Plan Review Details - Permit 05041896
Plan Review Stops For Permit 05041896
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-06 Cont ID  
Sent By shill Date 2005-06-06 Time 14:07 Rev Time 8.00
Received By shill Date 2005-06-03 Time 12:24 Sent To  
Notes
2005-06-06 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS ARE TO BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.PLEASE CALL 233-5025 FOR
 MORE INFORMATION.
  
 3.)PROVIDE A SURVEY FOR THIS PROPERTY.
  
 4.)PROVIDE INFORMATION IN REGARDS TO
 THE MATERIALS TO BE STORED IN THIS AREA.
  
 5.)HOW HAVE YOU DETERMINED A TYPE IV
 BUILDING, SHEET T.01?SHOW COMPLIANCE
 WITH FBC TABLE 500 AND FBC CHAPTER 5
 AREA INCREASES.PRINCIPAL USE IS A1,
 FBC304.2.1.1.
  
 6.)T.01 AND S.06 SHOWS A 3 HOUR
 REQUIRED FIRE SEPARATION BETWEEN A AND
 S1 OCCUPANCY.SHEET A.08 DOES NOT SHOW
 ANY 3 HOUR FIRE RATED WALLS (SHOWS THAT
 WALL AS 1 HR), LS1 SHOWS A 1 HR.SHOW
 FIRE SEPARATION AS REQUIRED BY FBC TABLE
 704.1 AND OPENING PROTECTIVES TABLE
 705.1.2.A 3 HR IS REQUIRED FOR THE
 DOORS 06 AND 05 BUT A 45 MIN IS SHOWN ON
 A.08 DOOR SCHEDULE.
  
 7.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED FAC9B72.PLEASE
 PROVIDE PRODUCT APPROVALS ALONG WITH
 SUPPORTING DOCUMENTATION (EVALUATION,
 NOA OR TEST REPORT, INSTALLATION
 INSTRUCTIONS).WWW.FLORIDABUILDING.ORG
  
 EXTERIOR DOORS (DOUBLE AND SINGLE)
 OVERHEAD DOORS
 LOUVERS
  
 7.)SHOW EXITING FROM THE KITCHEN LS01;
 SHOULD NOT GO THROUGH A MORE HAZARDOUS
 CONDITION, FBC1001.1.4.
  
 8.)THERE ARE SOME FILLED CELLS LACKING
 FROM THE PLAN A.01; BUILDING CORNERS,
 BOTH SIDES OF OPENINGS.ACI530,
 FBC2103, PRODUCT APPROVAL ATTACHMENT
 REQUIREMENTS.
  
 9.)A.02 SHOWS THE VERTICAL
 ACCESSIBILITY AS A RAMP, 2-A.07.ACCESS
 TO THIS RAMP IS ON EXISTING RAMPS.ARE
 THESE PEDESTRIAN RAMPS OR VEHICULAR?
 YOU CANNOT USE A VEHICULAR RAMP TO
 CONNECT ACCESSIBLE ELEMENTS.WHAT IS
 THE EXISTING RAMP SLOPE?
  
 10.) 9-A.06 IS TO COMPLY WITH FBC11
 FIGURE 19; MISSING THE EXTENSION AT
 BOTTOM OF RUN.
  
 11.)A-A.07, C-A.07, FBC11-4.16.4, GRAB
 BAR BEHIND WATER CLOSET IS TO BE 36
 INCHES MINIMUM.SHOW SIDE GRAB BAR
 DIMENSION IN COMPLIANCE WITH FBC11
 FIGURE 29.
  
 12.)A.07, SHOW SIDE DIMENSIONS OF
 ACCESSIBLE LAV, FBC11 FIGURE 31.
  
 13.)SHOW CLEARANCE AT BOTTOM OF RAMPS,
 FBC11-4.8.4(2).SHOW DIRECTION CHANGE
 DIMENSION FBC11-4.8.4(2).
  
 14.) THE SERVING AREA SHOWN A.09 IS TO
 COMPLY WITH FBC11-5.5.SHOW TURNING
 SPACE FBC11-4.2.3.
  
 15.)WHAT IS THE USE OF THE KITCHEN
 COUNTER, 51 SHEET A.09?IS THIS A
 SERVING AREA?
  
