Plan Review Details - Permit 05041760
Plan Review Stops For Permit 05041760
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2005-06-13 Cont ID  
Sent By jhiggins Date 2005-06-13 Time 09:11 Rev Time 0.00
Received By rkussner Date 2008-03-27 Time 16:12 Sent To  
Notes
2005-06-13 00:00:00ADDRESS 465 W EXECUTIVE CENTER DR
 ASSIGNED TOPARCEL ON 2/17/05. JTH.

Review Stop B BUILDING (STRUCTURAL)
Rev No 40 Status P Date 2007-12-21 Cont ID  
Sent By jwitmer Date 2007-12-21 Time 16:11 Rev Time 0.77
Received By jwitmer Date 2007-12-21 Time 16:11 Sent To  
Notes
2007-12-21 16:12:25REVISED ENERGY CALCULATIONS 11/13/07

Review Stop B BUILDING (STRUCTURAL)
Rev No 39 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jwitmer Date 2007-11-13 Time 16:23 Sent To  
Notes
2007-11-13 16:24:1811-13-07 SKYLINE FABRICATORS SHEET M-6 - OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 38 Status P Date 2007-11-13 Cont ID  
Sent By jwitmer Date 2007-11-13 Time 14:23 Rev Time 0.77
Received By jwitmer Date 2007-11-13 Time 14:23 Sent To  
Notes
2007-11-13 14:24:41SHOP DRAWINGS SKYLINE STEEL FABRICATORS SHEET M-6

Review Stop B BUILDING (STRUCTURAL)
Rev No 37 Status P Date 2007-11-09 Cont ID  
Sent By jwitmer Date 2007-11-09 Time 16:04 Rev Time 1.22
Received By jwitmer Date 2007-11-09 Time 16:04 Sent To PC
Notes
2007-11-09 16:05:03REVISION# 5, A-6.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 36 Status P Date 2007-09-30 Cont ID  
Sent By jwitmer Date 2007-09-30 Time 16:08 Rev Time 1.11
Received By jwitmer Date 2007-09-30 Time 16:08 Sent To PC
Notes
2007-09-30 16:22:07BUILDING PLAN REVIEW
 PERMIT: 05041760
 ADD: 465 W EXECUTIVE CTR DR
 CONT: THE WEITZ CO
 TEL: (561)719-0102
 FL BLD CODE= 20041FLORIDA BUILDING CODE
 WEST PALM BEACH AMENDMENTS
  
 4TH REVISIONREVIEW
 ACTION: REVIEWED
 1) SHEET # A-0.2, A-0.3, A-0.4,
 A-1.0, A-1.1, A-1.2, A-1.3, A-1.5,
 A-3.0, A-3.1, A-4.0, A-4.1, A-5.0, A-5.1,
 A-6.0, A-6.2, A-7.0, A-7.2,
 A-8.1, A-8.2, A-8.3 & A-10.1
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 35 Status F Date 2007-09-30 Cont ID  
Sent By jwitmer Date 2007-09-30 Time 08:25 Rev Time 0.33
Received By jwitmer Date 2007-09-30 Time 08:23 Sent To PC
Notes
2007-09-30 08:27:22BUILDING PLAN REVIEW
 PERMIT: 05041760
 ADD: 465 W EXECUTIVE CENTER DR
 CONT: THE WEITZ CO
 TEL: (561)719-0102
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVISION# 4REVIEW
 SHEET: A-6.1
 ACTION: DENIED
  
 SHEET A-6.1,DEETAIL 12
  
 1)THE HANDICAPPED SUITE KITHEN AREA, THE SINK BASE
 CABINET INDICATES A 2'-3" WIDTH IN THE OPENING.
 SINKS:11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER NO HIGHER THAN 34" ABOVE THE
 FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH
 30" WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH
 SINKS.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 34 Status F Date 2007-09-14 Cont ID  
Sent By jwitmer Date 2007-09-14 Time 16:42 Rev Time 0.77
Received By jwitmer Date 2007-09-14 Time 16:42 Sent To PC
Notes
2007-09-14 16:46:09BUILDING PLAN REVIEW
 PERMIT: 05041760
 ADD: 465 W EXECUTIVE CENTER DR
 CONT: THE WEITZ CO
 TEL: (561)719-0102
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 W/ * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)PLEASE PROVIDE THE FLORIDA COVERSHEETS THAT TIE TO
 THESE REPORTS. NOTE THESE REPORTS ARE TO BE UNDER THE
 2001 FBC.
 PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 33 Status P Date 2007-09-14 Cont ID  
Sent By jwitmer Date 2007-09-14 Time 16:34 Rev Time 1.11
Received By jwitmer Date 2007-09-14 Time 16:34 Sent To PC
Notes
2007-09-14 16:40:20SUBMITTALS:
 FIRESTOPPING FOR BUNDLED CABLES
 W-J3082 CABLES THROUGH MASONRY
 W-L3195 CABLES THROUGH DRYWALL
 C-AJ-3030 CABLES THROUGH MASONARY WITH SLEEVES
 ENGINEERING JUDGEMENT CAJ-3030

Review Stop B BUILDING (STRUCTURAL)
Rev No 31 Status P Date 2007-08-01 Cont ID  
Sent By jwitmer Date 2007-08-01 Time 12:45 Rev Time 0.44
Received By jwitmer Date 2007-08-01 Time 12:45 Sent To PC
Notes
2007-08-01 12:46:43REVISIONS TO THE CANOPY STEEL FRAMING.
 CALCULATIONS TO RAILING POST AND STAINLESS STEEL
 EXTENSION

Review Stop B BUILDING (STRUCTURAL)
Rev No 30 Status F Date 2007-08-01 Cont ID  
Sent By jwitmer Date 2007-08-01 Time 12:39 Rev Time 0.33
Received By jwitmer Date 2007-08-01 Time 12:39 Sent To PC
Notes
2007-08-01 12:43:51BUILDING PLAN REVIEW
 PERMIT: 05041760
 ADD: 465 W EXECUTIVE CTR DR
 CONT: THE WEITZ CO
 TEL: (561)719-0102
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SHOP DRAWING HANDRAILREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)11-4.13.6 MANEUVERING CLEARENCES AT DOORS.
 MINIMUM MANEUVERING CLEARANCES AT DOORS THAT ARE NOT
 AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH IN THE REQUIRED
 CLEARANCES SHALL BE CLEAR & LEVEL.
  
 3) THE RAISED DECK DOES NOT HAVE EDGE PROTECTION A
 WHEELCHAIR'S WHEEL COULD DROP BETWEEN THE DECK AND
 GAURDRAIL. 11-4.8.7 EDGE PROTECTION.
 RAMPS AND LANDINGS WITH DROP-OFFS SHALL HAVE CURBS,
 WALLS, RAILINGS, OR PROJECTING SURFACES THAT PREVENT
 PEOPLE FROM SLIPPING OFF THE RAMP. CURBS SHALL BE A
 MINIMUM OF 2 INCHES (50 MM) HIGH (SEE FIGURE 17 ).
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 29 Status F Date 2007-07-06 Cont ID  
Sent By jwitmer Date 2007-07-06 Time 16:32 Rev Time 0.55
Received By jwitmer Date 2007-07-06 Time 16:32 Sent To B
Notes
2007-07-06 16:35:58BUILDING PLAN REVIEW
 PERMIT:05041760
 ADD: 465 W EXECUTIVE CENTER DR
 CONT: THE WEITZ CO
 TEL: (561)719-0102
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) THE NOA'S SUBMITTED WERE NOT REVIEWED BY THE DESIGN
 PROFESSIONAL. WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 28 Status P Date 2007-07-06 Cont ID  
Sent By jwitmer Date 2007-07-06 Time 14:28 Rev Time 1.77
Received By jwitmer Date 2007-07-06 Time 14:28 Sent To PC
Notes
2007-07-06 15:33:24SUBMITTALS: SKYLINE STEEL SHOP DRAWINGS REVISIONS M-Z &
 M-3
 OVERHEAD ROLLING GRILLE FOR GIFT SHOP
 STRUCTURAL FRAMING SHOPS
 STEEL LADDER & ROOF HATCH
 FIRESTOPPING SUBMITTALS
 SKETCH 19-20 REPAIR IN STAIRWAY# 1 RELOCATION OF DOOR
 100C TO THE SOUTH SIDE OF STAIRWELL.
 BIO FIRESHIELD LECTRA STOP
 CURRIES FL5773/2004
 ARCH ALUMINUM ALUMINUM OUTSWING DOOR NOA 04-1208.01
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 27 Status P Date 2007-05-10 Cont ID  
Sent By jwitmer Date 2007-05-10 Time 08:45 Rev Time 0.55
Received By jwitmer Date 2007-05-10 Time 08:45 Sent To PC
Notes
2007-05-10 08:46:01METAL PAN STAIR SHOP DRAWINGS-OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 26 Status P Date 2007-05-07 Cont ID  
Sent By jwitmer Date 2007-05-07 Time 09:58 Rev Time 0.33
Received By jwitmer Date 2007-05-07 Time 09:58 Sent To PC
Notes
2007-05-07 09:59:35SSKYLINE STEEL SHOPS

Review Stop B BUILDING (STRUCTURAL)
Rev No 25 Status P Date 2007-05-07 Cont ID  
Sent By jwitmer Date 2007-05-07 Time 09:50 Rev Time 0.33
Received By jwitmer Date 2007-05-07 Time 09:50 Sent To  
Notes
2007-05-07 09:53:04FILIGRREE PRECAST SLAB ROOF SHORING LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 24 Status P Date 2007-05-07 Cont ID  
Sent By jwitmer Date 2007-05-07 Time 09:50 Rev Time 0.33
Received By jwitmer Date 2007-05-07 Time 09:50 Sent To  
Notes
2007-05-07 09:52:04POURED IN PLACE BEAM & SHORING ROOF LETTERES SKETCHES
2007-05-07 09:50:08FILIGREE PRECAST SLAB, ROOF SHORING LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 23 Status F Date 2007-05-07 Cont ID  
Sent By jwitmer Date 2007-05-07 Time 09:15 Rev Time 2.22
Received By jwitmer Date 2007-05-07 Time 09:15 Sent To PC
Notes
2007-05-07 09:23:37BUILDING PLAN REVIEW
 PERMIT: 05041760
 ADD: 465 W. EXECUTIVE CENTER DR
 CONT: THE WEITZ CO
 TEL: (561)719-0102
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 * WEST PALM BEACH AMENDMENTS
  
 STAIR SHOP DRAWINGREVIEW
  
 ACTION: DENIED
  
 1) 1007.3.1 RISERS SHALL BE A MAXIMUM HEIGHT OF 7 IN.
 (17.8 CM) AND A
 MINIMUM HEIGHT OF 4 IN. (10.2 CM). TREADS SHALL BE A
 MINIMUM OF 11 IN.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 22 Status P Date 2007-03-19 Cont ID  
Sent By jwitmer Date 2007-03-19 Time 13:40 Rev Time 0.55
Received By jwitmer Date 2007-03-19 Time 13:40 Sent To PC
Notes
2007-03-19 15:50:363-19-07 SUBMITTALS REVIEWED
  
 1)STRUCTURAL STUD FRAMING, EXTERIOR
 2) 6TH FLOOR BEAM AND POURED IN PLACE SLAB SHORING
 LETTERS & SKETCHES
 3) FILIGREE PRECAST SLAB SHORING LETTERS
 4) LAUNDRY CHUTE SHOP DRAWINGS
 5)SUBMITTALS SHOP DRAWINGS FOR WINDOWS, TRANSOMS &
 STOREFRONT DOORS
 6)BESAM AUTOMATIC SLIDING DOOR
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 21 Status P Date 2007-03-01 Cont ID  
Sent By jwitmer Date 2007-03-01 Time 13:16 Rev Time 0.77
Received By jwitmer Date 2007-03-01 Time 13:16 Sent To PC
Notes
2007-03-01 13:17:405TH FLOOR BEAM SHORING INSPECTION LETTER
 5TH FLOOR FILIGREE SHORING INSPECTION LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 20 Status P Date 2007-03-01 Cont ID  
Sent By jwitmer Date 2007-03-01 Time 12:21 Rev Time 0.33
Received By jwitmer Date 2007-03-01 Time 12:21 Sent To  
Notes
2007-03-01 12:21:55DAILY REPORTS 70-74

Review Stop B BUILDING (STRUCTURAL)
Rev No 19 Status N Date 2007-02-20 Cont ID  
Sent By jwitmer Date 2007-02-20 Time 09:01 Rev Time 0.00
Received By jwitmer Date 2007-02-20 Time 09:01 Sent To  
Notes
2007-02-20 09:01:42DAILY REPORTS 63-69

