1007, FBC1015.STAIR DETAIL
 DIFFICULT TO READ.THE RAILING CANNOT
 BE 34", FBC1015, FBC1026.5.
  
 PROVIDE A DETAIL FOR THE RAILINGS.NOT
 ADDRESSED.
  
 39.)PROPERTY APPRAISER'S WEBSITE SHOW
 TWO LOTS WITH THIS ADDRESS, EACH WITH A
 STRUCTURE ON IT.PLEASE CLARIFY.
  
 THE PLANS SHOW TWO ADDRESSES.ADDRESS
 ON THE PLAN IS TO BE ONE ADDRESS ONLY
 WHICH SHOULD MATCH THE APPLICATION.
  
 40.) REINFORCEMENT ABOVE OPENINGS HAS
 NOT BEEN SPECIFIED.PROVIDE A SCHEDULE.
  
 ADDRESSED BY STATING THAT LINTELS WILL
 BE INSTALLED.SEE COMMENT 46 BELOW.
  
 41.) A COPY OF THE PLANS HAS BEEN
 RETAINED.
  
 ***NEW COMMENTS***
  
 42.)SHOW POSITIVE DRAINAGE FBC R401.3,
 FBC*109.3.10.
  
 43.)PLANS SHOW AN ADDRESS OF 425 AND
 423 WILDER.APPLICATION IS FOR 423
 WILDER.
  
 44.)ALL CHANGES TO THE PLAN ARE TO BE
 CLEARLY INDICATED WITH A CLOUD AND
 REVISION NUMBER.AS NONE OF THE CHANGES
 WERE CLOUDED AND OLD SHEETS WERE NOT
 SUBMITTED, THIS REQUIRED A COMPLETELY
 NEW PLAN REVIEW.TO AVOID DELAYS,
 CLEARLY INDICATE ALL CHANGES AND SUBMIT
 OLD SHEETS AS IS STANDARD INDUSTRY
 PRACTICE.
  
 45.)A WOOD LOUVER IS SHOWN ON THE LEFT
 SIDE ELEVATION, HAND WRITTEN ON THE
 PLAN.PROVIDE A STRUCTURAL DETAIL AS TO
 HOW THIS WILL BE BUILT AND COMPLY WITH
 THE WIND PROVISIONS OF FBC16.
  
 46.)PROVIDE INFORMATION IN REGARDS TO
 THE BEAM ABOVE THE GARAGE DOOR.YOU
 HAVE A 16? SPAN SUPPORTING CONCRETE
 FLOOR JOISTS, A CONCRETE BALCONY AND A
 CONCRETE BLOCK 2ND FLOOR WITH NO
 STRUCTURAL INFORMATION AS TO HOW THIS
 WILL BE ACCOMPLISHED.THERE IS A NOTE
 STATING THAT LINTELS WILL GO OVER ALL
 OPENINGS.PROVIDE MORE INFORMATION.
  
 47.)PROVIDE A DETAIL FOR THE BEARING
 WALL, INTERIOR NON BEARING WALLS, AND
 THE CABANA WALL.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-25 Cont ID  
Sent By shill Date 2005-05-25 Time 14:12 Rev Time 4.00
Received By shill Date 2005-05-24 Time 17:11 Sent To PC
Notes
2005-05-25 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY PRIOR TO PERMIT ISSUANCE.
 THE PLANS MUST BE STAMPED AND THE
 RECEIPT ATTACHED TO THE APPLICATION.
 561-233-5025
  
 3.)PROVIDE A SURVEY FOR THIS PROPERTY.
  
 4.)SOILS INVESTIGATION REPORT
 REQUIRED.
  
 5.)THE ARCHITECT FIRM IS TO HAVE A CA
 NUMBER.TITLE BLOCK TO BE IN
 CONFORMANCE WITH FAC61G1-16.003,004.
  
 6.)ENERGY CALCS REQUIRED, FBC11-101.2.
 SIGN THE OWNER/AGENT LINE OF THE ENERGY
 CALC, FBC11-103.1.2.
  
 7.)THE WIND RESISTANCE NOTES ON T1
 WERE PREPARED BY ANOTHER DESIGN
 PROFESSIONAL, MAKES REFERENCE TO A
 COMMERCIAL STRUCTURE, AND STATE THAT
 THIS IS A PARTIALLY ENCLOSED BUILDING
 WHICH IS NOT TO BE SHUTTERED.OTHER
 SHEETS SPECIFY IMPACT GLASS.PLEASE
 CLARIFY.
  
 8.)SHOW THE BAY WINDOWS ON THE SITE
 PLAN FOR ZONING REVIEW.
  
 9.)INDICATE NORTH ON THE SITE PLAN AND
 THE FLOOR PLAN.
  
 10.)REGARDING THE MITERED GLASS, SEE
 FBC2406 AND 1707.L.4.2, SHOW COMPLIANCE.
 ALSO, LOCAL OR STATE PRODUCT APPROVAL
 REQUIRED FAC9B72.
  
 11.)LOCAL OR STATE PRODUCT APPROVAL
 REQUIRED FOR:
 SHINGLE OR METAL ROOF
 WINDOWS
 MULLIONS
 FIXED GLASS WINDOWS
 FRENCH DOORS
 CASEMENT WINDOW
 OVERHEAD DOOR
 SKYLIGHTS
 IMPACT PROTECTION IF REQUIRED
 TEST REPORT AND INSTALLATION
 INSTRUCTIONS REQUIRED IN ADDITION TO THE
 FLORIDA OR LOCAL PRODUCT APPROVAL.
  