 16.)THE SPACE BETWEEN THE BOTTOM RAIL
 OF THE GUARDRAIL AND THE DECK SCALES TO
 OVER 3?.THE GUARDRAILS ARE TO COMPLY
 WITH FBC1015.3.ALSO SPECIFY DESIGN
 CRITERIA FBC1608.2.1 (HANDRAILS) AND
 FBC1608.2.2 (GUARDRAILS).
  
 17.)THE HANDRAIL 3-A.10 IS TO BE
 COMPLIANT WITH FBC11 FIGURE 19.
  
 18.)S.01, C1, ACI318 STANDARD SHOULD
 BE 02, FBC3502.
  
 19.)SPECIFY SLOPE ON S.02.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-10 Cont ID  
Sent By dpalmer Date 2005-05-10 Time 08:50 Rev Time 1.50
Received By dpalmer Date 2005-05-10 Time 07:54 Sent To  
Notes
2005-05-10 00:00:00IN ELECTRIC FOR REVIEW.
 ************* UNSAT ************
  
 1)NOTE: PLEASE SUBMIT WIND LOADING
 CALCULATIONS/ WIND LOADING FOR LT POLES
 AND FIXTURES PER FBC 140 MPH.
 THIS IS REQUIRED AT THIS TIME.
  
 2)NOTE: PLEASE INCLUDE REQUIRED LICENSE
 # INFORMATION ON TITLE BLOCKS PER FAC
 61G15-23.002 AND FS 471.023.
 PLEASE SEE THIS IS REQUIRED OF ALL
 TRADES SHEETS WHEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 3)NOTE: PLEASE CORRELATE RISER DIAGRAMS
 AND PANEL SCHEDULES.
 PLEASE SEE ONE RISER SHOWS "NEW" PANEL
 SS IN BOLD AND PANELS K AND EK AS
 EXSITING? HOWEVER, SOME OF THESE ARE
 ALSO SHOWN AS NEW ON PANEL SCHEDULE(S)
 AND OTHER RISER?
 PLEASE ALSO SEE TRANSFORMER DETAIL SHOWS
 DISC('S) WHICH ARE NOT SHOWN ON RISER ?
 PLEASE SEE THERE ARE MANY ITEMS THAT DO
 NOT CORRELATE AND HAVE BEEN REDLINED.
 215.5
  
 4)NOTE: PLEASE 250.30 FOR GROUNDING OF
 TRANSFORMER TO BE SHOWN.
 PLEASE PROVIDE ATTACHMENT DETAIL.
  
 5)NOTE: PLEASE INCLUDE LOAD CALCULATIONS
 FOR ADDED LOAD TO ENTIRE SERVICE. PANEL
 HU2 IS FED FROM TWO OTHER ELECTRICAL
 PANELS/MAINS.
 PLEASE ALOS SHOW ALL CONTINUOUS LOADS AT
 125%, ALONG WITH LARGEST MOTORS LOADS.
 220,215.5
  
 6)NOTE: PLEASE SEE TRANSFOMER DETAIL
 SHOWN, SHOWS ONLY FEEDERS ETC FOR NEW
 PANEL "SS", HOWEVER OTHER PANELS ARE
 INDICATED AS NEW ALSO??
  
 7)NOTE: PLEASE SEE NOTE ON RISER
 MENTIONS; REFER TO ORIGINAL PLANS"
 PLEASE SEE THIS PROJECT/OTHER PERMITS/
 WERE COMPLETED SOME TIME AGO AND THOSE
 PLANS ARE NOT READILY AVAILABLE FOR
 VIEWING.
 ANY REFERENCES AND /OR INFORMATION
 NEEDED TO BE NOTED FROM PREVIOUS
 PLANS/DRAWINGS, NEEDS TO BE DONE ON
 PLANS SUBMITTED.
 215.5
  
 8)NOTE: PLEASE SEE 2002 NEC 210.8B3 FOR
 ALL GFI PROTECTION REQUIRED IN
 KITCHENS.SECTION 210.8(B)(3) IS NEW FOR
 THE 2002 CODE AND REQUIRES ALL 15- AND
 20-AMPERE, 125-VOLT RECEPTACLES IN
 NONDWELLING-TYPE KITCHENS TO BE GFCI
 PROTECTED. THIS REQUIREMENT APPLIES TO
 EACH AND EVERY 15- AND 20-AMPERE,
 125-VOLT KITCHEN RECEPTACLE, WHETHER OR
 NOT THE RECEPTACLE SERVES COUNTERTOP
 APPLIANCES.
  
