| 2005-06-09 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. ROUTE PLANS TO DBPR HOTEL & RESTURANT |
| | DIVISION FOR PLAN REVIEW. MINIMUM 2 SETS |
| | OF PLANS, REVIEWED BY DEBR SHALL BE |
| | RESUBMITTED FOR REVIEW, WITH DBPR STAMPS |
| | AND 2 PAGE "WORK SHEETS" ATTACHED SHALL |
| | BE RESUBMITTED FOR REVIEW. SECTION |
| | 101.4.7. |
| | 2. GREASE INTECEPTOR SHALL BE SIZED BY |
| | RODNEY COMPO, ENVIRONMENTAL COMPLIANCE |
| | MANAGER. PLEASE CONTACT MR. COMPO BY |
| | E-MAIL AT [email protected], OR FAX HIM AT |
| | (561) 659-7458. - PLEASE ATTACH THE |
| | DETERMINATION SHEET FROM MR. COMPO WITH |
| | PLANS WHEN RESUBMITTING. |
| | 3. PLEASE INDICATE HOW THE STORM WATER |
| | WILL BE KEPT FROM DRAINING INTO THE |
| | DUMPSTER PAD DRAIN. AND THE CAN WASH |
| | SINK SECTION 104.2.1. |
| | 4. SHTS A.01, A.07 & A.08 SHOW CLEAR |
| | FLOOR SPACE FOR THE FOLLOWING FIXTURES. |
| | ALL ACCESSIBLE WATER CLOSETS. LAVS, |
| | SHOWERS ECT. FOR EACH TOILET ROOM. ALSO |
| | SHOW THE 5' TURNING AREA IN EACH TOILET |
| | ROOM. SECTIONS 11-4.16.2, 11-4.19.3, |
| | 11-4.21.2. |
| | 5. SHOW THE FOLLOWING ACCESSIBLE FIXTURE |
| | REQUIREMENTS: |
| | FOR W/C'S |
| | A. 11-4.16.5 FLUSH CONTROLS |
| | FOR LAVS |
| | A. 11-4.19.3 HEIGHT & CLAEARANCES |
| | B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | C. 11-4.19.5 FAUCETS |
| | FOR SHOWERS |
| | A. 11-4.21.3 SEAT |
| | B. 11-4.21.4 GRAB BARS |
| | C. 11-4.21.5 CONTROLS |
| | D. 11-4.21.6 SHOWER UNITS |
| | E. 11-4.21.7 CURBS |
| | 6. SUBMIT CALCULATIONS FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS PER SECTIONS 1106 |
| | AND 1107 AND ALL SUBSECTIONS. SHOW 1/2 |
| | AREA OF ALL VERTICAL WALLS INCLUDING |
| | PARAPETS AND ALL AREAS OF ROOFS THAT |
| | DRAIN ONTO THE ROOF FROM ABOVE ADDED TO |
| | THE SQUARE FOOTAGE OF THE ROOF AREAS. |
| | SHOW THE LOCATION OF ALL SECONDARY ROOF |
| | DRAINS. |
| | 7. ALL P,M,E & FS SHEETS. ENGINEER SHALL |
| | INDICATE THE CERTIFICATION OF |
| | AUTHORIZATION REQUIRED BY |
| | 61G15-23.002(2) ON EACH SHEET IN THE |
| | TITLE BLOCK. FS 471.025. |
| | 8. ALL ARCHITECTURAL SHEETS. ENGINEER |
| | SHALL INDICATE THE CERTIFICATION OF |
| | AUTHORIZATION REQUIRED BY FAC |
| | 61G15-23.002(2) ON EACH SHEET IN THE |
| | TITLE BLOCK. FS 471.025. |
| | 9. SHT P.02 STORM DRAINAGE ISOMETRIC |
| | DOES NOT REFLECT THE ROOF DRAINAGE PLAN. |
| | 4" DD @ 391SF SHOWN ON THE ROOF PLAN IS |
| | NOT SHOWN ON THE STORM RISER DIAGRAM. |
| | ALSO PLEASE INDICATE WHERE "ACO DECK |
| | DRAIN" DRAINS TO. DOES THE 4" RWL 652SF |
| | AND THE 4" DD 652SF TIE INTO THE SAME |
| | "ACO DECK DRAIN" OR IS THE 6" "ACO DECK |