 SEPARATE PERMITS WILL BE REQUIRED FOR
 ANY PRODUCT APPROVALS NOT PROPERLY
 SUBMITTED AND REVIEWED PRIOR TO
 ISSUANCE.
  
 12.)PLEASE READ FBC35 IN REGARDS TO
 STANDARDS.YOU MAKE REFERENCE TO
 ACI318-63 ON SHEET A3.(ALSO SPECIFIES
 300PSI CONCRETE.) THAT REFERENCE IS VERY
 OUTDATED.CHECK ALL REFERENCES.
  
 13.)SHOW THE PLUMBING ON THE
 FOUNDATION PLAN.
  
 14.)PROVIDE DESIGN CRITERIA REQUIRED
 BY FBC1606.1.7.NO DESIGN PRESSURES FOR
 ROOF OR COMPONENTS AND CLADDING WERE
 PROVIDED.
  
 15.)A7.0 SPECIFIES HUGHES CONNECTORS.
 THEY HAVE BEEN OUT OF BUSINESS FOR MANY
 YEARS.SPECIFY AVAILABLE, CODE
 COMPLIANT PRODUCTS ONLY.
  
 16.)A7.0 MAKES REFERENCE TO BOCA 1996.
 GOVERNING CODE IS FBC2001.
  
 17.)A7.0, PLYWOOD/GYPBOARD SHEATHING
 NOTES, ITEM 2 (NAILING PATTERN 6? EDGES,
 6? FIELD) IS NON COMPLIANT, SEE
 FBC*TABLE 2306.1.
  
 18.)PROVIDE A WALL SECTION CONTINUOUS
 FOUNDATION THROUGH ROOF, INCLUDING GRADE
 IN RELATION TO FINISH FLOOR AND BOTTOM
 OF FOOTER, FBC*104.3.1.1, FBC*1804.1.7.
  
 19.)WATERSTOP REQUIRED FBC2111.1.9,
 FIRST AND SECOND FLOOR.
  
 20.)WHAT IS THE CONSTRUCTION OF THE
 CABANA WALLS?IT DOES NOT APPEAR TO BE
 BLOCK.PROVIDE A DETAIL.
  
 21.)PROVIDE A STRUCTURAL DETAIL FOR
 THE BAY WINDOWS.
  
 22.)PROVIDE CALCULATIONS TO JUSTIFY
 THE 16X16 FOOTER WITH TWO #5S FOR THE
 TWO STORY BLOCK STRUCTURE.A3, TYP CBS
 EDGE DETAIL AND CONCRETE WORK ITEM 3
 SHOWS 16X16, PLAN STATES 16X24.
 STRUCTURAL DETAILS SHOULD BE CONSISTENT.
  
 23.) PROVIDE CALCULATIONS FOR THE FILLED
 CELLS SET AT EVERY 10?.
  
 24.)VERTICAL FILLED CELLS SHOWN AND
 SPECIFIED ON ONE SIDE OF EACH OPENING
 ONLY.WINDOW AND DOOR TEST REPORTS
 GENERALLY HAVE A MINIMUM FASTENER
 EMBEDMENT REQUIREMENT, HOW WILL THIS BE
 ADDRESSED?
  
 25.)PROVIDE WINDOW AND DOOR BUCK
 DETAILS.
  
 26.) A4.0 WALL BETWEEN GARAGE AND ENTRY
 HALLWAY SHOWS A 6" CBS SOLID.WHAT DOES
 THIS MEAN?PROVIDE A DETAIL.
  
 27.)SPECIFY INSULATION FOR THE
 ADJACENT WALL (BETWEEN GARAGE AND ENTRY
 HALL).
  
 28.)ADJACENT DOORS SHALL BE BE EITHER
 SOLID CORE, INSULATED OR WOOD PANEL,
 CANNOT BE HOLLOW CORE (DOOR 7).
  
 29.)PROVIDE AREA CALCULATIONS ON THE
 PLAN - AREAS UNDER AIR, 1ST AND 2ND
 FLOORS, AND UNCONDITIONED SPACE.
  
 30.)CASEMENT WINDOWS ARE SPECIFIED IN
 THE WINDOW SCHEDULE, SINGLE HUNG ARE
 SHOWN.THE MASONRY OPENING SIZES DO NOT
 LEAVE ROOM FOR A WINDOW BUCK ON THE
 SIDES.
  
 31.)PROVIDE BEAM HEIGHTS ON THE PLAN.
  
 32.)DETAILS SHOWN ON A6.0 ARE NOT
 CLEAR.COMPLETE DIMENSIONS AND
 MATERIALS ARE NOT SHOWN.
  
 31.)PROVIDE A STRUCTURAL DETAIL FOR
 THE STAIRS, WITH ALL DIMENSIONS,
 INCLUDING THE LANDING AND FIREBLOCKING
 FBC2305.1.4(3).
  
 32.)SHOW ATTIC ACCESS LOCATIONS AND
 SIZE FBC2309.
  