 9)NOTE: PLEASE SEE NUMEROUS LOCATIONS ON
 RISER APPEARS TO A "NUMBERING" FOR
 NOTES, HOWEVER NO NOTES CORRELATING TO
 THESE COULD BE LOCATED ON PLANS??
 PLEASE SEE REDLINED PLANS FOR THESE.
  
 10)NOTE: PLEASE SEE 450.3 FOR MAX OPC
 FOR TRANSFORMERS> (125%).
 PLEASE SEE 125A,60A ETC SHOWN.
  
 11)NOTE: PLEASE SEE CONDUCTOR SIZE SHOWN
 @ #0??
 PLEASE SEE NEC 310.16, THIS IS NOT A
 CONDUCTOR SIZE RECOGNIZED UNDER THE AWG.
  
 PLEASE BE SURE TO SEE POSSIBLE COMMENTS
 FROM OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETS FROM SETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 ONE SET OF OLD SHEETS SHALL BE SUBMITTED
 FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2005-05-10 Cont ID  
Sent By mamini Date 2005-05-10 Time 14:43 Rev Time 0.50
Received By mamini Date 2005-05-10 Time 14:43 Sent To  
Notes
2005-05-10 00:00:00PASSED WITH PROVISOS:
  
 1. IF GARBAGE IS TO BE PICKED UP BY THE
 CITY THEN, THE DUMPSTER ENCLOSURE MUST
 HAVE A MINIMUM OF 12'-6" OPENING BETWEEN
 THE GATE POSTS AND INTERIOR DIMENSIONS
 SHOULD BE 12'-6" WIDE, 12'-0" DEEP.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-05-17 Cont ID  
Sent By mwennerg Date 2005-05-17 Time 10:28 Rev Time 0.00
Received By mwennerg Date 2005-05-17 Time 10:28 Sent To  
Notes
2005-05-17 00:00:001) ALL LIFE SAFETY SHALL COMPLY WITH
 NFPA 101, 2003 EDITION IN ACCORDANCE
 WITH FBC, SECTION 3401.7.
  
 2) PLEASE ILLUSTRATE THE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR THE GUARDS AND
 RAILINGS.
  
 3) DRAWINGS SHOW A HOOD SYSTEM IN THE
 KITCHEN. IF COOKING THAT PRODUCES GREASE
 LADEN VAPORS IS PLANNED, A UL-300
 COMPLIANT FIRE SUPPRESSION SYSTEM IS
 REQUIRED IN ACCORDANCE WITH NFPA 96.
  
 4) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR THE FIRE SPRINKLER AND
 FIRE ALARM REMODELS.
  
 5) FIRE EXTINGUISHERS ARE REQUIRED, AND
 SHALL BE LOCATED TO SATISFY THE 75'
 TRAVEL DISTANCE REQUIREMENT.
  
 6) WHAT TYPE OF COMMODITIES AND QUANTITY
 WILL BE STORED IN THE STORAGE AREA?
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910 OR 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-16 Cont ID  
Sent By shill Date 2005-06-16 Time 07:48 Rev Time 0.00
Received By shill Date 2005-06-16 Time 07:48 Sent To Z
Notes
2005-06-16 00:00:00TAKEN OFF OF BOARD, ROUTED TO ZONING
 WITH EMAIL TO MM, LM, AND JW
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2005-05-03 Time 15:46 Sent To  
Notes
2005-05-03 00:00:00TO "COMM" BD#52

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-06-14 Cont ID  
Sent By pkrauss Date 2005-06-14 Time 20:29 Rev Time 2.00
Received By pkrauss Date 2005-06-14 Time 20:14 Sent To  
Notes
2005-06-14 00:00:00DENIED:
 1.PLEASE INDICATE WHAT WILL BE STORED
 IN THE "STORAGE" AREA.
  
 2.PLAN SHEET A.01 INDICATES EXISTING
 RAMP.FRESH AIR INTAKES SHALL BE A
 MINIMUMOF 10 FT FROM LOADING DOCKS,
 PARKING LOSTS, ALLEYS, ETC. PER 2001
 FBC(M)401.5.1 & 401.5.
  
 3.EXHAUST OPENINGS SHALL NOT BE
 DIRECTED ONTO WALKWAYS PER 2001 FBC(M)
 401.5.2.
  
 4.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE PER
 2001 FBC(M) 606.2.1 & 606.4.1.
  
