Plan Review Details - Permit 05041811
Plan Review Stops For Permit 05041811
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-05-24 Cont ID  
Sent By mwennerg Date 2005-05-24 Time 13:19 Rev Time 0.00
Received By mwennerg Date 2005-05-24 Time 13:19 Sent To  
Notes
2005-05-24 00:00:00THIS PERMIT IS FOR THE REPLACEMENT OF
 FIRE ALARM CONDUIT IN THE LOBBY,
 MEZZANINE AND BALLROOM ONLY.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-05-12 Cont ID  
Sent By mwennerg Date 2005-05-12 Time 13:21 Rev Time 0.00
Received By mwennerg Date 2005-05-12 Time 13:21 Sent To  
Notes
2005-05-12 00:00:001) DUCT SMOKE DETECTORS SHALL BE WIRED
 TO THE FIRE ALARM PANEL, TO CAUSE A
 GENERAL ALARM PER LOCAL REQUIREMENTS.
  
 2) THE PLANS SHOW WORK ONLY IN CERTAIN
 AREAS OF THE FIRST FLOOR. DOES THIS WORK
 INCLUDE ANY GUEST ROOMS OR SUITES? IF
 SO, SINGLE STATION SMOKE DETECTORS ARE
 REQUIRED. PLANS SHOW GUEST ROOM
 DETECTORS TIED INTO THE FIRE ALARM
 SYSTEM.
  
 3) PLEASE SUBMIT A LETTER TO THE
 FOLLOWING ADDRESS IN REGARDS TO THE
 SCOPE OF YOUR WORK WITH THIS PROJECT.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 BUREAU OF FIRE PREVENTION
 500 N. DIXIE HIGHWAY
 WEST PALM BEACH, FLORIDA 33401
 T- (561) 835-2910 OR 805-6722
 F- (561) 835-2936

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-20 Cont ID  
Sent By adarroug Date 2005-05-20 Time 16:10 Rev Time 0.00
Received By adarroug Date 2005-05-20 Time 16:10 Sent To FIRE
Notes
2005-05-20 00:00:00TO "MWENNERGREN" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-02 Cont ID  
Sent By adarroug Date 2005-05-02 Time 16:36 Rev Time 0.00
Received By adarroug Date 2005-05-02 Time 16:36 Sent To FIRE
Notes
2005-05-02 00:00:00TO "F" BOX