 33.)SAFETY GLASS REQUIRED AT TUBS AND
 SHOWER, FBC2405.1.
  
 34.)THE CANTILEVERED BALCONY DETAIL A6
 DOES NOT HAVE A SLAB DIMENSION.
  
 35.)SPECIFY SOFFIT VENTING AND SHOW
 COMPLIANCE FBC2309.7.
  
 36.)SPECIFY REACTION LOADS ON THE ROOF
 FRAMING PLAN A7.0.
  
 37.)PROVIDE CALCULATIONS FOR THE BOND
 BEAM, ONE 8X8 WITH TWO #4S.
  
 38.)PROVIDE DESIGN CRITERIA FOR
 HANDRAILS AND GUARDRAILS, FBC1608.2,
 FBC1007, FBC1015.STAIR DETAIL
 DIFFICULT TO READ.THE RAILING CANNOT
 BE 34", FBC1015, FBC1026.5.
  
 39.)PROPERTY APPRAISER'S WEBSITE SHOW
 TWO LOTS WITH THIS ADDRESS, EACH WITH A
 STRUCTURE ON IT.PLEASE CLARIFY.
  
 40.) REINFORCEMENT ABOVE OPENINGS HAS
 NOT BEEN SPECIFIED.PROVIDE A SCHEDULE.
  
 41.) A COPY OF THE PLANS HAS BEEN
 RETAINED.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-05-31 Cont ID  
Sent By btrobaug Date 2006-05-31 Time 11:38 Rev Time 1.00
Received By btrobaug Date 2006-05-31 Time 07:14 Sent To M
Notes
2006-05-31 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
  
 2} 250.6 OBJECTIONABLE CURRENT OVER
 GROUNDING CONDUCTORS.
 (A) ARRANGEMENT TO PREVENT OBJECTIONABLE
 CURRENT. THE GROUNDING OF ELECTRICAL
 SYSTEMS, CIRCUIT CONDUCTORS, SURGE
 ARRESTERS, AND CONDUCTIVE
 NON?CURRENT-CARRYING MATERIALS AND
 EQUIPMENT SHALL BE INSTALLED AND
 ARRANGED IN A MANNER THAT WILL PREVENT
 OBJECTIONABLE CURRENT OVER THE GROUNDING
 CONDUCTORS OR GROUNDING PATHS.
 DISCONTINUE ONE OR MORE BUT NOT ALL OF
 SUCH GROUNDING CONNECTIONS.PREFERABLY
 AT PANEL "A".
  
 3} 220.17 APPLIANCE LOAD DWELLING
 UNIT(S).
 IT SHALL BE PERMISSIBLE TO APPLY A
 DEMAND FACTOR OF 75 PERCENT TO THE
 NAMEPLATE RATING LOAD OF FOUR OR MORE
 APPLIANCES FASTENED IN PLACE, OTHER THAN
 ELECTRIC RANGES, CLOTHES DRYERS,
 SPACE-HEATING EQUIPMENT, OR
 AIR-CONDITIONING EQUIPMENT, THAT ARE
 SERVED BY THE SAME FEEDER OR SERVICE IN
 A ONE-FAMILY, TWO-FAMILY, OR MULTIFAMILY
 DWELLING. RECALCULATE THE SERVICE LOAD
 PER 220 PART II, OR OPTIONAL
 CALCULATIONS PER 220 PART III. INDICATE
 CALCULATION USED.
  
 4} THE RANGE IS LISTED AT 8KW IN THE
 CALC'S BUT AT 25 AMPS ON A 40 AMP
 BREAKER ON THE SCHEDULE.
  
 5} 11.8.3.5 NFPA-72 WHERE STAIRS LEAD TO
 OTHER OCCUPIED LEVELS, A SMOKE ALARM OR
 SMOKE DETECTOR SHALL BE LOCATED SO THAT
 SMOKE RISING IN THE STAIRWAY CANNOT BE
 PREVENTED FROM REACHING THE SMOKE ALARM
 OR SMOKE DETECTOR BY AN INTERVENING DOOR
 OR OBSTRUCTION.ADD ONE INSIDE THE STAIR
 HALL. AFTER REVIEWING PREVIOUS NOTES,
 IREALIZED THE ARTICLES FROM THAT REVIEW
 WERE CURRENT. SEE NOTE #4, SAME INTENT,
 DIFFERENT NUMBER.
  
 6} SMOKE DETECTORS TARE REQUIRED TO BE
 INTERCONNECTED PER R313.1 FBC, 11.8.2
 NFPA-72. PLEASE SUPPLY SPECIFICATIONS
 INDICATING COMPLIANCE WITH THESE
 ARTICLES WHILE THE DETECTORS ARE BEING
 FED WITH MORE THAN ONE CIRCUIT.
  
 7} PLEASE SEE 210.11(C)(3) BATHROOM
 BRANCH CIRCUITS. IN ADDITION TO THE
 NUMBER OF BRANCH CIRCUITS REQUIRED BY
 OTHER PARTS OF THIS SECTION, AT LEAST
 ONE 20-AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY THE BATHROOM
 RECEPTACLE OUTLET(S). SUCH CIRCUITS
 SHALL HAVE NO OTHER OUTLETS.
 EXCEPTION: WHERE THE 20-AMPERE CIRCUIT
 SUPPLIES A SINGLE BATHROOM, OUTLETS FOR
 OTHER EQUIPMENT WITHIN THE SAME BATHROOM
 SHALL BE PERMITTED TO BE SUPPLIED IN
 ACCORDANCE WITH 210.23(A). ALL BATHS ARE
 IN VIOLATION EXCEPT 35 AND 38.
  