| | DRAIN SEPARATE? SUBMIT DETAIL. SECTION |
| | 104.2.1. |
| | 10. SHT P.03 SANITARY & GREASE WASTE |
| | PIPING PLAN, AND WASTE PIPING ISOMETRICS |
| | SAFE WASTE NOT APPROVED. SEPARATE TRAPS |
| | REQUIRED FOR EACH FIXTURE. SECTION |
| | 1002.1. - FLOOR SINKS WITH INDIRECT |
| | WASTE PIPES SHALL NOT BE LOCATED WHERE |
| | THEY CAN BE A TRIPPING HAZARD. LOCATE |
| | ALL FLOOR SINKS UNDER THE FIXTURES. - |
| | FLOOR DRAINS ARE NOT APPROVED FOR |
| | INDIRECT WASTE. EITHER A FLOOR SINK OR A |
| | HUB DRAIN IS APPROVED. SECTIONS 802.3 & |
| | 802.3.2. - DISHWASHER SHALL DRAIN TO |
| | SANITARY WASTE NOT GREASE WASTE PER |
| | UTILITY DEPT. REQUIREMENT. - CLEANOUTS |
| | ARE REQUIRED NEAR THE JUNCTION OF THE |
| | BUILDING DRAIN AND THE BUILDING SEWER. |
| | SECTION 708.3.5. |
| | 11. SHT P.04 WATER PIPING ISOMETRIC. AIR |
| | CHAMBERS ARE NOT APPROVED AND SHALL BE |
| | DELETED. ALSO WATER HAMMER ARRESTORS |
| | REQUIRED BY SECTION 604.9 SHALL BE |
| | LOCATED NEAR THE FIXTURE IN AN |
| | "EFFECTIVE RANGE" NOT IN THE CEILING AS |
| | SHOWN. PDI-WH 201 AND MANUF. |
| | INSTALLATION INSTRUCTIONS. |
| | 12. SHT P.04 WATER PIPING ISOMETRIC. |
| | FULL OPEN VALVES REQUIRED ON ALL WATER |
| | DOWN FEED LINES. (SEE CAN WASH) SECTION |
| | 606.1(4) - SHUT OFF VALVES ARE REQUIRED |
| | AT THE HOSE BIBB. SECTION 606.2(2) - NO |
| | OUTLET FOR WATER FEEDING "FIAT #830-AA |
| | FAUCET. PLEASE INDICATE WHAT TYPE OF |
| | FAUCET THIS IS, WHAT ITS WHAT IS THE |
| | PURPOSE OF THE FLOOR DRAIN IT SERVES. |
| | 13. SHT P.05 SAFE WASTE IS NOT APPROVED. |
| | DELETE DETAIL. SECTION 1002.1. |
| | 14. SHT P.05 WATER HEATER DETAIL, |
| | THERMAL EXPANSION CONTROL IS REQUIRED. |
| | SECTION 607.3.2. - P&T DISCHARGE LINE |
| | SHALL DRAIN TO A FLOOR SINK OR HUB DRAIN |
| | FLOOR DRAINS ARE NOT APPROVED INDIRECT |
| | WASTE RECEPTORS. SECTIONS 802.3 AND |
| | 802.3.2. |
| | 15. THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR GAS PERMIT. |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. - |
| | SHOW ON ISOMETRIC. |
| | C. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). - INDICATE |
| | THE TOTAL DEVELOPED LENGTH OF EACH |
| | SYSTEM. (2LB FROM METER & 1/2LB |
| | DOWNSTREAM OF REGULATOR.) |
| | D. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | F. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. - MANUAL |
| | VALVE SHALL BE UPSTREAM OF GAS REGULATOR |
| | ALSO. |
| | G. SUBMIT MANUF. SPECIFICATION SHEET FOR |
| | REGULATOR. PLEASE INDICATE MANUF., MAKE, |
| | AND MODEL. SECTION 303.8 |
| | |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |