Plan Review Details - Permit 05041807
Plan Review Stops For Permit 05041807
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-05-18 Cont ID  
Sent By alange Date 2005-05-18 Time 11:18 Rev Time 1.00
Received By alange Date 2005-05-18 Time 10:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-06-22 Cont ID  
Sent By dpalmer Date 2005-06-22 Time 12:42 Rev Time 0.33
Received By dpalmer Date 2005-06-22 Time 12:42 Sent To  
Notes
2005-06-22 00:00:00********** PROVISO/REVISION REQ'D *****
  
 PLEASE SEE NOW THAT CIRCUITING IS SHOWN
 ON PLANS AND PANEL SCHEDULE IS
 SUBMITTED, PLEASE SEE THE FOLLOWING CODE
 COMMENTS FOR CORRECTION NEEDED.
  
 1)NOTE: PLEASE SEE ALL SD'S WHICH ARE
 REQUIRED TO BE WIRED "INLINE" ARE ALL
 SHOWN ON SEPARATE CIRCUITS??? THIS IS
 NOT POSSIBLE . PLEASE ADJUST CIRCUITING,
 ALL SD'S ON SAME CIRCUIT AND THIS
 CIRCUIT SHALL BE ARC FAULT PROTECTED.
 SD'S MAY BE PLACED ON ONE OF THE BEDRM
 CIRCUITS.
 NFPA-72 8-1.4.1.6.2, 210.12
  
 2)NOTE: PLEASE SEE CIRCUITING REQ'D FOR
 "DINING RM". PLEASE SEE DIN RM RECEPTS
 ARE SHOWN ON WITH LIV RM CIRCUITS.
 210.52B1
  
 3)NOTE: PLEASE SEE GFI RECEPT PLACEMENT
 FOR WHAT APPEARS TO BE A KITCHEN
 PENINSULAR IS TO BE VERIFIED AND SHOWN
 TO MEET 210.52C3,5
  
 PLEASE MAKE THE ABOVE CORRECTIONS AND
 SUBMIT REVISED PLANS BEFORE ROUGH
 ELECTRICAL INSPECTION IS CALLED IN.
  
 PLEASE NOTE: IF PLANS COME BACK WITH AMY
 OTHER CORRECTIONS NEEDED BEFORE PERMIT
 IS ISSUED, PLEASE MAKE CORRECTIONS AT
 THATTIME. THIS WILL ALSO ALLEVIATE A
 REVSION FEE AT A LATER DATE.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-03 Cont ID  
Sent By dpalmer Date 2005-05-03 Time 13:45 Rev Time 0.30
Received By dpalmer Date 2005-05-03 Time 13:45 Sent To  
Notes
2005-05-03 00:00:00** UNSAT **'
  
 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS
 AND CORRELATE WITH A PANEL SCHEDULE TO
 BE SUBMITTED.
 215.5
  
 2)NOTE: PLEASE SEE SWITCHES SHOWN AND
 NOTED TO SW OUTLETS, HOWEVER THESE ARE
 NOTE SHOWN? PLEASE SHOW.
 215.5
  
 3)NOTE: PLEASE SEE ALL NEW CIRCUTING TO
 BEDRMS SHALL HAVE ARC FAULT PROTECTION
 AS REQUIRED UNDER 2002 NEC 210.12.
 THIS WOULD INCLUDE , RECEPTS, LTS, FANS,
 SD'S.
  
 4)NOTE: PLEASE SEE 210.52D,210.11C3 FOR
 IN 20A #12FOR BATH(S) CIRCUIT(S).
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2005-05-10 Cont ID  
Sent By mwennerg Date 2005-05-10 Time 09:22 Rev Time 0.00
Received By mwennerg Date 2005-05-10 Time 09:22 Sent To  
Notes
2005-05-10 00:00:001) THERE DOESN'T APPEAR TO BE ANYTHING
 THAT WILL EFFECT LIFE SAFETY IN THE
 SCOPE OF THIS WORK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-08 Cont ID  
Sent By shill Date 2005-06-08 Time 10:23 Rev Time 0.00
Received By shill Date 2005-06-08 Time 10:23 Sent To  
Notes
2005-06-15 00:00:00WAITING FOR COMM BOARD
  
 COMM BOARD 38
2005-06-08 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-26 Cont ID  
Sent By kstevens Date 2005-05-26 Time 18:23 Rev Time 0.00
Received By kstevens Date 2005-05-02 Time 16:47 Sent To  
Notes
2005-05-02 00:00:00TO "COMM" BD#7

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-06-30 Cont ID  
Sent By jleech Date 2005-06-30 Time 13:29 Rev Time 0.33
Received By jleech Date 2005-06-30 Time 13:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-05-26 Cont ID  
Sent By kstevens Date 2005-05-26 Time 18:15 Rev Time 0.33
Received By kstevens Date 2005-05-26 Time 18:15 Sent To  
Notes
2005-05-26 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 1. SUBMIT SANITARY RISER DIAGRAM TO SHOW
 CHANGES IN LOCATION FOR TUB, SHOWER, AND
 KITCHEN SINK. SHOW ALL PIPE SIZES,
 VENTING, AND LOCATION OF CONNECTION FOR
 EACH FIXTURES MOVED. SECTION 104.3.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]