 8} 210.11(C)(1) SMALL-APPLIANCE BRANCH
 CIRCUITS. IN ADDITION TO THE NUMBER OF
 BRANCH CIRCUITS REQUIRED BY OTHER PARTS
 OF THIS SECTION, TWO OR MORE 20-AMPERE
 SMALL-APPLIANCE BRANCH CIRCUITS SHALL BE
 PROVIDED FOR ALL RECEPTACLE OUTLETS
 SPECIFIED BY 210.52(B). ONLY ONE
 CIRCUIT, #34 APPEARS TO BE A "SMALL
 APPLIANCE" CIRCUIT. IT SHOULD BE
 DESIGNATED SUCH ON THE PANEL SCHEDULE,
 ALONG WITH THE REQUIRED SECOND CIRCUIT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-01-30 Cont ID  
Sent By dpalmer Date 2006-01-30 Time 16:13 Rev Time 0.00
Received By dpalmer Date 2006-01-30 Time 11:37 Sent To M
Notes
2006-01-30 00:00:00*********** UNSAT2ND REVIEW *********
  
 ** PLEASE SEE MANY NOTES FROM PREVIOUS
 REVIEW WHICH STILL NEED TO BE ADDRESSED.
 ** PLEASE ALSO SEE NEW NOTES DUE TO
 CHANGES ON PLANS.
  
  
  
 ** PLEASE KNOW, PLANS HAVE ONLY BEEN
 SUBMITTED FOR"PLAN REVIEW"AND NOT
 FOR PERMIT.
 PLEASE KNOW, AS OF OCT 1ST, 2005 THE FBC
 HAS CHANGED TO THE 2004. PLANS MUST
 CHANGE TO THE 2004 FBC WHEN SUBMITTED
 FOR PERMIT. THIS WILL AFFECT MANY AREAS
 OF PLANS.
 PLEASE ALSO KNOW A NEW PERMIT PROCESSING
 NUMBER MAY BE GIVEN.
  
  
  
 1)NOTE: NOTE #1, NO, PLEASE SEE RESPONSE
 LTR MENTIONS THIS WAS SUBMITTED, HOWEVER
 THIS COULD NOT BE LOCATED ON PLANS.
  
 **PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2) NOTE: NOTE #2 OK, HOWEVER PLEASE SEE
 NOTE #12.
  
  
 3)NOTE: NOTE #3 NO, PLEASE SEE NEW
 COMMENT FOR CIRCUITING ON PLANS.
 PLEASE SEE THE REQUIRED DEDICATED BATH
 CIRCUIT IS SHOWN ON WITH OTHER RECEPTS
 ETC IN OTHER AREAS WHICH IS NOT
 PERMITTED.
  
 ** PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
 APPEAR TO BE SHOWN AS 20A'S HOWEVER NO
 CONDUCTORS SIZES ARE SHOWN?
  
 4)NOTE: NOTE #4 NO, PLEASE SEE MANY SD'S
 WERE ADDED, HOWEVER PLEASE STILL SE
 MISSING SD'S AS REDLINED. THESE MUST BE
 INSIDE AND OUTSIDE ALL SLEEEPING RMS.
 PLEASE ALSO SEE SD'S ARE REQUIRED TO BE
 WIRED INLINEETC , HOWEVER PLEASE SEE
 SD'S ARE BEING SHOWN TO AT LEAST 6
 SEPARATE CIRCUITS????
  
 ** SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER: NFPA-72 11.5.1.1
 PLEASE SEE REDLINED PLANS, MANY ARE
 MISSING.
  
 5)NOTE: NOTE #5 NO, PLEASE SEE CWP IS
 NOT SHOWN AS PART OF THE MAIN GROUNDING
 ELETRODE SYSTEM AS REQUIRED PER 250.50,
 250.64C
  
 **PLEASE SHOW GROUNDING ELETRODE
 SYSTEM PER 250.50. FOOTER STEEL/COLD
 WATER/ ETC. SIZE ALL PER 250.66
  
 6)NOTE: NOTE #6 NO, PLEASE SEE REDLINED
 PLANS FOR MISSING RECEPTS.
  
 ** PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
 PLEASE SEE PLANS, THERE ARE NUMEROUS
 MISSING.
 PLEASE ALSO SEE "RAIL AREA" ON SECOND
 FLR IS CONSIDERED WALL SPACE AND WILL
 REQUIRED RECEPT(S). (FLR OUTLET)
  
 7)NOTE: NOTE #7 OK.
  
  
 8)NOTE: NOTE #8 OK.
 HOWEVER PLEASE SEE NEW COMMENT FOR POOL
 PANEL.
  
  
 9)NOTE: NOTE #9 NO, PLEASE SEE THIS IS
 STILL BEING SHOWN??
  
 **PLEASE SEE 250.6,250.24, NO
 EQUIPMENT GROUNDING SHALL BE INSTALLED
 FROM METER TO MAIN.
  
 10)NOTE: NOTE #10 NO, PLEASE SEE MISSING
 IN HALL AS REDLINED ON PLANS.
  
 ** PLEASE 210.52H FOR MISSING
 REQUIRED HALL RECEPTS. MORE THAN ONE
 LOCATION.
  
 11)NOTE: NOTE #11 NO, PLEASE SEE AREAS
 WHERE ONLY A FAN IS BEING SHOWN FOR THE
 MIN OF EITHER A SWITCHED RECEPT OR LIGHT
 FIXTURE OF SOME SORT.
  
 **PLEASE SEE 210.70 FOR MISSING
 EGRESS LIGHTING CONTROL(S) IN MORE THAN
 ONE LOCATION. PLEASE ALSO SEE MISSING
 LIGHTING FOR GRADE LEVEL ACCES STAIRS.
  
 12)NOTE: NOTE #12 NO, PLEASE SEE MISSING
 GFI RECEPT PENINSULAR.
  
 ** PLEASE SEE 210.52C-1-5 FOR
 RECEPTS REQUIRED IN KITCHENS ALONG
 COUNTERSPACES ETC.
  
 13)NOTE: NOTE #13 OK.
  
 14)NOTE: NOTE #14 OK.
  
 15)NOTE: NOTE #15 OK.
  
 16)NOTE: NOTE #16 OK.
  
 17)NOTE: NOTE #17 OK.
  
 18)NOTE: NOTE #18 NO, PLEASE SHOW
 CALCUALTIONS PER NEC.
  
 ** PLEASE SEE NEC FOR LOAD
 CALCULATIONS.
 PLEASE SUBMIT LOAD CALCULATIONS BASED ON
 MIN REQUIREMENTS UNDER 220.31 ETC.
  
 19)NOTE: NOTE #19 OK, HOWEVER SEE NEW
 NOTE FOR POOL PANEL.
  
  
 20)NOTE: NOTE #20, OK, HOWEVER PLEASE
 SEE NEW NOTE FOR MIN LOAD.
  
 ** PLEASE SEE MISSING
 LAUNDRY/WASHER CIRCUIT REQUIRED PER
 220.16, 210.11C2
  
 21)NOTE: NOTE #21 OK.
  
 22)NOTE: NOTE #22 OK, WALL ADDED.
  
  
 23)NOTE: NOTE #23 NO, PLEASE SEE THIS
 COMMENT IS THE SAME AS BEFORE. PLEASE
 ALSO SEE NEW NOTES FOR SAID PLANS AND
 SET BEING RETAINED FOR POSSIBLE REVIEW
 BY THE STATE'S LEGAL COUNSEL. PLEASE SEE
 BOTH COMPANIES AS SHOWN DOES SEEM TO BE
 LICENSED AS REQUIRED AND NOTED ON
 PREVIOUS REVIEW AS REQUIRED UNDER
 FLORIDA STATUES.
 PLANS ARE NOW SIGNED.
 THIS COMMENT REMAINS FOR ALL TRADES AND
 ALL REVIEWER(S) WHETHER OR NOT COMMENT
 IS MADE BY OTHER(S).
  
 ** PLEASE SEE TITLE BLOCKS ARE
 MISSING LICENSE INFORMATION AS REQUIRED
 UNDER FAC 61G1-16.004 AND FS 481.219
 PLEASE ALSO SEE TITLE BLOCKS CHANGE FROM
 PAGE TO PAGE WITH DIFFERENT COMPANY NAME
 AND FIRMS SHOWN.
 PLEASE SEE THIS COMMENT IS FOR ALL
 TRADES AND FOR ALL SHEETS WHEATHER OR
 NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 ** NEW NOTES**
  
 1)NOTE: PLEASE CORRELAT EFLOORS WITH
 OTHER SHEETS. PLEASE SEE THE FIRST FLOOR
 IS NOTED AS THE "2ND FLR" THIS FLR
 CONTAINS THE GARAGE, POOL ETC.
 PLEASE ALSO ADJUST 2ND FLR, AS IT IS
 SHOWN AS FIRST FLR.
  
 2)NOTE: PLEASE SEE ITEM(S) IN LOAD
 CALCUALTIONS AND NOT ON SCHEDULE OR
 PLANS.
 PLEASE SEE JACUZZI, ? PLEASE ALSO SEE
 680.71 FOR GFI PROTECTION REQUIRED TO BE
 INDICATED.
  
 3)NOTE: PLEASE SEE WASHER IS NOW LISTED,
 HOWEVER THE MIN KW RATING FOR
 WASHER/LAUNDRY CIRCUIT IS 1.5 KW.
 220.16
  
 4)NOTE: PLEASE CORRELATE ALL CIRCUITING
 ON PLANS WITH PANEL SCHEDULE.
 PLEASE SEE SMALL APPLIANCE CIRCUITS
 SHOWN WITH RECEPTS OUTSIDE, BATHS ETC.
 PLEASE SEE BATHS CIRCUITS SHOWN ON
 OTHERS AS PREVIOUSLY NOTED.
 PLEASE SEE SOME CIRCUIT(S) MISSING,
 PLEASE SEE SD'S ETC ETC.
 215.5
 MANY OF THESE ARE REDLINED ON PLANS.
  