 HOOD/SUPRESSION REVIEW:
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPPRESSION, GAS AND WALK-IN
 COOLERS.
 1.PROVIDED ELEVATION OF THE KITCHEN
 EXHAUST FAN INDICATED ON PLAN SHEET
 M.04.SHALL COMPLY WITH 2001 FBC(M)
 506.3.14.2 & 506.3.14.3.
  
 2.PROVIDE CLEARANCE TO COMBUSTIBLES.
 INDICATE CLEARANCE REDUCTION METHODS ON
 PLAN.
  
 3.INDICATE DUCT & HOOD MATERIAL IN
 ACCORDANCE WITH 2001 FBC(M) 506.3.3 &
 507.4 RESPECTIVELY.
  
 4.AIR VELOCITY WITHIN THE GREASE DUCT
 SHALL NOT LESS THAN 1,500 FPM & NOT
 GREATER THAN 2,500 FPM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-06-09 Cont ID  
Sent By kstevens Date 2005-06-09 Time 18:32 Rev Time 9.00
Received By kstevens Date 2005-06-09 Time 18:30 Sent To  
Notes
2005-06-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ROUTE PLANS TO DBPR HOTEL & RESTURANT
 DIVISION FOR PLAN REVIEW. MINIMUM 2 SETS
 OF PLANS, REVIEWED BY DEBR SHALL BE
 RESUBMITTED FOR REVIEW, WITH DBPR STAMPS
 AND 2 PAGE "WORK SHEETS" ATTACHED SHALL
 BE RESUBMITTED FOR REVIEW. SECTION
 101.4.7.
 2. GREASE INTECEPTOR SHALL BE SIZED BY
 RODNEY COMPO, ENVIRONMENTAL COMPLIANCE
 MANAGER. PLEASE CONTACT MR. COMPO BY
 E-MAIL AT [email protected], OR FAX HIM AT
 (561) 659-7458. - PLEASE ATTACH THE
 DETERMINATION SHEET FROM MR. COMPO WITH
 PLANS WHEN RESUBMITTING.
 3. PLEASE INDICATE HOW THE STORM WATER
 WILL BE KEPT FROM DRAINING INTO THE
 DUMPSTER PAD DRAIN. AND THE CAN WASH
 SINK SECTION 104.2.1.
 4. SHTS A.01, A.07 & A.08 SHOW CLEAR
 FLOOR SPACE FOR THE FOLLOWING FIXTURES.
 ALL ACCESSIBLE WATER CLOSETS. LAVS,
 SHOWERS ECT. FOR EACH TOILET ROOM. ALSO
 SHOW THE 5' TURNING AREA IN EACH TOILET
 ROOM. SECTIONS 11-4.16.2, 11-4.19.3,
 11-4.21.2.
 5. SHOW THE FOLLOWING ACCESSIBLE FIXTURE
 REQUIREMENTS:
 FOR W/C'S
 A. 11-4.16.5 FLUSH CONTROLS
 FOR LAVS
 A. 11-4.19.3 HEIGHT & CLAEARANCES
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 FOR SHOWERS
 A. 11-4.21.3 SEAT
 B. 11-4.21.4 GRAB BARS
 C. 11-4.21.5 CONTROLS
 D. 11-4.21.6 SHOWER UNITS
 E. 11-4.21.7 CURBS
 6. SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106
 AND 1107 AND ALL SUBSECTIONS. SHOW 1/2
 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS AND ALL AREAS OF ROOFS THAT
 DRAIN ONTO THE ROOF FROM ABOVE ADDED TO
 THE SQUARE FOOTAGE OF THE ROOF AREAS.
 SHOW THE LOCATION OF ALL SECONDARY ROOF
 DRAINS.
 7. ALL P,M,E & FS SHEETS. ENGINEER SHALL
 INDICATE THE CERTIFICATION OF
 AUTHORIZATION REQUIRED BY
 61G15-23.002(2) ON EACH SHEET IN THE
 TITLE BLOCK. FS 471.025.
 8. ALL ARCHITECTURAL SHEETS. ENGINEER
 SHALL INDICATE THE CERTIFICATION OF
 AUTHORIZATION REQUIRED BY FAC
 61G15-23.002(2) ON EACH SHEET IN THE
 TITLE BLOCK. FS 471.025.
 9. SHT P.02 STORM DRAINAGE ISOMETRIC
 DOES NOT REFLECT THE ROOF DRAINAGE PLAN.
 4" DD @ 391SF SHOWN ON THE ROOF PLAN IS
 NOT SHOWN ON THE STORM RISER DIAGRAM.
 ALSO PLEASE INDICATE WHERE "ACO DECK
 DRAIN" DRAINS TO. DOES THE 4" RWL 652SF
 AND THE 4" DD 652SF TIE INTO THE SAME
 "ACO DECK DRAIN" OR IS THE 6" "ACO DECK
 DRAIN SEPARATE? SUBMIT DETAIL. SECTION
 104.2.1.
 10. SHT P.03 SANITARY & GREASE WASTE
 PIPING PLAN, AND WASTE PIPING ISOMETRICS
 SAFE WASTE NOT APPROVED. SEPARATE TRAPS
 REQUIRED FOR EACH FIXTURE. SECTION
 1002.1. - FLOOR SINKS WITH INDIRECT
 WASTE PIPES SHALL NOT BE LOCATED WHERE
 THEY CAN BE A TRIPPING HAZARD. LOCATE
 ALL FLOOR SINKS UNDER THE FIXTURES. -
 FLOOR DRAINS ARE NOT APPROVED FOR
 INDIRECT WASTE. EITHER A FLOOR SINK OR A
 HUB DRAIN IS APPROVED. SECTIONS 802.3 &
 802.3.2. - DISHWASHER SHALL DRAIN TO
 SANITARY WASTE NOT GREASE WASTE PER
 UTILITY DEPT. REQUIREMENT. - CLEANOUTS
 ARE REQUIRED NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
 SECTION 708.3.5.
 11. SHT P.04 WATER PIPING ISOMETRIC. AIR
 CHAMBERS ARE NOT APPROVED AND SHALL BE
 DELETED. ALSO WATER HAMMER ARRESTORS
 REQUIRED BY SECTION 604.9 SHALL BE
 LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING AS
 SHOWN. PDI-WH 201 AND MANUF.
 INSTALLATION INSTRUCTIONS.
 12. SHT P.04 WATER PIPING ISOMETRIC.
 FULL OPEN VALVES REQUIRED ON ALL WATER
 DOWN FEED LINES. (SEE CAN WASH) SECTION
 606.1(4) - SHUT OFF VALVES ARE REQUIRED
 AT THE HOSE BIBB. SECTION 606.2(2) - NO
 OUTLET FOR WATER FEEDING "FIAT #830-AA
 FAUCET. PLEASE INDICATE WHAT TYPE OF
 FAUCET THIS IS, WHAT ITS WHAT IS THE
 PURPOSE OF THE FLOOR DRAIN IT SERVES.
 13. SHT P.05 SAFE WASTE IS NOT APPROVED.
 DELETE DETAIL. SECTION 1002.1.
 14. SHT P.05 WATER HEATER DETAIL,
 THERMAL EXPANSION CONTROL IS REQUIRED.
 SECTION 607.3.2. - P&T DISCHARGE LINE
 SHALL DRAIN TO A FLOOR SINK OR HUB DRAIN
 FLOOR DRAINS ARE NOT APPROVED INDIRECT
 WASTE RECEPTORS. SECTIONS 802.3 AND
 802.3.2.
 15. THE FOLLOWING INFORMATION IS
 REQUIRED FOR GAS PERMIT.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. -
 SHOW ON ISOMETRIC.
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3). - INDICATE
 THE TOTAL DEVELOPED LENGTH OF EACH
 SYSTEM. (2LB FROM METER & 1/2LB
 DOWNSTREAM OF REGULATOR.)
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 F. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. - MANUAL
 VALVE SHALL BE UPSTREAM OF GAS REGULATOR
 ALSO.
 G. SUBMIT MANUF. SPECIFICATION SHEET FOR
 REGULATOR. PLEASE INDICATE MANUF., MAKE,
 AND MODEL. SECTION 303.8
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2005-06-29 Cont ID  
Sent By jroach Date 2005-06-29 Time 14:36 Rev Time 0.00
Received By jroach Date 2005-06-29 Time 14:36 Sent To  
Notes
2005-06-29 00:00:006/29/2005 ***FAILED***
  
 CONCERNS REGARDING BATHROOMS ACCESSED
 FROM THE EXTERIOR.HAVE CONTACTED THE
 ARCHITECT (ALBERT GARGIULO) SEVERAL
 TIMES AND HAVE NOT RECEIVED A CALL BACK.
  
 PLEASE CONTACT JOHN ROACH, PLANNER AT
 (561) 822-1439 REGARDING THIS MATTER.