Plan Review Details - Permit 05041888
Plan Review Stops For Permit 05041888
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-14 Cont ID  
Sent By adarroug Date 2005-07-14 Time 13:31 Rev Time 0.00
Received By adarroug Date 2005-07-14 Time 13:31 Sent To M
Notes
2005-07-14 00:00:00TO "PKRAUSS" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-17 Cont ID  
Sent By shill Date 2005-06-17 Time 09:25 Rev Time 0.00
Received By shill Date 2005-06-17 Time 09:25 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-04-26 Cont ID  
Sent By adarroug Date 2005-04-26 Time 15:50 Rev Time 0.00
Received By adarroug Date 2005-04-26 Time 15:50 Sent To M
Notes
2005-04-26 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-07-21 Cont ID  
Sent By prafter Date 2005-07-21 Time 08:37 Rev Time 0.75
Received By prafter Date 2005-07-21 Time 08:37 Sent To  
Notes
2005-07-21 00:00:00MECH. PLAN REV. 7/21/05.
  
 PROVISO:BALANCED R/A 2003 FBC/M
 601.4R/A DUCT SIZE MUST BE EQUAL TO
 SUPPLY DUCT SIZE, ON DUCTED RETURN.
  
 PAT RAFTER 561/805/6728.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-07-06 Cont ID  
Sent By prafter Date 2005-07-06 Time 10:26 Rev Time 1.00
Received By prafter Date 2005-07-06 Time 10:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2005-05-03 Time   Rev Time 0.00
Received By hmoser Date 2005-05-03 Time 13:44 Sent To  
Notes
2005-05-03 00:00:00PLAN DENIED
 1) REFER TO SECTION 601.4 BALANCED
 RETURN AIR.
 2) SHOW LOCATION OF CONDENSOR AND
 CONDENSATE LINE.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732