 5)NOTE: PLEASE REMOVE POOL PANEL OR
 LABLE AS "FUTURE". PLEASE KNOW, IF POOL
 IS PERMITTED DURING CONSTRUCTION OF MAIN
 HOUSE , THE PLANS WILL BE REQUIRED TO BE
 REVISED TO INCLUDE THIS.
 215.5
  
 6)NOTE: PLEASE SEE FLORIDA STATUES
 SECTION 553.80(2)(B) WITH RESPECT TO
 DESIGN PROFESSIONAL AND CODE COMPLIANT
 COMMENTS THREE OR MORE TIMES AND
 POSSIBLE 4X FEE ACCESSED TO DESIGN
 PROFESSIONALS. PLEASE KNOW THIS IS GIVEN
 ONLY A NOTICE ON THIS REVIEW.
 ** PLEASE KNOW, ONE SET OF PLANS ARE
 BEING RETAINED FOR FILE AS MENTIONED
 ABOVE.
  
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
 PLEASE SEE DUE TO THE AMOUNT OF COMMENTS
 ,CODE CORRECTIONS NEEDED, AND MISSING
 INFORMATION FURTHER COMMENTS MAY BE
 POSSIBLE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-03 Cont ID  
Sent By dpalmer Date 2005-05-03 Time 14:28 Rev Time 1.50
Received By dpalmer Date 2005-05-03 Time 14:05 Sent To M
Notes
2005-05-03 00:00:00************* UNSAT ******************
  
 PLANS SUBMITTED FOR "PLAN REVIEW ONLY
 AND NOT SUBMITTED FOR PERMIT.
 REVIEW FOR A NEW SFR.
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2) NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 3)NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
 APPEAR TO BE SHOWN AS 20A'S HOWEVER NO
 CONDUCTORS SIZES ARE SHOWN?
  
 4)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 PLEASE SEE REDLINED PLANS, MANY ARE
 MISSING.
  
 5)NOTE: PLEASE SHOW GROUNDING ELETRODE
 SYSTEM PER 250.50. FOOTER STEEL/COLD
 WATER/ ETC. SIZE ALL PER 250.66
  
 6)NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
 PLEASE SEE PLANS, THERE ARE NUMEROUS
 MISSING.
 PLEASE ALSO SEE "RAIL AREA" ON SECOND
 FLR IS CONSIDERED WALL SPACE AND WILL
 REQUIRED RECEPT(S). (FLR OUTLET)
  
 7)NOTE: PLEASE SEE MISSING RECEPT REQ'D
 FOR A/C EQUIPMENT. 210.63
  
 8)NOTE: PLEASE CORRELATE RISER DIGRAM(S
 WITH PANEL SCHEDULE(S) AND PLANS.
 PLANS INDICATE MULTIPLE PANELS A&B AND
 MSB. PLEASE SEE NO PANEL SCHEDULE
 SUBMITTED FOR PANEL "C". PLEASE SEE
 THERE ARE NUMEROUS ITEMS THAT DO NOT
 CORRELATE SERVICE AND PLANS.
  
 9)NOTE: PLEASE SEE 250.6,250.24, NO
 EQUIPMENT GROUNDING SHALL BE INSTALLED
 FROM METER TO MAIN.
  
 10)NOTE: PLEASE 210.52H FOR MISSING
 REQUIRED HALL RECEPTS. MORE THAN ONE
 LOCATION.
  
 11)NOTE: PLEASE SEE 210.70 FOR MISSING
 EGRESS LIGHTING CONTROL(S) IN MORE THAN
 ONE LOCATION. PLEASE ALSO SEE MISSING
 LIGHTING FOR GRADE LEVEL ACCES STAIRS.
  
 12)NOTE: PLEASE SEE 210.52C-1-5 FOR
 RECEPTS REQUIRED IN KITCHENS ALONG
 COUNTERSPACES ETC.
  
 13)NOTE: PLEASE SHOW ALL OUTSIDE, GARAGE
 RECEPTS ETC AS GFI/ GFI PROTECTED.
 210.8B3
  
 14)NOTE: PLEASE SEE MISSING ISCONNECTS
 FOR A/C EQUIPMENT.440.11
  
 15)NOTE: PLEASE CORRELATE LOAD
 CALCAULTIONS AND PANEL SCHEDULES FOR A/C
 EQUIPMENT. SHOWN AT 5KW. 7.5 KW, 10 KW
 ??
 ETC ETC.
  
 16)NOTE: PLEASE INCLUDE ALL CONDUCTOR
 SIZES ON PANEL SCHEDULES AND CORRELATE
 WITH THE OCP SHOWN.
 310.16,240.4
  
 17)NOTE: PLEASE SEE 210.11C1 FOR MISSING
 REQUIRED SMALL APPLIANCE CIRCUITS.
 PLEASE SEE LOAD CALCS INDICATE TWO,
 HOWEVERONE SHOWN AT 1.5KW AND THE
 OTHER AT 1.2? PLEASE SEE MIN OF 1.5KW IS
 REQUIRED PER 220.16, 210.11C1 PLEASE
 ALSO SEE PANEL SCHEDULES DO NOT INDICATE
 SMALL APPLIANCE CIRCUITS??
  
 18)NOTE: PLEASE SEE NEC FOR LOAD
 CALCULATIONS.
 PLEASE SUBMIT LOAD CALCULATIONS BASED ON
 MIN REQUIREMENTS UNDER 220.31 ETC.
  
 19)NOTE: PLEASE SEE POOL HEATER MAY NOT
 BE DERATED AT 65% AS THIS LOAD IS A
 CONTINUOUS LOAD (3 OR MORE) HOURS AND
 MUST BE SHOWN AT 125% ALONG WITH LARGEST
 MPTORS LOADS. POOL PUMP IS ALSO 125% FOR
 A CONT LOAD.215.3, 230.42 ETC.
  
 20)NOTE: PLEASE SEE MISSING
 LAUNDRY/WASHER CIRCUIT REQUIRED PER
 220.16, 210.11C2
  
 21)NOTE: PLEASE SEE THERE ARE THREE A/C
 SYSTEMS SHOWN ON PANEL SCHEDULE,
 HOWEVER, LOAD CALCS ONLY SHOWN 2???
 PLEASE CORRELATE.
 215.5
  
 22)NOTE: PLEASE SEE 110.26 FOR MIN
 CLEARENCES REQUIRED FOR A/C, AHU DISC'S.
 PLEASE ALSO SEE OCP IS NOT PERMITTED IN
 CLOTHES/ STORAGE CLOSETS.240.24D ETC
  
 23)NOTE: PLEASE SEE TITLE BLOCKS ARE
 MISSING LICENSE INFORMATION AS REQUIRED
 UNDER FAC 61G1-16.004 AND FS 481.219
 PLEASE ALSO SEE TITLE BLOCKS CHANGE FROM
 PAGE TO PAGE WITH DIFFERENT COMPANY NAME
 AND FIRMS SHOWN.
 PLEASE SEE PLANS ALSO APPEAR TO BE
 "SIGNED" WITH INITIALS WHICH ARE NOT
 ACCEPTABLE. IF INDEED THIS IS THE "LEGAL
 SIGNATURE" OF ARCH, PLEASE SUBMIT A
 SIGNED, DATED SEALED AND NOTORTIZED
 LETTER STATING LEGAL SIGNATURE.
 FS 481.221
 PLEASE SEE THIS COMMENT IS FOR ALL
 TRADES AND FOR ALL SHEETS WHEATHER OR
 NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 PLEASE SEE DUE TO THE AMOUNT OF COMMENTS
 ,CODE CORRECTIONS NEEDED, AND MISSING
 INFORMATION FURTHER COMMENTS MAY BE
 POSSIBLE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2005-05-18 Cont ID  
Sent By mwennerg Date 2005-05-18 Time 09:48 Rev Time 0.00
Received By mwennerg Date 2005-05-18 Time 09:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2005-05-18 Cont ID  
Sent By mwennerg Date 2005-05-18 Time 09:44 Rev Time 0.00
Received By mwennerg Date 2005-05-18 Time 09:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-05-26 Cont ID  
Sent By adarroug Date 2006-05-26 Time 11:11 Rev Time 0.00
Received By adarroug Date 2006-05-26 Time 11:11 Sent To E
Notes
2006-05-26 00:00:00TO "E" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-05-15 Cont ID  
Sent By adarroug Date 2006-05-15 Time 14:07 Rev Time 0.00
Received By adarroug Date 2006-05-15 Time 14:07 Sent To Z
Notes
2006-05-15 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-01-28 Cont ID  
Sent By adarroug Date 2006-01-28 Time 15:46 Rev Time 0.00
Received By adarroug Date 2006-01-28 Time 15:46 Sent To E
Notes
2006-01-28 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-01-10 Cont ID  
Sent By adarroug Date 2006-01-10 Time 14:26 Rev Time 0.00
Received By adarroug Date 2006-01-10 Time 14:26 Sent To Z
Notes
2006-01-10 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-03 Cont ID  
Sent By adarroug Date 2005-05-03 Time 11:16 Rev Time 0.00
Received By adarroug Date 2005-05-03 Time 11:16 Sent To E
Notes
2005-05-03 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-04-28 Cont ID  
Sent By adarroug Date 2005-05-25 Time 14:24 Rev Time 0.00
Received By shill Date 2005-04-28 Time 10:39 Sent To Z
Notes
2005-04-28 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-06-07 Cont ID  
Sent By tgordon Date 2006-06-07 Time 10:34 Rev Time 0.30
Received By tgordon Date 2006-06-07 Time 10:34 Sent To B
Notes
2006-06-07 00:00:00*** DENIED ***
 1) RETURN AIR DUCTS TO FIRST FLOOR ROOMS
 OFFICE, STAIR HALL, GUEST ROOM, AND
 IN-LAW BEDROOM ARE NOT SIZED OR SIZED TO
 SMALL, SEE NOTE #5.
  
 2) PLEASE SHOW OR EXPLAIN HOW RETURN AIR
 DUCTS ARE TO TIE INTO THE OPEN RETURN IN
 THE A/C CLOSET ( LOUV. DOOR R/A AND
 DUCTED RETURN AIR).
  
 3) PLEASE SUBMIT ENERGY CALCULATIONS
 FORM 600A-04 (2004) PER FBC 13-600.3.A .
  
 4) PLEASE SUBMITMANUAL J CALCULATIONS,
 PER 2004 FBC 13-607.1.ABC.1 .
  
 5)BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-01-31 Cont ID  
Sent By tgordon Date 2006-01-31 Time 11:25 Rev Time 0.30
Received By tgordon Date 2006-01-31 Time 11:25 Sent To P
Notes
2006-01-31 00:00:00*** DENIED ***
 1) MACHANICAL PLAN (DUCT LAY-OUT) IS
 DIFFICULT TO READ DUE TO SIZE.
 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY. PER 2004 FBC 106.1.1
  
 2) NO RETURN AIR PROVIDED FOR. BALANCED
 RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 4) WHEN APPLYING FOR PERMIT PLANS WILL
 NEED TO COMPLY WITH 2004 BUILDING CODES,
 AND ENERGY CALCULATIONS WILL NEEN TO BE
 ON FORM 600A-2004.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-05-18 Cont ID  
Sent By prafter Date 2005-05-18 Time 09:05 Rev Time 0.75
Received By prafter Date 2005-05-18 Time 09:05 Sent To FIRE
Notes
2005-05-18 00:00:00MECH. PLAN REVIEW:
  
 1. NO A/C EQUIPMENT INFORMATION.
  
 2. NO ENERGY CALCULATIONS FOR BUILDING.
  
 3. A/C SYSTEM MUST ADHEAR TO BALANCED
 R/A 2003 FBC/M 601.4 .
  
 4. A/C AHU MUST ADHEAR TO 2003 FBC/M
 307.2.3 FOR AUX. DRAIN PANS .
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-06-06 Cont ID  
Sent By jleech Date 2006-06-06 Time 17:03 Rev Time 0.00
Received By jleech Date 2006-06-06 Time 17:03 Sent To M
Notes
2006-06-06 00:00:00DENIED;
 SANITARY RISER DIAGRAM NOT TO CODE;
 TOO MANY CODE VIOLATIONS TO LIST.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-01-31 Cont ID  
Sent By jleech Date 2006-01-31 Time 14:46 Rev Time 1.00
Received By jleech Date 2006-01-31 Time 14:46 Sent To B
Notes
2006-01-31 00:00:00DENIED;
 1. FBC-2004 TO BE USED.
 2.THE 1/2 BATHROOMS ON 1 ST FLOOR DO NOT
 APPEAR TO HAVE THE CLEARANCES REQUIRED
 BY FBC-2004 PLUMBING SEC.405.3.1.
 3.SANIRARY RISER DIAGRAM, SIZE ALL
 PIPES, VENTING VIOLATIONS, FIXTURES MISS
 NAMED, DOES NOT FOLLOW FLOOR PLAN.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-05-03 Cont ID  
Sent By jleech Date 2005-05-03 Time 15:39 Rev Time 0.50
Received By jleech Date 2005-05-03 Time 15:39 Sent To M
Notes
2005-05-03 00:00:00PLUMBING FIXTURES MAY NOT HAVE REQUIRED
 CLEARANCES. SEE FBC 2001 PLUMBING SEC.
 405.3.1.
 PLUMBING RISER IS NOT READABLE PLEASE
 RE-DO.BEFORE RESUBING FOR PERMIT
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2006-05-24 Cont ID  
Sent By mmclean Date 2006-05-24 Time 10:29 Rev Time 0.00
Received By mmclean Date 2006-05-24 Time 10:29 Sent To I
Notes
2006-05-24 00:00:00NOTE: MUST PULL A SEPERATE PERMIT FOR
 POOL/SECK.
  
 NOTE: MUST PULL A SEPERATE PERMIT FOR
 FENCE/WALL/GATE WITH EASEMENT APPROVAL
 FROM THE CITY OF WEST PALM BEACH UTILITY
 DEPT.
  
 NOTE: MUST MAINTAIN 1000SQ FT OR 75%
 WHICHEVER IS LESS WITHIN THE FIRST 25FT
 FRONT SETBACK.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-01-27 Cont ID  
Sent By mmclean Date 2006-01-27 Time 10:38 Rev Time 0.00
Received By mmclean Date 2006-01-26 Time 18:42 Sent To I
Notes
2006-01-26 00:00:00DENIED.
 1. TOO MUCH CONCRETE WITHIN THE FRONT
 SETBACK OF PROPERTY. CAN ONLY 312.5SQ FT
 OF CONCRETE WITHIN THE FRONT SETBACK.
  
 NOTE: MUST MAINTAIN
 2. THE FRONT PORCH MUST BE 25FT WITHIN
 THE FRONT SETBACK. ROOF CAN ONLY PROJECT
 3FT INTO THE 25FT FRONT SETBACK.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-04-29 Cont ID  
Sent By adarroug Date 2005-05-03 Time 11:17 Rev Time 0.00
Received By mmclean Date 2005-04-29 Time 10:43 Sent To I
Notes
2005-04-29 00:00:00DENIED,
 1. MUST PROVIDE TWO COPY OF SURVEYS
 SHOWING THE HOUSE WITH SETBACKS.
 2. TOO MUCH CONCRETE WITHIN THE FRONT
 SETBACK 25FT.
 NOTE: MUST MEET THE ZONING REQUIRMENTS
 OF 1000SQ OR 75% OF LANDSCAPE WITHIN THE
 FRONT SETBACK (25FT)
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720