Review Stop B BUILDING (STRUCTURAL)
Rev No 18 Status F Date 2007-02-20 Cont ID  
Sent By jwitmer Date 2007-02-20 Time 08:46 Rev Time 0.77
Received By jwitmer Date 2007-02-20 Time 08:46 Sent To PC
Notes
2007-02-20 08:50:13BUILDING PLAN REVIEW
 PERMIT: 05041760
 ADD: 465 W EXECUTIVE CTR
 CONT: THE WEITZ CO
 TEL: (561)719-0102
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 LAUNDRY CHUTEREVIEW
 ACTION: DENIED
  
 1) DOCUMENTS SUBMITTED, TWO SETS, THIS IS A THRESHOLD
 BUILDING REQUIRING THREE SETS OF ALL DOCUMENTS
 SUBMITTED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status P Date 2007-01-25 Cont ID  
Sent By jwitmer Date 2007-01-25 Time 09:30 Rev Time 0.33
Received By jwitmer Date 2007-01-25 Time 09:30 Sent To  
Notes
2007-01-25 09:31:174TH FLOOR BEAM SHORING LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status P Date 2007-01-25 Cont ID  
Sent By jwitmer Date 2007-01-25 Time 09:27 Rev Time 0.55
Received By jwitmer Date 2007-01-25 Time 09:27 Sent To  
Notes
2007-01-25 09:28:404TH FLOOR PRE-CAST SLAB SHORING- FILIGREE- OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status F Date 2007-01-25 Cont ID  
Sent By jwitmer Date 2007-01-25 Time 07:11 Rev Time 1.11
Received By jwitmer Date 2007-01-25 Time 07:11 Sent To  
Notes
2007-01-25 07:14:34 
  
  
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 05041760
 ADD: 465 W EXECUTIVE CTR DR
 CONT: THE WEITZ CO
 TEL: (561)719-0102
  
  
 2001 FBC=2001 FLORIDA BUILDING CODE
 *= W. P. B. AMENDMENTS
  
 REVISION: REFUSE CHUTE
 REVIEW
 ACTION: DENIED
  
 1) FBC 104.2.1ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME
 AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN.PLEASE COMPLY.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
2007-01-02 13:29:413RD FLOOR DECK FILIGREE PRECAST SLAB INSPECTION LETTER
 3RD FLOOR BEAM SHORING INSPECTION LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status N Date 2006-12-14 Cont ID  
Sent By jwitmer Date 2006-12-14 Time 08:47 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2006-12-14 08:47:49DAILY INSPECTION REPORTS 27-29

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status N Date 2006-12-04 Cont ID  
Sent By jwitmer Date 2006-12-04 Time 13:06 Rev Time 0.55
Received By jwitmer Date 2006-12-04 Time 13:06 Sent To PC
Notes
2006-12-04 13:07:59PRECAST SLAB LETTER
 PRE-CAST SLAB SHORING SHOP DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status N Date 2006-12-04 Cont ID  
Sent By jwitmer Date 2006-12-04 Time 12:58 Rev Time 0.55
Received By jwitmer Date 2006-12-04 Time 12:56 Sent To  
Notes
2006-12-04 12:58:40DAILY INSPECTION REPORTS 16- 26.

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status N Date 2006-11-15 Cont ID  
Sent By jwitmer Date 2006-11-15 Time 08:19 Rev Time 0.77
Received By jwitmer Date 2006-11-15 Time 08:19 Sent To PC
Notes
2006-11-15 08:20:3211-15-06
 1) DRY- IN PLAN
 2) BEAM SHORING PLAN
 3) INSPECTION REPORTS 7-16

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status N Date 2006-10-30 Cont ID  
Sent By jwitmer Date 2006-10-30 Time 08:34 Rev Time 0.50
Received By jwitmer Date 2006-10-30 Time 08:34 Sent To  
Notes
2006-10-30 08:36:402 SUBMITTALS:
 1) WELDERS QUALIFICATION RECORD
 2) BEARING CAPACITY CERTIFICATION

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status N Date 2006-10-25 Cont ID  
Sent By jwitmer Date 2006-10-25 Time 09:39 Rev Time 0.33
Received By jwitmer Date 2006-10-25 Time 09:39 Sent To  
Notes
2006-10-25 09:40:32HAWTHORNE SUITES DAILY INSPECTION REPORTS 1-6.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status N Date 2006-10-17 Cont ID  
Sent By jwitmer Date 2006-10-17 Time 16:52 Rev Time 0.33
Received By jwitmer Date 2006-10-17 Time 16:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2006-10-17 Cont ID  
Sent By jwitmer Date 2006-10-17 Time 16:43 Rev Time 0.55
Received By jwitmer Date 2006-10-17 Time 16:43 Sent To PC
Notes
2006-10-17 16:44:55STRUCTURAL STEEL SHOP DRAWINGS JOIST SKYLINE STEEL

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status N Date 2006-08-03 Cont ID  
Sent By jwitmer Date 2006-08-03 Time 15:20 Rev Time 0.00
Received By jwitmer Date 2006-08-03 Time 15:20 Sent To  
Notes
2006-08-03 00:00:00THRESHOLD INSPECTION PLAN: SLIDER
 ENGINEERING GROUP
 PAUL BARBIERI P.E.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status N Date 2006-08-03 Cont ID  
Sent By jwitmer Date 2006-08-03 Time 15:19 Rev Time 0.00
Received By jwitmer Date 2006-08-03 Time 15:19 Sent To  
Notes
2006-08-03 00:00:00RECEIVED SPECIAL INSPECTOR AGREEMENT

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-08-03 Cont ID  
Sent By jwitmer Date 2006-08-03 Time 14:02 Rev Time 3.33
Received By jwitmer Date 2006-08-03 Time 13:13 Sent To  
Notes
2006-08-03 00:00:00 
 PERMIT: 05041760
 ADD: 465 W. EXECUTIVE CENTER DR.
 (74-43-43-20-00-000-3010)
 CONT: THE WEITZ CO.
 TEL: (561)686-5511
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 ---ISSUED PERMIT---
  
  
 BUILDING PROVISO:
  
  
 1) PLEASE SUBMIT PRODUCT APPROVAL & FL
 COVERSHEET FOR 6'-0"X7'-0"OUTSWING
 COMMERCIAL STEEL DOORS LOCATED IN ZONE #
 5 BEFORE DOOR AND WINDOW BUCK
 INSPECTION. DESIGN PRESURE FOR 6'-4"X
 7'-0" OPENING IS -68.3.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-04-12 Cont ID  
Sent By jwitmer Date 2006-04-12 Time 10:48 Rev Time 5.55
Received By jwitmer Date 2006-04-12 Time 10:48 Sent To  
Notes
2006-04-12 00:00:00PERMIT: 05041760
 ADD: XXX W. EXECUTIVE CENTER DR.
 (74-43-43-20-00-000-3010)
 CONT: THE WEITZ CO.
 TEL: (561)686-5511
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
 1)COMMENT# 3 FROM THE PREVIOUS REVIEW,
 COMPLIED.THRESHOLD INSPECTION REPORT.
  
 2) COMMENT# 5 FROM THE PREVIOUS REVIEW,
 DEALS WITH IMPACT FEES ONLY 1 SET
 STAMPED MINIMUM 2 SETS REQUIRE SSTAMP,
 AND THERE ISN'T ANY COUNTY RECEIPT IN
 PACKAGE INDICATING PAYMENT.BEFORE A
 PERMIT TO CONSTRUCT CAN BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH
 CO.,THE PERMIT PLANS STAMPED BY THEM AND
 THE RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.
  
 3A) COMMENTS 6& 7 FROM THE PREVIOUS
 REVIEW, DEALS WITH ACCESSIBILITY, FAIR
 HOUSING. ONLY 1 SEET OF PLANS APPROVED
 BY PLANNING, 3 ARE REQUIRED.
 3B) THE SIDEWALK FROM THE RIGHT-OF-WAY
 TO THE ENTRY, PLANS DO NOT INDICATE CURB
 CUTS, NOR IS THE CROSS WALK FROM POOL TO
 HOTEL ENTRY SHOW CROSS HATCHING.
 3C) HANDICAPPED PARKING WITH ACCESS
 AISLES, NO DETAILS TRANSITION FROM
 ACCESS AISLE TO SIDEWALK?
 3D) PLANS DO NOT INDICATE ACCESS TO
 DROP OFF ZONE IN FRONT OF HOTEL.
  
 4) COMMENT# 11 FROM THE PREVIOUS REVIEW
 DEALS WITH CURRIES EXTERIOR DOORS
 MISSING REPORT FOR DOUBLE DOORS
 (6'-0"X7'-0") LOCATED IN END ZONE(5).
 PRESSURES 38.6/-68.3.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-12-02 Cont ID  
Sent By jwitmer Date 2005-12-02 Time 09:39 Rev Time 4.44
Received By jwitmer Date 2005-12-02 Time 07:08 Sent To  
Notes
2005-12-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05041760
 ADD: XXX W. EXECUTIVE CENTER DR.
 (74-43-43-20-00-000-3010)
 CONT: THE WEITZ CO.
 TEL: (561)686-5511
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) COMMENT# 2FROM THE PREVIOUS REVIEW,
 PERMIT APPLICATION CORRECT THE PCN TO
 (74-43-43-20-00-000-3010) OR PROVIDE
 ADDITIONAL INFORMATION.THE CITY GIS
 SYSTEM ONLY INDICATES A SINGLE LOT SEE
 ATTACHED PAGES. OWNER AS COURTNEY LAKES
 APARTMENTS LLC. PALM BEACH COUNTY
 PROPERTY APPRAISERS OFFICE INDICATES
 THIS SINGLE LOT HAS BEEN REPLATED INTO
 (5) LOTS. THE CITY HAS NOT RECEIVED A
 COPY OF THE REPLAT TO UPDATE OUR LAND
 FILE AND TO ADDRESS THE NEWLY FORMED
 LOTS. PROVIDE A COPY OF THE RECORDED
 REPLAT!!!!!
  
 2) COMMENT# 3 FROM THE PREVIOUS REVIEW
 SEE ATTACHMENT,LOW VALUE, CALCULATED
 VALUE IS: $9,907,170.00 SEE ADDITIONAL
 FEES.
  
 3) COMMENT# 5 FROM THE PREVIOUS
 REVIEWDEALS WWITH THE THRESHOLD
 INSPECTOR FORMS TO BE FILLED OUT,WPB
 AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 4) COMMENT# 7FROM THE PEVIOUS REVIW,
 903.8.2 FLOR ST STATUTE 553.895(2)
 ALL RESIDENTIAL BUILD. 3 OR MORE STORIES
 TALL WHETHER DESIGNATED AS TOWNHOUSE,
 CONDOMINIUMS, "APARTMENT HOUSES,
 TENEMENTS, GARDEN APARTMENTS OR BY ANY
 OTHER NAME SHALL BE SUPPLIED BY FIRE
 SPRINKLERS MEETING NFPA 101. SINCE THE
 FIRE SPRINKLERS ARE REQUIRED BY CODE
 THEY MUST BE PART OF THE PERMIT PACKAGE.
  
 5)COMMENT# 10 FROM THE PREVIOUS REVIEW,
 BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6) COMMENT# 3A) FROM THE PREVIOUS REVIEW
  
 DEALS WITH CROSSWALKS FOR ACCESSIBLE
 ROUTES, PLEASE INDICATE WHERE THE
 ACCESSIBLE ROUTE IS ON EITHER C-2 OR
 C-3, ALSO INDICATE FLARED CURBING FOR
 SIDEWALKS.11-4.1.2(1) AT LEAST ONE
 ACCESSIBLE ROUTE COMPLYING WITH ?11-4.3
 SHALL BE PROVIDED WITHIN THE BOUNDARY OF
 THE SITE FROM PUBLIC TRANSPORTATION
 STOPS, ACCESSIBLE PARKING SPACES,
 PASSENGER LOADING ZONES IF PROVIDED, AND
 PUBLIC STREETS OR SIDEWALKS, TO AN
 ACCESSIBLE BUILDING ENTRANCE.
  
 7) PLANS INDICATE THE ACCESSIBLE PARKING
  
 COMMENT# 14 FROM THE PREVIOUS REVIEW,
  
 THE ACCESSIBLE PARKING SPACES ARE TO BE
 ON THE SHORTEST ROUTE OF TRAVEL.
 11-4.6.2 LOCATION. ACCESSIBLE PARKING
 SPACES SERVING A PARTICULAR
 BUILDING SHALL BE LOCATED ON THE
 SHORTEST SAFELY ACCESSIBLE ROUTE OF
 TRAVEL FROM ADJACENT PARKING TO AN
 ACCESSIBLE ENTRANCE.IN PARKING
 FACILITIES THAT DO NOT SERVE A
 PARTICULAR BUILDING, ACCESSIBLE PARKING
 SHALL BE LOCATED ON THE SHORTEST
 ACCESSIBLE ROUTE OF TRAVEL TO AN
 ACCESSIBLE PEDESTRIAN ENTRANCE OF THE
 PARKING FACILITY.IN BUILDINGS WITH
 MULTIPLE ACCESSIBLE ENTRANCES WITH
 ADJACENT PARKING, ACCESSIBLE PARKING
 SPACES SHALL BE DISPERSED AND LOCATED
 CLOSEST TO THE ACCESSIBLE ENTRANCES.
  
 8) COMMENT# 18 FROM THE PREVIOUS REVIEW
 INDICATE COMPLIANCE WITH 11-9.1.4(1) FOR
 SUITE TYPE "C".18) 11-9.1.4(1) IN
 ORDER TO PROVIDE PERSONS WITH
 DISABILITIES A RANGE OF OPTIONS
 EQUIVALENT TO THOSE AVAILABLE TO OTHER
 PERSONS SERVED BY THE FACILITY, SLEEPING
 ROOMS AND SUITES REQUIRED TO BE
 ACCESSIBLE BY11-9.1.2 SHALL BE
 DISPERSED AMONG THE VARIOUS CLASSES OF
 SLEEPINGACCOMMODATIONS AVAILABLE TO
 PATRONS OF THE PLACE OF TRANSIENT
 LODGING.FACTORS TO BE CONSIDERED
 INCLUDE ROOM SIZE, COST, AMENITIES
 PROVIDED, & THE NUMBER OF BEDS PROVIDED.
  
 9) COMMENT FROM# 24 FROM THE PREVIOUS
 REVIEW, THERE SEEMS TO BE CONFUSION ON
 THE LAUNDRY& REFUSE CHUTE ON LOCATION
 SEE A-1.2 & A-1.3 .
  
 10) COMMENT # 26 FROM THE PREVIOUS
 REVIEW, MISSING RATING ON DOORS LEADING
 TO REFUSE & LAUNDRY ROOMS A 3/4HR
 RATING.705.2.4.3 REFUSE AND LAUNDRY
 CHUTE ACCESS ROOMS.ACCESS OPENINGS
 FOR REFUSE AND LAUNDRY CHUTES SHALL BE
 LOCATED IN ROOMS OR COMPARTMENTS
 COMPLETELY ENCLOSED BY CONSTRUCTION AND
 OPENING PROTECTIVES IN ACCORDANCE WITH
 TABLE 705.1.2.ACCESS OPENINGS TO
 REFUSE AND LAUNDRY CHUTES SHALL NOT BE
 LOCATED IN EXIT ACCESS CORRIDORS OR EXIT
 ENCLOSURES.
  
 11) COMMENT# 40 FROM THE PREVIOUS REVIEW
 DEALS WITH CURRIES EXTERIOR DOORS IN END
 ZONE# 5, REPORT GOOD FOR +/- 62 REQUIRES
 A -68.3.
  
 12) COMMENT# 41 FROM THE PREVIOUS REVIEW
  
 DEALS WITH RESAM AES AUTO DOORS, ARCH
 PLANS A4.1 SECTION# 1 INDICATES A NEW
 STEEL MULLION NOT DEPICTED ON STRUCRURAL
 PLANS. 1707.4.5.2 MULLIONS SHALL BE
 DESIGNED TO TRANSFER THE DESIGN PRESSURE
 LOADS APPLIED BY THE WINDOW OR DOOR
 ASSEMBLIES TO THE ROUGH OPENING
 SUBTRATE. INDICATE COMPLIANCE.
  
 13) A-3.0 WINDOW SCHEDULE INDICATES A
 WINDOW TYPE "A" BUT DOESN'T INDICATE IF
 THIS IS A HORIZONTAL SLIDER OR FIXED?
 IF THE WINDOWS ARE SLIDERS THE REPORT
 WAS TESTED WITH A 63" WINDOW WHEREAS THE
 PLANS CALL FOR A 65" WINDOW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-08 Cont ID  
Sent By jwitmer Date 2005-06-08 Time 14:38 Rev Time 12.00
Received By jwitmer Date 2005-06-08 Time 14:38 Sent To  
Notes
2005-06-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05041760
 ADD: XXX W. EXECUTIVE CENTER DR.
 (74-43-43-20-00-000-3010)
 CONT: THE WEITZ CO.
 TEL: (561)686-5511
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) ADDRESS TO BE DETERMINED BY CITY MIS
 DEPARTMENT, JOHN HIGGINS 822-1239.
  
 2) PERMIT APPLICATION CORRECT THE PCN TO
 (74-43-43-20-00-000-3010) OR PROVIDE
 ADDITIONAL INFORMATION.
  
 3) LOW VALUE, CALCULATED VALUE IS:
 $9,907,170.00 SEE ADDITIONAL FEES.
  
 4) FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGEN-
 CY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESH-
 OLD BUILDING. THE PURPOSE OF THE SRUCTUR
 AL INSPECTION PLAN IS TO PROVIDE SPECIF-
 IC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
 S-7 SHORING NOTES, SHORING TO BE SET
 BY CONTRACTOR BUT THE THRESHOLD
 INSPECTOR TO SIGN OFF FOR APPROVAL.
  
 5) WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 6) W.P.B. AMENDMENT 105.13.4.4 ALL PLANS
 FOR THE BUILDING WHICH ARE REQUIRED TO
 BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR
 ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 7) 903.8.2 FLOR ST STATUTE 553.895(2)
 ALL RESIDENTIAL BUILD. 3 OR MORE STORIES
 TALL WHETHER DESIGNATED AS TOWNHOUSE,
 CONDOMINIUMS, "APARTMENT HOUSES,
 TENEMENTS, GARDEN APARTMENTS OR BY ANY
 OTHER NAME SHALL BE SUPPLIED BY FIRE
 SPRINKLERS MEETING NFPA 101.
  
 8) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS:
 A) THE REPORT SUBMITTED DOES HAVE A
 RAISED SEAL BUT THE SIGNATURE IS COPIED.
 B) TEST BORING SHEETS COPIED NOT SIGNED
 OR SEALED.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 9) SURVEY OR SITE PLAN WITH THE
 FOOTPRINT LOCATED ON PROPERTY,WITH
 DIMENSIONS TO THE PROPERTY LINES,
 TABLE 600,% OF ALLOWABLE OPENINGS.
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 11) HANSON PROFESSIONAL SERVICES TO
 COMPLY WITH CERTIFICATE OF AUTHORIZATION
 NUMBER TO BE ON PLANS, THE ADDRESS
 LISTED WITH THE STATE OF FL IS
 SPRINGFIELD, ILL. 481.219 F.S.
 CERTIFICATE OF AUTHORIZATION.THE TITLE
 BLOCK FOR ANY SHEET BEARING THE NAME OF
 AN ARCHITECT PRACTICING UNDER A
 FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE THE CERTIFICATE
 OF AUTHORIZATION NUMBER.
  
 12)A-0.1 CONSTRUCTION TYPE INDICATES THE
 BUILDING TO BE A TYPE IV, UNPROTECTED,
 FULLY SPRINKLERED STRUCTURE, HOWEVER
 SHEET A-3.0 INDICATES TOP OF BUILDING TO
 BE 71.66' WITH 6 STORIES. THIS IS IN
 EXCESS OF THE ALLOWABLE 55' AND 5
 STORIES ALLOWED UNDER TABLE 500.
 FOOTNOTE "H" DOES NOT ALLOW FOR A STORY
 INCREASE.THIS IS A TYPE II
 CONSTRUCTION. SEE TABLE 500 AND 604.
  
 13A) PROVIDE: 11-4.1.2(1) AT LEAST ONE
 ACCESSIBLE ROUTE COMPLYING WITH 11-4.3
 SHALL PROVIDED WITHIN THE BOUNDARY OF
 THE SITE FROM PUBLIC TRANSPORTATION
 STOPS, ACCESSIBLE PARKING SPACES,
 PASSENGER LOADING ZONES IF PROVIDED, AND
 PUBLIC STREETS OR SIDEWALKS, TO AN
 ACCESSIBLE BUILDING ENTRANCE.
  
 13B) PROVIDE: 11-4.1.3(1) AT LEAST ONE
 ACCESSIBLE ROUTE COMPLYING WITH 11-4.3
 SHALL CONNECT ACCESSIBLE BUILDING OR
 FACILITY ENETRANCES WITH ALL ACCESSIBLE
 SPACES AND ELEMENTS WITHIN THE BUILDING
 OR FACILITY.
  
 14)11-4.6.2 LOCATION. ACCESSIBLE PARKING
 SPACES SERVING A PARTICULARBUILDING
 SHALL BE LOCATED ON THE SHORTEST SAFELY
 ACCESSIBLE ROUTE OFTRAVEL FROM
 ADJACENT PARKING TO AN ACCESSIBLE
 ENTRANCE.IN PARKINGFACILITIES THAT
 DO NOT SERVE A PARTICULAR BUILDING,
 ACCESSIBLE PARKINGSHALL BE LOCATED ON
 THE SHORTEST ACCESSIBLE ROUTE OF TRAVEL
 TO ANACCESSIBLE PEDESTRIAN ENTRANCE
 OF THE PARKING FACILITY.IN BUILDINGS
 WITHMULTIPLE ACCESSIBLE ENTRANCES
 WITH ADJACENT PARKING, ACCESSIBLE
 PARKING SPACES SHALL BE DISPERSED AND
 LOCATED CLOSEST TO THE ACCESSIBLE
 ENTRANCES. EACH PARKING SPACE MUST BE NO
 LESS THAN 12 FEET WIDE.
  
 15) PROVIDE COMPLIANCE WITH HEAD ROOM
 BENEATH STAIRS- A BARRIEER TO WARN BLIND
 OR VISUALLY IMPAIRED PERSONS SHALL BE
 PROVIDED.11-4.4.2.SEE SHEET A-7.0 .
  
 16A) 11-9.1.2 PLANS INDICATE 120
 SLEEPING UNITS, 11-9.1.2 REQUIRES 2
 ROOMS WITH ROLL IN SHOWERS, PROVIDE
 COMPLIANCE.
  
 16B) FL S. S. 509 A NUMBER OF ROOMS
 EQUALING AT LEAST 5% OF THE GUEST ROOMS
 MINUS THE NUMBER OF "ACCESSIBLE ROOMS"
 REQUIRED BY THE TABLE IN 11-9.1.2 SHALL
 PROVIDE THE ADDITIOINAL SPECIAL
 ACCESSIBILTY FEATURES OF 11-9.2.3
 11-9.2.3 HOTEL, MOTEL AND CONDOMINIUM
 SPECIAL ACCESSIBILITY FEATURE.
 NOTHING IN THIS SECTION SHALL BE
 CONSTRUED AS RELIEVING THE OWNER OF THE
 RESPONSIBILITY OF PROVIDING ACCESSIBLE
 ROOMS IN CONFORMANCE WITH 11-9.1
 11-9.5 OF THE CODE.
  
 IN ALL BUILDINGS, STRUCTURES AND
 FACILITIES LICENSED AS A HOTEL, MOTEL OR
 RESORT CONDOMINIUM PURSUANT TO CHAPTER
 509, FLORIDA STATUTES, A NUMBER
 OF ROOMS EQUALING AT LEAST 5 PERCENT
 OF THE GUEST ROOMS MINUS THE NUMBER
 OF ACCESSIBLE ROOMS REQUIRED BY THE
 TABLE IN 11-9.1.2 SHALL PROVIDE THE
 FOLLOWING ADDITIONAL SPECIAL
 ACCESSIBILITY FEATURES:
  
 11-9.2.3(1) GRAB RAILS IN BATHROOMS
 AND TOILET ROOMS WHICH COMPLY
 WITH ?11-4.16.4 OF THIS CODE.
  
 11-9.2.3(2) ALL BEDS IN DESIGNED
 ACCESSIBLE GUEST ROOMS SHALL BE
 OPEN-FRAME TYPE TO PERMIT PASSAGE OF
 LIFT DEVICES.
  
 11-9.2.3(3) ALL STANDARD WATER
 CLOSET SEATS SHALL BE AT A HEIGHT OF
 15 INCHES, MEASURED VERTICALLY FROM
 THE FINISH FLOOR TO THE TOP OF THE
 SEAT, WITH A VARIATION OF PLUS OR
 MINUS 1/2 INCH.A PORTABLE OR
 ATTACHED RAISED TOILET SEAT SHALL BE
 PROVIDED IN ALL DESIGNATED
 PERMANENT DISABILITY ACCESSIBLE
 ROOMS.
  
  
 17) 11-9.3.1 GENERAL. IN SLEEPING ROOMS
 REQUIRED TO COMPLY WITH THISSECTION,
 AUXILIARY VISUAL ALARMS SHALL BE
 PROVIDED AND SHALL COMPLY WITH
 ?11-4.28.4.VISUAL NOTIFICATION
 DEVICES SHALL ALSO BE PROVIDED IN
 UNITS, SLEEPING ROOMS AND SUITES TO
 ALERT ROOM OCCUPANTS OF INCOMING
 TELEPHONE CALLS AND A DOOR KNOCK OR
 BELL.
  
 18) 11-9.1.4(1) IN ORDER TO PROVIDE
 PERSONS WITH DISABILITIES A RANGE OF
 OPTIONS EQUIVALENT TO THOSE AVAILABLE
 TO OTHER PERSONS SERVED BY THE
 FACILITY, SLEEPING ROOMS AND SUITES
 REQUIRED TO BE ACCESSIBLE BY
 11-9.1.2 SHALL BE DISPERSED AMONG THE
 VARIOUS CLASSES OF SLEEPING
 ACCOMMODATIONS AVAILABLE TO PATRONS OF
 THE PLACE OF TRANSIENT LODGING.
 FACTORS TO BE CONSIDERED INCLUDE ROOM
 SIZE, COST, AMENITIES PROVIDED, AND
 THE NUMBER OF BEDS PROVIDED.
  
 19) 11-9.4 OTHER SLEEPING ROOMS AND
 SUITES. DOORS AND DOORWAYS DESIGNED TO
 ALLOW PASSAGE INTO AND WITHIN ALL
 SLEEPING UNITS OR OTHER COVERED UNITS
 SHALL COMPLY WITH 11-4.13.5. CLEAR
 WIDTH.
  
 20A) 11-4.10.5 RAISED AND BRAILLE
 CHARACTERS ON HOISTWAY ENTRANCES.
  
 20B) 11-4.10.12(2) TACTILE, BRAILLE, AND
 VISUAL CONTROL INDICATORS.
  
 21) 11-4.30 SIGNAGE.?11-4.30.1
 GENERAL. SIGNAGE REQUIRED TO BE
 ACCESSIBLE BY ?11-4.1 SHALL COMPLY WITH
 THE APPLICABLE PROVISIONS OF ?11-4.30.
  
  
  
 22)SHEET A-1.0 HAWTHORN ROOMPROVIDE
 USEAGE, FOR THIS REVIEW CONSIDERED AS
 RESTRAUNT OCC LOAD 2104/15= 141
 OCCUPANTS REQUIRES (2) EXITS, 1/3 THE
 DISTANCE OF THE ROOM APART, 1004.1.4
 WHERE 2 OR MORE EXITS OR EXIT ACCESS
 DOORS ARE REQUIED, AT LEAST 2 OF THE
 EXIT OR EXIT ACCESS DOORS SHALL BE
 PLACED A DISTANCE APART EQUAL TO NOT
 LESS THAN 1/2 OF THE LENGTH OF THE
 MAXIMUM OVERALL DIAGONAL DIMENSION OF
 THE BUILDING OR AREA TO BE SERVED,
 (1/3RD DISTANCE FOR FIRE SPRINKLERED
 BUILDINGS).
  
 23)SHEET A-1.0,/A- 6.3 TRIM CIRCULAR
 COLUMN WRAP, CHAIRAIL AND 8" CROWN
 MOLDING, PROVIDE ADDITIONAL DETAILS SEE
 803.4 FOAM PLASTICS. FOAM PLASTICS SHALL
 NOT BE USED AS INTERIOR FINISH.4
 EXECPTIONS.
  
 24) SHEET A-1.0705.2.4.1 GENERAL.
 REFUSE AND LAUNDRY CHUTES, ACCESS AND
 TERMINATION ROOMS AND INCINERATOR ROOMS
 SHALL BE CONSTRUCTED IN ACCORDANCE WITH
 705.2.4.2 THROUGH 705.2.4.6.INDICATE
 COMPLIANCE
  
 25) SHEET A-1.0 705.2.4.4 TERMINATION
 ROOM. REFUSE AND LAUNDRY CHUTES SHALL
 DISCHARGE INTO AN ENCLOSED TERMINATION
 ROOM COMPLETELY SEPARATED FROM THE
 REMAINDER OF THE BUILDING BY
 CONSTRUCTION AND OPENING PROTECTIVES
 IN ACCORDANCE WITH TABLE 705.1.2.
 REFUSE CHUTES SHALL NOT TERMINATE IN AN
 INCINERATOR ROOM. INDICATE COMPLIANCE
  
 26) SHEET A-1.2/ A-1.3705.2.4.3
 REFUSE AND LAUNDRY CHUTE ACCESS ROOMS.
 ACCESS OPENINGSFOR REFUSE AND
 LAUNDRY CHUTES SHALL BE LOCATED IN ROOMS
 OR COMPARTMENTSCOMPLETELY ENCLOSED
 BY CONSTRUCTION AND OPENING PROTECTIVES
 IN ACCORDANCE WITH TABLE 705.1.2.
 ACCESS OPENINGS TO REFUSE AND LAUNDRY
 CHUTES SHALL NOT BE LOCATED IN EXIT
 ACCESS CORRIDORS OR EXIT ENCLOSURES.
 INDICATE COMPLIANCE.
  
 27) ALL RATED CORRIDORS, ETC:
 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 28) 1016.4 STAIR IDENTIFICATION. AN
 APPROVED SIGN SHALL BE LOCATED AT EACH
 FLOOR LEVEL LANDING IN ALL ENCLOSED
 STAIRWAYS OF BUILDINGS FOUR OR MORE
 STORIES IN HEIGHT.THE SIGN SHALL
 INDICATE THE FLOOR LEVEL AND THE
 AVAILABILITY OF ROOF ACCESS FROM THAT
 STAIRWAY AND AN IDENTIFICATION OF THE
 STAIRWAY.THE SIGN SHALL ALSO STATE THE
 FLOOR LEVEL OF AND DIRECTION TO
 EXIT DISCHARGE.THE SIGN SHALL BE
 LOCATED APPROXIMATELY 5 FT (1524 MM)
 ABOVE THE FLOOR LANDING IN A POSITION
 WHICH IS READILY VISIBLE WHEN THE
 DOOR IS IN THE OPEN OR CLOSED POSITION.
  
 29) SHEET A-1.3 INDICATES A EXIT ONTO
 THE ROOF DOOR 615B/ 615 A, SEE 1006.2.2
 FOR REQUIRED ROOF-OVER BALCONY, PORCH OR
 GALLERY.
  
 30) SHEET A-1.3 DETAIL A-5.2 DETAIL# 4
 INDICATES A USE OF A RAISED WALKABLW
 DECK AND HANDRAIL. PROVIDE DETAILS FOR
 GAURDRAIL, INDICATE COMPLIANCE WITH:
  
 30A)11015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR
 ORNAMENTAL PATTERN SUCH THAT A 4-INCH
 (102 MM) DIAMETER SPHERE CANNOT PASS
 THROUGH ANY OPENING UP TO A HEIGHT OF 34
 INCHES.A BOTTOM RAIL OR CURB
 SHALL BE PROVIDED THAT WILL REJECT THE
 PASSAGE OF 2-INCH (51 MM) DIAMETER
 SPHERE.
  
 30B)1608.2.2.1 GUARDRAIL SYSTEMS SHALL
 BE DESIGNED AND CONSTRUCTED FOR A
 CONCENTRATED LOAD OF 200 LB (890 N)
 APPLIED AT ANY POINT AND IN ANY
 DIRECTION AT THE TOP OF THE GUARDRAIL.
  
 30C)1608.2.2.2 GUARDRAIL SYSTEMS LOCATED
 OTHER THAN WITHIN DWELLING UNITS SHALL
 BE DESIGNED AND CONSTRUCTED FOR A LOAD
 OF 50 PLF (730 N/M) APPLIED HORIZONTALLY
 AT THE REQUIRED GUARDRAIL HEIGHT AND A
 SIMULTANEOUS LOAD OF 100 PLF (1459 N/M)
 APPLIED VERTICALLY DOWNWARD AT THE TOP
 OF THE GUARDRAIL.
  
 30D) 1608.2.2.3 THE GUARDRAIL SYSTEM
 SHALL ALSO BE DESIGNED ANDCONSTRUCTED TO
 RESIST A 200 LB (890 N) CONCENTRATED
 HORIZONTAL LOAD APPLIED ON A 1 SQ FT
 AREA (0.093 M^2) AT ANY POINT IN THE
 SYSTEM INCLUDING INTERMEDIATE RAILS OR
 OTHER ELEMENTS SERVING THIS PURPOSE.
  
 31) SHEET A-1.3 ROOM 621 A MULTI-PURPOSE
 ROOM WITH AN OCC LOAD OF 260 (ASSEMBLY
 OCCUPANCY) REQUIRES A 2HR RATED WALL/
 WITH 1 1/2 HR RATED DOORS, SEE TABLE
 705.1.2.
  
 32A) SHEET A-1.3 CONFERENCE ROOM
 INDICATES A 1 HR RATED WALL, PROVIDE
 INFORMATION ON THE RATING OF WINDOW NEXT
 TO DOOR.TABLE 705.1.2.
  
 32B)THIS SAME WINDOW TO BE SAFETY GLASS,
 HAZARDOUS AREA. FL BLD CODE 2405.2
 HAZARDOUS LOCATION PROVIDE SAFETY GLASS
 FOR THIS LOCATION.
  
 33) SHEET A-4.1 DETAIL 3 INDICATES THE
 USE OF ELEVATED SLABS & CMU. 2111.1.9*
 LOCAL AMENDMENT, WHERE EXTERIOR WALL
 MASONARY UNITS BEAR ON A CONCRETE FLOOR
 SURFACE, A 1.5" RECESS SHALL BE PROVIDED
 TO MINIMIZE WATER INTRUSION INTO
 FINISHED AREAS.
  
 34) SHEET A-5.0 DETAIL# 6, THE CANOPY
 DETAIL INDICATES THE CEILING OF THE
 CANOPY TO BE CONSTRUCTED OF STUCCO ON
 5/8" CEMENT BOARD. PROVIDE ADDITIONAL
 INFORMATION. THE STO PRODUCT APPROVAL
 SUBMITTED UNDER LIMITATIONS 3.1 "THIS
 SYSTEM IS NOT TO BE USED ON HORIZONTAL
 SURFACES.
  
 35) THE PLANS ALSO INDICATE THE USE OF
 EFIS SYSTEMS FOR THE EXTERIOR WALLS,
  
 35A) THE SUBMITTED STO EFIS REPORT
 INDICATES THAT IT WAS TESTED WITH STUDS
 AND PLYWOOD SUBSTRATE, PROVIDE TEESTING
 REPORT FOR THE ASSEMBLY THAT WILL BE
 USED FOR TYPE II BUILDING, SECTION 604
 NONCOMBUSTIBLE EXTERIOR WALLS.
  
 35B) SHOW COMPLIANCE WITH :2603.6
 EXTERIOR WALLS OF BUILDINGS OF ANY
 HEIGHT. EXTERIOR WALLS OF
 BUILDINGS OF TYPES I, II, III, IV AND V0
 CONSTRUCTION OF ANY HEIGHT SHALL
 COMPLY WITH ?2603.6.1 THROUGH ?2603.6.7.
  
 35C)1404.1.1 ARCHITECTURAL TRIM ON
 BUILDINGS OF TYPE I, II AND IV
 CONSTRUCTION NOT MORE THAN THREE STORIES
 OR 40 FT (12.2 M) HIGH MAY BE OF
 TYPE VI CONSTRUCTION, AND MAY BE OF TYPE
 VI CONSTRUCTION ON ALL BUILDINGS
 OF TYPE III, V AND VI CONSTRUCTION.
 TRIM SHALL BE SECURED TO THE WALL
 WITH METAL OR OTHER APPROVED BRACKETS OR
 FASTENERS.WHEN ARCHITECTURAL
 TRIM IS LOCATED ALONG THE TOP OF
 EXTERIOR WALLS, IT SHALL BE COMPLETELY
 BACKED BY THE EXTERIOR WALL AND SHALL
 NOT EXTEND OVER THE TOP OF EXTERIOR
 WALLS.
  
 36) S-7 CODE DESIGN NOTES INDICATE THAT
 THIS 6 STORY STRUCTURE WAAS DESIGNED TO
 ASCE 7-98, EXPOSURE "C". PROVIDE THE
 POSITIVE AND NEGATIVE PRESSURES FOR
 WALLS, INTERIOR AND END ZONES FOR THE
 EFIS APPLICATION,1606.1.1./ CHAPTER 6
 ASCE 7-98.
  
 37) IN READING THE ICC REPORT SUBMITTED
 FOR 5/8" DENS-GLASS GOLD THE REPORT
 STATES (7.4)IT IS PERMITTED WHERE THE
 DESIGN WIND PRESSURES DO NOT EXCEED
 21.7 PSF.
  
 38) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 39) PRODUCT APPROVAL- ROOFING JOHN
 MANVILLE MODIFIED BITUMEN ROOF SYSTEMS,
 THIS REPORT THIS REPORT HAS (8)
 APPLICATIONS SOME INSULATEDAND OTHERS
 NON-INSULATED. DEPENDING ONWHICH REPORT
 USED, THE PRESSURES MAY HAVE LIMITATION
 7 OR 9 NOT ALLOWING INCREASES. HIGHLIGHT
 THE REPORT TO BE USED.!!!!!!
  
 40) CURRIES EXTERIOR DOORS THE
 6'X7'DOORS LOCATED IN END ZONE 5 WILL
 REQUIRE -121PSF, SUBMITTED REPORTS LOW
 PRESSURE OR REPORTS ARE EXPIRED. SEE
 DOORS 130B & 137B.CURRIES 747 16 GA LOW
 PRESSURE REPORT ONLY GOOD FOR -62.
  
 41) RESAM AES AUTO DOORS- LOW PRESSURE
  
 42) PGT HORIZONTAL ROLLER WINDOWHR-810:
 LOW PRESSURES IN ZONE# 5, MISSING FL
 COVERSHEET.
  
 43) MISSING REPORTS FOR WALL LOUVER,
 NO FL COVERSHEET.
  
 44) EXTERIOR GUARDRAILS, MISSING PRODUCT
 APPROVALS & FL COVERSHEET.
  
 45) FIXED WINDOWS, ABOVE AUTOMATIC
 SLIDING DOORS, NO REPORT,OR FL COVER
 SHEET.
  
 46A) HORIZONTAL MULLION OVER FRONT
 HORIZONTAL SLIDING ENTRY DOOR. NO REPORT
 NOR FL COVERSHEET.
  
 46B) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 46C) 1707.4.5.2 MULLIONS SHALL BE
 DESIGN- ED TO TRANSFER THE DESIGN
 PRESSURE LOADS APPLIED BY THE WINDOW OR
 DOOR ASSEMBLIES TO THE ROUGH OPENING
 SUBTRATE.
  
 47) 3003.6.1 VENTS. HOISTWAYS OF ELEVA-
 TORS SERVING MORE THAN 3 FLOORS SHALL BE
 PROVIDED WITH MEANS OF VENTING SMOKE AND
 HOT GASES TO THE OUTER AIR IN CASE OF
 FIRE.
  
 48) 3003.6.3 THE AREA OF THE VENTS SHALL
 BE NOT LESS THAN 3 SQ FT FOR EACH
 ELEVATOR CAR, WHICHEVER IS GREATER.
  
 49) 3003.7.1 ACCESS TO MACHINE ROOMS AND
 MACHINERY SPACES. A PERMANENT, SAFE AND
 CONVENIENT MEANS OF ACCESS TO ELEVA- TOR
 MACHINE ROOMS AND OVERHEAD MACHINERY
 SPACES SHALL BE PROVIDED FOR AUTHORIZED
 PERSONAL. THE MEANS OF ACCESS SHALL NOT
 BE THROUGH RESTROOMS, DRESSING ROOMS,
 OR TENANT ( INCLUDING OWNER-OCCUPIED)
 SPACES.
  
 50) 3003.4.1 IN ALL STRUCTURES THAT ARE
 MORE THAN THREE STORIES HIGH OR IN
 WHICH THE VERTICAL DISTANCE BETWEEN THE
 BOTTOM TERMINAL LANDING AND THE
 TOP TERMINAL LANDING EXCEEDS 25 FEET
 (7.6 M) MUST BE CONSTRUCTED TO
 CONTAIN AT LEAST ONE PASSENGER LEVATOR
 THAT IS OPERATIONAL AND WILL
 ACCOMMODATE AN AMBULANCE STRETCHER 76
 INCHES (1931 MM) LONG AND 24 INCHES
 (610 MM) WIDE IN THE HORIZONTAL
 POSITION.THIS ELEVATOR SHALL BE
 IDENTIFIED.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 22 Status P Date 2009-10-14 Cont ID  
Sent By btrobaug Date 2009-10-14 Time 16:07 Rev Time 0.00
Received By btrobaug Date 2009-10-14 Time 14:52 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 21 Status F Date 2008-05-22 Cont ID  
Sent By dpalmer Date 2008-05-22 Time 11:41 Rev Time 0.00
Received By dpalmer Date 2008-05-22 Time 11:41 Sent To B
Notes
2008-05-22 11:41:20** DENIEDREVIEW**
  
  
  
 1) NOTE: PLEASE KNOW THE LETTER SUBMITTED BY THE
 GENERAC BUSINESS DEVELOPMENT MANAGER IS NOT ACCEPTABLE.
 THE GENERATOR SHALL BE INSTALLED AT A MINIMUM PER THE
 MANUFACTURES SPECS/CUT SHEET WHICH IS ALREADY ON FILE.
 THIS UNIT PER PREVIOUS SPECS STATE A MINIMUM OF 5FT
 AROUND UNIT.
 IN EITHER CASE COMBUSTIBLES WILL ALSO BE NOTED UNDER
 BUILDING/FIRE MARSHAL REVIEW.
 PLEASE SEE NFPA-110 WHICH REQUIRES INSTALLATION PER
 CHAPTER 7. THERE ARE TOO MANY CODE SECTIONS TO LIST.
 PLEASE SEE THE CHAPTER AS NOTED.
 PLEASE SEE THE MINIMUM REQUIREMENTS FOR INSTALLATION
 FOR ELECTRICAL SHALL MEET 110.3, 90.7, 110.26. AS SHOWN
 THIS UNIT WITH INSTALLED WOOD FENCING WITHIN 6 INCHES
 OF GENERATOR DOES NOT MEET ANY KNOWN CODES AND NOT THE
 GENERATOR MANUFACTURES INSTALLATION INSTRUCTIONS FOR
 MINIMUM CLEARANCES.
  
 ** AS THIS IS A LIFE SAFETY/ EMERGENCY GENERATOR, THE
 WALL ENCLOSURE AS INSTALLED AND SHOWN SHALL BE REMOVED
 IMMEDIATELY UNTIL ALL CODE ITEMS ARE RESOLVED. THIS IS
 A FIRE/LIFE SAFETY AND PROPERTY HAZARD.
  
  
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 20 Status F Date 2008-05-04 Cont ID  
Sent By dpalmer Date 2008-05-04 Time 12:59 Rev Time 0.00
Received By dpalmer Date 2008-05-04 Time 12:59 Sent To  
Notes
2008-05-04 12:59:32** DENIED REVISIONS**
  
 ** REVIEW BASED ON NEW PLANS NOW SUBMITTED WHICH WERE
 NOT PREVIOUSLY SUBMITTED SHOWING THE ENCLOSURE.
  
 1) NOTE: PLEASE KNOW THE PLANS NOW SHOW AN ENCLOSURE
 BUILT RIGHT UP NEXT TO THE GENERATOR. PLEASE PROVIDE
 THE MINIMUM CLEARANCES PER THE GENERATOR MANUFACTURE.
 THIS OFFICE IS NOT AWARE OF ANY GENERATOR MANUFACTURE
 WHO ALLOWS ONLY 6 INCHES OF CLEARANCE ON THE SIDES. IN
 FACT THIS MANUFACTURE AS SUBMITTED REQUIRED AS MUCH AS
 5FT ON PREVIOUS PROJECTS/DOCUMENTS SUBMITTED TO THIS
 OFFICE ON PREVIOUS REVIEWS.
 PLEASE ALSO KNOW THAT REMOVABLE PANELS ARE NOT
 ACCEPTABLE AS THESE ARE NOT READILY ACCESSIBLE OR
 ACCESSIBLE AS REQUIRED BY CODE.
 THIS IS A LIFE SAFETY AND FIRE HAZARD AND THIS FENCING
 SHALL BE REMOVED IMMEDIATELY UNTIL SUCH TIME AS MINIMUM
 CODE COMPLIANCE IS DETERMINED.BASED ON INFORMATION TO
 THIS OFFICE THIS IS A CURRENT HAZARD. THIS INFORMATION
 HAS BEEN FORWARDED TO INSPECTION SERVICES AS OF THIS
 REVIEW.
 PLEASE SEE THE LIMITATIONS AS SHOWN ON PLANS WITH ONLY
 6 INCHES ON TWO SIDES AND ONLY 1.5 AND 2FT ON THE OTHER
 IS NOT PERMITTED.
 MUST SUPPLY *MINIMUM* PER CODE AND MANUFACTURE.
 90.7, 110.3, 110.26, 100, 700.12B6, 701.10B5, 702.11
 PLEASE ALSO SEE SECTION 7 OF NFPA-110.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 19 Status F Date 2008-04-24 Cont ID  
Sent By dpalmer Date 2008-04-24 Time 16:05 Rev Time 0.00
Received By dpalmer Date 2008-04-24 Time 16:03 Sent To PC
Notes
2008-04-24 16:05:15** DENIED REVIEW **
  
 1) NOTE: PLEASE SEE NOTES DATED 4/7/08 WHICH REQUESTED
 SUBMISSION OF UPDATED SHEETS FOR OTHER TRADES SUCH AS
 ARCHITECTURAL, SITE ETC.
 STILL NEED UPDATE SLAB DETAILS, ELEVATION, TIE DOWN,
 OVER TURN DETAILS AS REQUIRE DIN FBC AND NFPA-110
 CHAPTER 7.
 PLEASE KNOW ONCE THE OTHER DETAILS AND PLANS ARE
 REVIEWED AND MEET THE REQUIREMENTS OF THE FBC AND OTHER
 ADOPTED CODES ELECTRICAL REVIEW WILL BE OK.
  
 2) NOTE: PLEASE SEE THAT THREE SETS OF THE MANUFACTURES
 SPECS/CUT SHEETS ARE SUBMITTED.
 FBC106.1.2 THIS IS A THRESHOLD PROJECT.
 ONE COMPLETE SET REMAINS ON FILE THE OTHER TWO ARE FOR
 JOB-SITE.
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 18 Status F Date 2008-04-07 Cont ID  
Sent By dpalmer Date 2008-04-07 Time 11:17 Rev Time 0.00
Received By dpalmer Date   Time   Sent To PC
Notes
2008-04-07 11:18:27STILL NEED TO SUBMIT REVISED PLANS FOR GENERATOR WHICH
 IS TO INCLUDE REVISED SITE, ELECTRICAL, MECHANICAL, AND
 ARCHITECTURAL.

Review Stop E ELECTRICAL
Rev No 17 Status P Date 2008-02-07 Cont ID  
Sent By dpalmer Date 2008-02-07 Time 10:18 Rev Time 0.00
Received By dpalmer Date 2008-02-07 Time 10:18 Sent To PC
Notes
2008-02-07 10:19:33GENERATOR ONLY ON ELEC RISER. IS NOT ON OTHER PLANS OR
 SHEETS FOR ANY OTHER TRADE REVIEWS SINCE BEGINING OF
 PROJECT.

Review Stop E ELECTRICAL
Rev No 16 Status P Date 2008-01-22 Cont ID  
Sent By dpalmer Date 2008-01-22 Time 09:11 Rev Time 0.00
Received By dpalmer Date 2008-01-22 Time 09:11 Sent To PC
Notes
2008-01-22 09:14:51REDLINED NEUTRAL SHOWN FOR FIRE PUMP. THIS CONDUCTOR
 MAY NOT BE SMALLER THAN THE GROUNDING ELECTRODE.
 250.24C, 230.42C

Review Stop E ELECTRICAL
Rev No 15 Status P Date 2007-11-28 Cont ID  
Sent By dpalmer Date 2007-11-28 Time 15:33 Rev Time 0.00
Received By dpalmer Date 2007-11-28 Time 15:33 Sent To M
Notes
2007-11-28 15:34:14ENERGY CALCS STAMPED FOR ELEC ONLY.

Review Stop E ELECTRICAL
Rev No 14 Status P Date 2007-11-27 Cont ID  
Sent By dpalmer Date 2007-11-27 Time 11:03 Rev Time 0.00
Received By dpalmer Date 2007-11-27 Time 11:03 Sent To PC
Notes
2007-11-27 11:05:34REDLINED, NEUTRAL CONDUCTOR FOR FIRE PUMP SHALL NOT BE
 SMALLER THAN GROUNDING ELECTRODE CONDUCTOR.
 230.42C, 250.24C.

Review Stop E ELECTRICAL
Rev No 13 Status F Date 2007-10-27 Cont ID  
Sent By dpalmer Date 2007-10-27 Time 10:08 Rev Time 0.00
Received By dpalmer Date 2007-10-27 Time 09:33 Sent To PC
Notes
2007-10-27 10:09:02** DENIED REVISION **
  
 1) NOTE: PLEASE SEE COMMENTS FROM TWO PREVIOUS REVIEWS
 AS THE COMMENTS WITH RESPECT THE ENERGY CALCULATIONS
 HAS NOT YET BEEN ADDRESSED. AS PREVIOUSLY MENTIONED NO
 FURTHER ELECTRICAL REVISIONS WILL BE GRANTED UNTIL THE
 CALCULATIONS HAVE BEEN CORRECTED, SUBMITTED AND ARE
 CODE COMPLIANT FOR BUILDING BEING CONSTRUCTED.
 FBC 2001 CHAPTER 13.
  
 2) NOTE: PLEASE SEE MISSING NEUTRAL CONDUCTOR TO THE
 FIRST MEANS OF DISCONNECT AT THE FIRE PUMP CONTROLLER.
 PLEASE SEE THE PLANS HAVE NOW BEEN REVISED TO INDICATE
 AN INCREASE IN FIRE PUMP FROM 20HP TO 60HP.
 PLEASE PROVIDE NEW LOCK ROTOR OVER CURRENT PROTECTION.
 PLEASE SUBMIT NEW MANUFACTURES SPECS/CUT SHEETS FOR THE
 NEW FIRE PUMP CONTROLLER, AND FIRE PUMP.
 PLEASE SEE THE FIRE SPRINKLER PLANS ON FILE DO NOT
 CORRELATE WITH SIZE AND WILL BE REQUIRED TO BE REVISED
 ALSO.
 PLEASE SEE 250.20, 250.24, ETC FOR GROUNDED NEUTRAL. IS
 THE #2 AS SHOWN ON #27 NOTE FROM FPL THE NEUTRAL? IF SO
 PLEASE COORDINATE THIS WITH NOTE #3.
 OTHER ADDITIONAL INFORMATION AND COORDINATION PER
 104.1.2, OF 2001 FBC AND NEC 695.4, NFPA-20, NEC 110.3,
 90.7 ETC.
  
 3) NOTE: PLEASE SEE UNIT B MISSING BEDROOM #2
 RECEPTACLE PER 210.62, 210.52
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
 PLEASE ADDRESS COMMENT NUMBER #1.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 12 Status F Date 2007-10-05 Cont ID  
Sent By dpalmer Date 2007-10-05 Time 12:28 Rev Time 0.00
Received By dpalmer Date 2007-10-05 Time 12:11 Sent To M
Notes
2007-10-05 12:29:05*** DENIED REVISION ***
  
  
 1) NOTE:PLEASE SUBMIT COMPLETED ENERGY CALCULATIONS
 WHICH COORDINATE ALL LIGHTING ON PLANS AND FIXTURE
 LEGEND. PLEASE SEE THE INPUT DATA REPORT NEEDS ALL
 ITEMS ON PLANS WHICH CONSUME ENERGY AND PROVIDES
 EFFICIENCY TO BE ON THE IDR.
 PLEASE SEE THE LIGHTING FIXTURE WATTAGES AS SHOWN DO
 NOT MATCH WITH THE LIGHTING FIXTURES WATTAGES AS SHOWN
 AND LISTED ON PLANS.
 PLEASE SEE THAT NO EXTERIOR LIGHTING COULD BE FOUND ON
 THE IDR SO NO REVIEW OF THESE COULD BE DONE. CHAPTER
 13, 400.2, 400.3.A, 415.1.AB.1, 415.1.A, TABLE 4-15,
 415.2 ETC.
 PLEASE CLARIFY HOW 13-415.1.ABCD.1.1.4 IS MET?
  
 CALCULATIONS WILL BE ROUTED TO OTHER TRADES.
  
 IF THERE ARE ANY QUESTIONS AS STATED ON PREVIOUS
 REVIEW
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 11 Status F Date 2007-08-27 Cont ID  
Sent By dpalmer Date 2007-08-27 Time 14:37 Rev Time 0.00
Received By dpalmer Date 2007-08-27 Time 14:37 Sent To PC
Notes
2007-08-27 14:37:54 
 SOME SHEETS OK, AND STAMPED.
  
  
  
  
  
 *** DENIED***
  
 SHEETS E16
  
 1) NOTE: PLEASE SEE THE NOTES ON THE ENERGY
 CALCULATIONS AS NO FURTHER REVISIONS WILL BE ACCEPTED
 UNTIL THE COMMENTS ARE CORRECTED FOR THE FBC CHAPTER 13
 REQUIREMENTS.
  
  
 2) NOTE: PLEASE SEE THE REVISED SHEET E-16 AS THERE ARE
 FEEDERS WHICH DO NOT MEET THE MINIMUM SIZE PER THE
 NEC.
 PLEASE SEE 240.4 WHEN A CONDUCTOR SIZE DOES NOT
 COORDINATE WITH THE OVER CURRENT PROTECTION DEVICES, IT
 IS PERMISSIBLE TO GO THE NEXT STANDARD SIZE OVER
 CURRENT PROTECTION PER 240.6, HOWEVER YOU MAY NOT
 EXCEED THAT NEXT STANDARD SIZE.
 PLEASE SEE THE MINIMUM FEEDERS FOR EEP AND P1A
 110.14, 240.4, 310.16
  
 PLEASE REVISE.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2007-08-27 Cont ID  
Sent By dpalmer Date 2007-08-27 Time 14:38 Rev Time 0.00
Received By dpalmer Date 2007-08-27 Time 14:38 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2007-08-27 Cont ID  
Sent By dpalmer Date 2007-08-27 Time 14:38 Rev Time 0.00
Received By dpalmer Date 2007-08-27 Time 14:38 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2007-08-27 Cont ID  
Sent By dpalmer Date 2007-08-27 Time 07:45 Rev Time 0.00
Received By dpalmer Date 2007-08-27 Time 07:44 Sent To PC
Notes
2007-08-27 07:45:15*** DENIED ***
  
 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS
 SUBMITTED ARE DONE UNDER THE 2004 EDITION OF THE FBC
 WITH THE 2006 REVISIONS.
 ** THIS PROJECT IS UNDER THE 2001 FBC. PLEASE SEE
 13-400, 13-400.3, 13-400.3.ABCD,.1, .2, AND.3.
  
 ** NO REVIEW OF CALCULATIONS COULD BE DONE AT THIS
 TIME.
  
 ** PLEASE KNOW THIS WILL HOLD UP AND OR DELAY ANY TCO
 AND CO FOR PROJECT AS THERE COULD BE ITEMS WHICH MAY
 NEED TO BE CHANGED OR ADJUSTED ON SITE.
  
 ** THESE HAVE BEEN NOTED AND ON HOLD AS OF 7/9/07
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2007-08-06 Cont ID  
Sent By dpalmer Date 2007-08-06 Time 12:56 Rev Time 0.00
Received By dpalmer Date 2007-08-06 Time 12:56 Sent To PC
Notes
2007-08-06 13:09:41**HOLD **
  
  
 PLANS UNDER "T" FOR PU, AS THE REVISED ENERGY
 CALCUALTIONS WERE NOT SUBMITTED.
 CALLED CONTRACTOR TWICE AND LEFT MESSAGES. TWO SETS OF
 REVISIONS SUBMITTED ARE UNDER "T" ON HOLD FOR REVIEW.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2007-08-06 Cont ID  
Sent By dpalmer Date 2007-08-06 Time 13:11 Rev Time 0.00
Received By dpalmer Date 2007-07-07 Time 12:19 Sent To PC
Notes
2007-08-06 13:10:52PLANS UNDER T ON HOLD.
 CALLED CONTRACTOR TWICE.
2007-07-07 13:18:442007-07-07 13:18:44
 PLANS PLACED OUTFRONT.
2007-07-07 13:18:05** PLANS ARE ON HOLD UNTIL MONDAY 7/9/07.
 THE PREVIOUS REVIEW REQUESTED REVISED ENERGY
 CALCULATIONS WHICH NEED TO CORRELATE WITH PLANS AS
 LIGHTING WAS REVISED.
 CALLED THE CONTRACTOR AND LEFT MESSAGE TO CALL ASAP. DV
 PALMER.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-06-09 Cont ID  
Sent By dpalmer Date 2007-06-09 Time 17:27 Rev Time 0.00
Received By dpalmer Date 2007-06-09 Time 16:44 Sent To PC
Notes
2007-06-09 17:28:25** UNSAT **
  
 1) NOTE: PLEASE SEE PERMIT 07050818 FOR LV DATA AND
 VOICE HAS BEEN PLACED ON HOLD FOR NO INSPECTIONS AS
 THESE SYSTEMS WERE NOT ON PRIMARY PLANS AND THE
 REVISION HAVE FAILED WITH COMMENTS FOR THESE ITEMS.
  
 2) NOTE: PLEASE SEE THAT NO LOW VOLTAGE PERMIT HAS BEEN
 APPLIED FOR ALL OTHER LOW VOLTAGE SYSTEMS FOR
 CATV/PHONE SYSTEMS WHICH ARE ONE MASTER/PRIME PLANS.
 PLEASE SE FBC ADMIN SECTION 105.1 WHICH REQUIRES
 PERMITS. THE VALUE IS BASED ON THESE SEPARATELY AS THE
 FBC VALUATION TABLES FOR PERMIT DOES NOT INCLUDE LV.
  
 3) NOTE: PLEASE SEE THE VOICE/DATA OUTLETS ARE NO ADDED
 TO PLANS AS *HAND-DRAWN* WHICH IS NOT PERMITTED UNDER
 FS 471.025. NO CHANGES ARE TO BE MADE TO THE ENGINEERS
 PLANS.
 PLEASE KNOW AS THESE ITEMS WERE NOT PART OF THE
 ORIGINAL PLANS, SEPARATE PLANS ARE TO BE SUBMITTED
 WHICH WILL BE PLACED UNDER PERMIT WHICH IS NOTED ABOVE
 BEING PLACED ON HOLD.
  
  
 4) NOTE: PLEASE SEE AS IT APPEARS SOME LIGHTING HAS
 BEEN REVISED, PLEASE SUBMIT REVISED ENERGY CALCULATIONS
 PER FBC CHAPTER 13.
  
 5) NOTE: PLEASE SEE THAT THE PARCEL CONTAINS SEVERAL
 HOLDS FROM THE ASSISTANT BUILDING OFFICIAL, LICENSE
 SUPERVISOR AND ADDRESSING REVIEWER. PLEASE SEE HOLDS
 STATES ADDRESS IS TO BE CHANGED AND NO PERMITS CAN BE
 ISSUED UNTIL THESE ITEMS ARE DONE.
 PLEASE CONTACT THE ADDRESSING REVIEWER AND THE ABOVE
 MENTIONED PERSON FOR NEW ADDRESS AS THE TITLE BLOCKS ON
 PLANS WILL BE REQUIRED TO COORDINATE FOR THESE. PLEASE
 ISSUE ALL NEW REVISED SHEETS FOR ELECTRICAL ONCE THIS
 IS DONE.
  
 6) NOTE: PLEASE SEE REDLINED PLANS WHICH REQUESTED UPON
 ISSUANCE OF PERMIT FOR NOTES FOR SIGNAGE ON STORAGE
 ROOM DOORS AND OTHER REDLINED NOTES. PLEASE SEE THE
 PREVIOUS REVIEW ON 7/15/2006 AND NOTES BELOW WHICH ARE
 FROM REDLINED PLANS AND REVIEW OF THAT DATE.
  
  
 **** NOTES REDLINED ****
  
  
 1) EM BATTERY BACK LT FIXTURE OF SOME
 SORT WILL BE REQUIRED IN THE FIRE PUMP
 RM. LS 101 7.8,7.9, NEC 700.16.
  
  
 2) SIGNAGE REQUIRED AT ALL DOORS FOR ENTRANCE THROUGH
 STORAGE RMS TO ELECTRICAL ROOMS. SIGNAGE SHALL INCLUDE
 WORDING. "CLEAR PATH OF EGRESS TO ALL ELECTRICAL ROOMS
 SHALL BE MAINTAINED AT ALL TIMES" OR WORDS TO THAT
 EFFECT.
 MIN 1" LTRS ON CONTRASTING BACK AND SIGNAGE SHALL BE
 PERMANENTLY AFFIXED.
  
 3) SIGNAGE REQUIRED FOR ALL MAINS AND DISCONNECTING
 MEANS.
 230.2E,700.8,701.9
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-07-15 Cont ID  
Sent By dpalmer Date 2006-07-15 Time 15:47 Rev Time 0.00
Received By dpalmer Date 2006-07-15 Time 13:56 Sent To  
Notes
2006-07-15 00:00:00**** NOTES REDLINED ****
  
  
 1) EM BATTERY BACK LT FIXTURE OF SOME
 SORT WILL BE REQUIRED IN THE FIRE PUMP
 RM. LS 101 7.8,7.9, NEC 700.16.
  
  
 2) SIGNAGE REQUIRED AT ALL DOORS FOR
 ENTRANCE THROUGH STORAGE RMS TO
 ELECTRICAL ROOMS. SIGNAGE SHALL INCLUDE
 WORDING. "CLEAR PATH OF EGRESS TO ALL
 ELECTRICAL ROOMS SHALL BE MAINTAINED AT
 ALL TIMES" OR WORDS TO THAT EFFECT.
 MIN 1" LTRS ON CONTRASTING BACK AND
 SIGNAGE SHALL BE PERMANANTLY AFFIXED.
  
 3) SIGNAGE REQUIRED FOR ALL MAINS AND DISCONNECTING
 MEANS.
 230.2E,700.8,701.9
  
  
 ***********************************
  
 FIRE PUMP SUBMITTIALS STAMPED AND
 INSERTED INTO SPEC BOOKS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-04-18 Cont ID  
Sent By dpalmer Date 2006-04-18 Time 08:33 Rev Time 0.00
Received By dpalmer Date 2006-04-17 Time 16:44 Sent To  
Notes
2006-04-18 00:00:00*** UNSAT ***
  
 1) NOTE: PELASE SUBMIT THE MANUFACTURES
 SPECS/CUT SHEETS FOR FIRE PUMP AND FIRE
 PUMP CONTROLLER. THIS WAS REQUESTED ON
 THE TWO PREVIOUS REVIEWS AND THE
 RESPONSE LTR MENTIONS THESE ARE TO BE
 SUBMITTED, HOWEVER THESE COULD NOT BE
 LOCATED ON PACKAGE.
 THESE ARE NEED TO VERIFY COMPLIANCE FOR
 LOCKED ROTOR SETTING FOR MAX OCP , THE
 MEANS OF DISCONNECT REQUIRED PER NFPA-20
 CHAPTERS 6 AND 7, (1999)7-3.6, 7-4.2 AND
 NFPA-70.695.5, 230.76,230.79
  
 2) NOTE: PLEASE SEE THAT ALL ELECTRICAL
 SHEETS ARE SIGNED, DATED AND SEALED AS
 REQUIRED PER FS 471.025
 PLEASE SEE NEW SHEETS ARE SIGNED, DATED
 AND SEALED AND MANY OF THE OTHER SHEETS
 ARE NOT DATED.
 PLEASE SEE PLANS MUST BE RE-SEALED AS
 THE SEAL AS SHOWN IS NO LONGER
 ACCEPTABLE AS PUBLIC RECORD FOR THE
 FLORIDA BOARD OF PROFESSINAL ENGINEER'S.
 PLEASE SEE FAC 61G15-23.001 WHICH IN FEB
 04 CHANGED TO NOW REQUIRE ALL SEALS TO
 CONTAIN THE WORDING OF "LICENSE" AND
 COULD NO LONGER USE "CERTIFICATE".
 PLEASE KNOW, AN EXTENSION WAS GRANTED TO
 THE DATE OF 12/31/05 TO GIVE ALL
 ENGINEERS 2 YRS TO OBTAIN NEW SEALS. WE
 CAN NO LONGER ACCEPT OLD SEALS.
 PLEASE SEE PREVIOUS SHEETS WERE NOT
 DATED.
  
 ** PLEASE SEE THE FOLLOWING IS A NEW
 COMMENT AND CAN BE SET UP AS A "PROVISO"
 WHICH WOULD REQUIRE REVISIONS BEFORE
 ROUGH OR MAY BE ADDRESSED AT THIS TIME
 SINCE PLANS ARE COMING BACK FOR COMMENTS
 AND COMMENTS FROM OTHER TRADES.
  
 1) NOTE: PLEASE SEE NFPA-101 (2003)
 7.8.1.3 AND 7.9.2.2 WHICH REQUIRES AMIN
 OF 10FT CANDLE (108LUX) IN STAIR TOWERS.
  
 PLEASE ALSO KNOW A MIN OF ONE BATTERY
 BACK UP FIXTURE ON EVERY OTHER LEVEL
 MEETING THE MIN OF 1FT CANDLE UNDER
 EMERGENCY CONDITIONS WILL BE REQUIRED.
 PLEASE PROVIDE PHOTO-METRICS FOR STAIRS
 WALKING SURFACE. PLEASE KNOW, THIS CAN
 BE A TYPICAL DETAIL AS EACH STAIR TOWER
 AND FLOOR LEVEL IS THE SAME.
 PLEASE KNOW, THE BATTERY BACK UP FIXTURE
 ON EVERY OTHER LEVEL AT A MIN IS
 REQUIRED DUE THE POSSIBLE TRIPPING IS
 DISCONNECTING OF A SINGLE MEANS OF OCP
 AND WOULD LEAVE STAIR TOWERS IN TOTAL
 DARKNESS.
 PLEASE SEE THE CORRIDORS ARE ONLY
 REQUIRED TO MEET 1 FT CANDLE UNDER
 NORMAL AND EMERGENCY CONDITIONS.
 A BATTERY BACK UP FIXTURE MEETING THE
 MIN FT CANDLES WILL BE REQUIRED IN THE
 EGRESS PATH.
 ** PLEASE KNOW, THIS WAS NOT IN PREVIOUS
 COMMENTS FROM ELECTRICAL REVIEW, HOWEVER
 THE NEW REQUIREMENTS OF THE 2003 LS101
 WAS ADOPTED BY THE STATE OF FLORIDA ON
 JAN 1ST, 2005.
 ** AS MENTIONED ABOVE THIS CAN BE DONE
 AT THIS TIME OR A "PROVISO" BEFORE FIRST
 ROUGH INSPECTION CAN BE SET UP.
 IF THERE ARE ANY QUESTIONS ON THIS,
 PLEASE CALL.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-04-17 00:00:00REVIEW COMMENCED,
2006-04-13 00:00:00IN ELECTRICAL FOR REVIEW

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-11-14 Cont ID  
Sent By dpalmer Date 2005-11-14 Time 15:57 Rev Time 0.00
Received By dpalmer Date 2005-11-14 Time 10:26 Sent To  
Notes
2005-11-14 00:00:00*** UNSAT ***
  
 PLEASE SEE SOME COMMENTS FROM PREVIOUS
 REVIEW AND SOME NEW COMMENTS DUE TO
 INFORMATION NOW SUBMITTED AND/OR CHANGES
 IN DESIGN.
  
 1)NOTE: PLEASE SEE NO INFORMATION WAS
 SUBMITTED FOR FIRE PUMP WITH FIRE PUMP
 CONTROLLER. PLEASE SEE RISER DIAGRAM
 DOES NOT INCLUDE HP RATING OF PUMP IN
 ORDER TO VERIFY FEEDERS/SEC'S ETC.
 SPECS NOT SPECIFIC TO ANY ONE SIZE.
 PLEASE ALSO SUBMIT SPECS FOR PUMP, THE
 MANUFACTURE CUT SHEETS.
  
 2)NOTE: PLEASE SEE NEC NFPA-70,
 701.11(B)3, WHICH REQUIRES ADDITIONAL
 "ON-SITE" FUEL SOURCE WHEN RELYING ON
 THE UTILITY COMPANY ONLY FOR FUEL.
 PLEASE SUBMIT SPECS/ CUT SHEETS FOR
 "ON-SITE" TANK, LP). PLEASE SEE FIRE
 REVIEW COMMENTS FOR SIZING OF THE TANK
 AND WHETHER OR NOT THE SIZE MAY REQUIRE
 TANK TO BE DIRECTLY BURIED IN THE
 GROUND.
  
 3)NOTE: PLEASE SEE RESPONSE LETTER
 MENTIONS CORRECTIONS MADE TO PLANS FOR
 GFI PROTECTION FOR ALL KITCHEN CIRCUITS
 15AND 20A AND 120V. PER 2002 NEC 210.8B3
 COULD NOT LOCATE THIS.
  
 4)NOTE: PLEASE SEE EEP AND ELP WILL BE
 REQUIRED TO HAVE MCB'S AS SPECS FOR ATS
 SWITCH SUBMITTED FOR BOTH UNITS DOES NOT
 CONTAIN AN MANUAL MEANS OF DISCONNECT
 LOCATED ON THE OUTSIDE OF THE ATS FOR
 DISCONNECTING FEEDERS COMING INTO
 BUILDING FROM GEN.
 225.31,225.34.
 PLEASE ALSO VERIFY IF THE SPECS FOR
 ATS'S SUBMITTED IS FOR BOTH.
 ** PLEASE KNOW, IT IS KNOW THAT SPEC
 BOOKS SUBMITTED DOES CONTAIN A NOTE FOR
 MANUAL MEANS OF DISCONNECT, HOWEVER THE
 MANUFACTURE SPECS/CUT SHEETS DID NOT
 MATHC WITH THIS.
  
 5)NOTEL PLEASE SEE P1B AS THIS IS A 225A
 MLO WITH 300A OCP FEEDING THIS PANEL.
  
 6)NOTE: PLEASE SEE SOME CIRCUITS STILL
 SHOWN AS 30A OCP ON #12 AWG, PLEASE SEE
 MOST WERE CORRECTED ON PREVIOUS REVIEW.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-09 Cont ID  
Sent By dpalmer Date 2005-05-09 Time 06:30 Rev Time 8.00
Received By dpalmer Date 2005-05-04 Time 15:18 Sent To  
Notes
2005-05-09 00:00:00********* UNSAT *********
  
 HAWTHORNE SUITES 6- STORY HOTEL
  
 1)NOTE: PLEASE SEE MISSING LICENSE
 INFORMATIONREQUIRED ON TITLE BLOCKS
 PER FAC 61G1-16.004 FOR ARCHITECT'S AND
 ARCHITECTUAL FIRMS. PLEASE ALSO SEE FAC
 61G15-23.002 FOR ENGINEERS AND
 ENGINEERING FIRMS.
 PLEASE SEE FS 481.219 AND FS 471.023.
  
 2)NOTE: PLEASE SEE LS 101 5-9 FOR
 CIRCUITING OF EM LIGHTING. PLEASE SEE
 STAIRS AND HALL WILL REQUIRE TWO CIRUITS
 FROM EM PANEL OR BATTERY BACK-UP
 FIXTURES WILL BE REQUIRED.
  
 3)NOTE: PLEASE VERIFY EM LTS REQUIRED IN
 ELEVATOR EQUIPMENT RMS AND ELECTRICAL
 RMS. LS 101 5-9
  
 4)NOTE: PLEASE SEE NOTE #28 ON
 ELECTRICAL EQUIPMENT SCHEDULE. PLEASE
 SEE 695.4B1, THE OVERCURRENT PROTECTIVE
 DEVICE(S) SHALL BE SELECTED OR SET TO
 CARRY INDEFINITELY THE SUM OF THE
 LOCKED-ROTOR CURRENT OF THE FIRE PUMP
 MOTOR(S) AND THE PRESSURE MAINTENANCE
 PUMP MOTOR(S) AND THE FULL-LOAD CURRENT
 OF THE ASSOCIATED FIRE PUMP ACCESSORY
 EQUIPMENT WHEN CONNECTED TO THIS POWER
 SUPPLY. PLEASE SEE 300A IS SHOWN FOR
 LOCKED ROTOR EXCEEDING.
 PLEASE ALSO SEE LOCATION OF FIRE PUMP
 DISCONNECT/ SERVICE MEANS SHALL BE
 REMOTE FROM MAIN ELECTRICAL SERVICE.
 PLEASE SEE NEC 2002 695.3 COMMENTARY
 THE POWER SOURCE FOR AN ELECTRIC
 MOTOR-DRIVEN FIRE PUMP MUST BE RELIABLE
 AND HAVE ADEQUATE CAPACITY TO CARRY THE
 LOCKED-ROTOR CURRENTS OF THE FIRE PUMP
 MOTOR AND ACCESSORY EQUIPMENT. THESE TWO
 MAIN REQUIREMENTS ENSURE THAT THE FIRE
 PUMP WILL OPERATE IN THE EVENT OF A FIRE
 WITHOUT BEING ACCIDENTALLY DISCONNECTED
 AND THAT THE FIRE PUMP WILL CONTINUE TO
 OPERATE UNTIL THE FIRE IS EXTINGUISHED,
 THE FIRE PUMP IS PURPOSELY SHUT DOWN, OR
 THE PUMP ITSELF IS DESTROYED.
 PLEASE SEE FOLLOWING COMMENTS FOR
 REQUESTED INFORAMTION INCLUDING FIRE
 PUMP INFORMATION.
 PLEASE SEE FIRE PUMP IS SHOWN HAVING TWO
 FEEDS FROM THE MAIN SWITCH BOARD??
  
 5)NOTE: PLEASE SEE ELECTRICAL PANELS /
 OCP NOT PERMITTED IN STORAGE AREAS AND
 AREAS WITH EASILY IGNITIBLE MATERIALS.
 PLEASE SEE 110.26,408.7 240.24D
 PLEASE SEE THESE AREAS SHALL BE
 DEDICATED TO ELECTRICAL EQUIPMENT.
  
 6)NOTE:PLEASE SEE DISCONNECTING MEANS
 REQUIRED FOR FEEDS FROM GENERATOR TO BE
 LOCATED AT MAIN BLDG/ ELECTRICAL RMS.
 PLEASE SEE 225.31-36.
  
 7)NOTE: PLEASE SEE GENERATOR APPEARS TO
 BE A SEPARATELY DERIVED SYSTEM. PLEASE
 SEE NOTES TO ELECTRICAL RISER DIAGRAM
 APPEARS TO SHOW TRANSFER SWITCH(S) AS
 4-POLE??
 PLEASE SEE 250.30 FOR SYSTEM SEPARATELY
 DERIVED.
 PLEASE SEE ALSO SEE 250.24,250.6 FOR
 GROUNDING/EQUIPMENT GROUNDING.
  
 8)NOTE: PLEASE SEE NOTES TO RISER
 DIAGRAM #15 AND #16 ARE LEFT BLANK?
 HOWEVER, PLEASE SEE THESE #'S ARE USED
 ON RISER.
  
 9)NOTE: PLEASE SEE FIRE PUMP DISC IS
 SHOWN BEING CONNECTED TO MAIN SERVICE
 EQUIPMENT. PLEASE SEE 695.4 THIS IS NOT
 PERMITTED. FIRE PUMP DISCONNECTING MEANS
 SHALL BE DIRECTLY CONNECTED TO UTILITY
 SERVICE. FPL.
  
 10)NOTE: PLEASE VERIFY OF MSB HAS A MCB
 WITH A MANUAL MEANS OF DISCONNECT
 LOCATED ON THE OUTSIDE OF EQUIPMENT.
 PLEASE SEE 230.76,230.79
  
 11)NOTE: PLEASE CORRELATE OCP SHOWN ON
 MSWBD WITH RATINGS OF PANELS. PLEASE SEE
 SOME PANELS ARE SHOWN WITH 400A OCP AND
 PANELS ARE RATED AT 225A'S.
 PLEASE SEE 100A OCP FEEDING PANELS RATED
 AT 400A'S. PLEASE SEE THIS IS OK,
 HOWEVER ITEMS ON PANEL APPEAR TO HAVE
 LOAD EXCEEDING THE 100'S.
 THIS CAN NOT BE VERIFIED AT THIS TIME
 DUE TO LOAD CALCS NOT BEING SHOWN ON
 EACH PANEL.
  
 12)NOTE: PLEASE SEE 250.104 FOR OTHER
 METAL PIPES REQUIRED. (FIRE PUMP) ETC.
  
 13)NOTE: PLEASE PROVIDE LOAD ON EACH
 PANEL SCHEDULE PER NEC 220,215.5
  
 14)NOTE: PLEASE SHOW ALL CONTINUOUS
 LOADS AND LARGEST MOTORS LOADS @ 125%.
 PLEASE SEE LIGHTING ETC. 215.3,230.42
 ETC.
  
 15)NOTE: PLEASE SEE NOE FEEDERS
 SHOWN/NOTED FOR PD1. 215.5,310.16,240.4
  
 16)NOTE: PLEASE SEE NO PANEL SCHEDULE
 WAS PROVIDED FOR PANEL "PP".
 215.5
  
 17)NOTE: PLEASE SEE PANEL H3P IS ALSO
 SHOWN AS HP3?
 PLEASE CORRELATE.
  
 18)NOTE: PLEASE SEE FIRE PUMP IS NOT
 SHOWN BEING FED FROM THE GENERATOR?
 PLEASE SEE TWO MEANS OF POWER SHALL BE
 SUPPLIED FOR BLDG'S EXCEEDING
 75'/HIGH-RISE. IF BLDG DOES NOT EXCEED
 75', A DIRECT CONNECTION TO FPL MAY BE
 ACCEAPTED AS A RELIABLE SOURCE.
  
 19)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL
 SCHEDULES. PLEASE ALSO SEE TYPICAL
 SUITES SHALL REQUIRE THIS ALSO.
  
 20)NOTE: PLEASE SEE NOTE #28 ON
 EQUIPMENT SCHEDULE MENTIONS THAT
 PLUMBING CONTRACTOR IS TO SUPPLY AND
 INSTALL FIRE PUMP, FIRE PUMP
 CONTROLLER/DISCONNECT ETC.
 PLEASE SEE STATE OF FLORIDA ECLB SCOPE
 OF WORK PERMITTED UNDER PLUMB
 CONTRACTORSA LICENSE DOES NOT PERMIT PC,
 TO INSTALL ELECTRICAL EQUIPMENT. PELASE
 ADJUST NOTES.
  
 21)NOTE: PLEASE SEE NUMEROUS PANEL
 SCHEDULES WHICH INDICATE 30A OCP ON #12
 AWG?
 PLEASE SEE 310.16 AND 240.4 FOR MIN
 SIZING REQUIRED.
  
 22)NOTE: PLEASE SEE WIND LOADING IS
 REQUIRED FOR SITE LIGHTING POLES AND
 FIXTURES. THIS IS REQUIRED AT THIS TIME
 IF SHOWN ON PLANS.
 WIND LOADING IS @ 140MPH PER FBC.
  
 23)NOTE: : PLEASE SEE EEP IS BEING FED
 WITH A 100A OCP FROM GEN? HOWEVER THIS
 IS BEING FED WITH 400A OCP FROM MSWBD?
  
 24)NOTE: PLEASE SEE NOTES TO RISER
 DIAGRAM MENTIONS 9-4" CONDUITS TO MAINS,
 HOWEVER CONDUCTORS FOR THESE CONDUITS
 COULD NOT BE LOCATED?
 PLEASE SEE 240.4,310.16
 215.5
  
 25)NOTE: PLEASE PROVIDE ALL MANUFACTURE
 SPEC/CUT SHEETS FOR FIRE PUMP, FIRE PUMP
 CONTROLLER, ATS'S SWITCHES, GENERATOR
 ETC. PLEASE ALSO PROVIDE INFORMATION FOR
 GEN. PRIME MOVER. IF A SUB-BASE FUEL
 TANK, PLEASE PROVIDE MANUFACT SHEETS.
  
 26)NOTE: PLEASE SEE NEC 2002 210.8B3 FOR
 GFI PROTECTION REQUIRED IN KITCHEN/
 SERVING AREAS. PLEASE ALSO SEE EMPLOYEE
 KITCHEN.
  
 27)NOTE: PLEASE SEE POSSIBLE COMMENTS
 FROM OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 28)NOTE: PLEASE SEE DUE TO MISSING
 INFORMATION A COMPLETE REVIEW FOR CODE
 COMPLIANCE CAN NOT BE DONE AT THIS TIME.
 PLEASE BE SURE TO PROVIDE ALL
 INFORMATION AS REQUESTED ABOVE.
  
 ***PLEASE BE SURE TO REMOVE OLD/VOIDED
 SHEETS FROM SETS AND ONLY INSERT NEW
 REVISED SHEETS INTO THREE COMPLETE SETS
 FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
2005-05-06 00:00:00NOTES TO FOLLOW UPON COMPLETION OF
 REVIEW.
 PLANS WILL BE IN THE FAILED STATUS ONCE
 THESE NOTES ARE COMPLETE.
 5/6/05

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2006-10-19 Cont ID  
Sent By rchokshi Date 2006-10-19 Time 09:18 Rev Time 0.00
Received By rchokshi Date 2006-10-19 Time 09:17 Sent To  
Notes
2006-10-19 09:19:41NO COMMENTS 10/19/06

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2005-10-12 Cont ID  
Sent By mamini Date 2005-10-12 Time 10:39 Rev Time 1.00
Received By mamini Date 2005-10-12 Time 10:39 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2005-05-10 Cont ID  
Sent By mamini Date 2005-05-10 Time 10:20 Rev Time 1.00
Received By mamini Date 2005-05-10 Time 10:20 Sent To  
Notes
2005-05-10 00:00:00FAILED:
  
 1. PLEASE SUBMIT THE FINAL CIVIL PLANS
 AS APPROVED BY THE PUBLIC UTILIRIES AND
 ENGINEERING FOR ALL THE CONNECTIONS TO
 THE SERVICES.
 2. PLEASE SUBMIT A COPY OF SITE
 ASSESSMENT STUDY REPORT AND REMEDIAL
 ACTION PLANS IF ANY.
 3. PLEASE NOTE THAT POLLUTION PREVENTION
 PLANS MUST BE INCLUDED IN CIVIL PLANS.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status F Date 2008-06-02 Cont ID  
Sent By mwennerg Date 2008-06-02 Time 15:50 Rev Time 0.00
Received By mwennerg Date 2008-06-02 Time 15:50 Sent To  
Notes
2008-06-02 15:52:56***DENIED***
  
 1) PLEASE SEE MECHANICAL COMMENT #1 REGARDING DISTANCE
 FROM STORAGE TANK TO PROPERTY LINE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status F Date 2008-05-14 Cont ID  
Sent By mawillia Date 2008-05-14 Time 16:16 Rev Time 0.00
Received By mawillia Date 2008-05-14 Time 15:45 Sent To  
Notes
2008-05-14 16:12:14*****PROVISO*****
  
  
 1.THE ACTUAL ADDRESS OF THE PROJECT SITE SHALL BE
 SHOWN IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
 NO ADDRESS SHOWN ON SHEETS MSP1, MSP2, AND E-16;THE
 INCORRECT ADDRESS IS SHOWN ON SHEET SK-6.
  
 2.PLEASE ADDRESS ELECTRICAL PLAN REVIEW COMMENT.
  
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 THE ABOVE COMMENTS HAVE BEEN ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status N Date 2008-04-16 Cont ID  
Sent By mawillia Date 2008-04-16 Time 17:10 Rev Time 0.00
Received By mawillia Date 2008-04-16 Time 16:49 Sent To  
Notes
2008-04-16 17:05:35*****REVIEWED*****
  
  
 REVIEWED SHEETS MSP1 & MSP2, FH-C2, AND PD-C1;THE
 SCOPE OF REVISIONS HAVE NO OR VERY LITTLE BEARING ON
 LIFE SAFETY.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2008-03-26 Cont ID  
Sent By mwennerg Date 2008-03-26 Time 15:31 Rev Time 0.00
Received By mwennerg Date 2008-03-26 Time 15:31 Sent To  
Notes
2008-03-26 15:32:28REVISED SHEETS FA-1- FA-7.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2008-02-22 Cont ID  
Sent By mawillia Date 2008-02-22 Time 15:49 Rev Time 0.00
Received By mawillia Date 2008-02-22 Time 15:30 Sent To  
Notes
2008-02-22 15:49:03*****DENIED*****
  
  
 AS PER BATTALLION CHIEF/FIRE MARSHAL MIKE CARSILLO, THE
 SUBMITTED PLAN SHEETS WILL NOT BE ACCEPTED WITH
 HAND-DRAWN, INK, OR WHITE/BLACK OUTED MARKINGS.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-01-24 Cont ID  
Sent By mwennerg Date 2007-01-24 Time 15:00 Rev Time 0.00
Received By mwennerg Date 2007-01-24 Time 15:00 Sent To M
Notes
2007-01-24 15:06:48***PROVISO***
  
 1) LAUNDRY CHUTE SHOP DRAWINGS SUBMITTED FOR REVIEW OK
 PROVIDED THAT REQUIRED FIRE PROTECTION SYSTEM IS NOT
 ALTERED OR NEGATIVELY IMPACTED REGARDING INTENT OF
 DESIGN.
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 (561) 805-6722 OR 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-11-16 Cont ID  
Sent By mwennerg Date 2005-11-16 Time 09:43 Rev Time 0.00
Received By mwennerg Date 2005-11-16 Time 09:43 Sent To  
Notes
2005-11-16 00:00:00******PROVISO******
  
 THANK YOU FOR YOUR WELL ADDRESSED
 RESPONSES. ALTHOUGH ITEMS #14-20 AND
 #23-24 ARE INFORMATIONAL, AN
 ACKNOWLEDGMENT WOULD BE APPRECIATED.
 PLANS WILL BE STAMPED WHEN RETURNED FOR
 OTHER REVIEW COMMENTS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-05-31 Cont ID  
Sent By mwennerg Date 2005-05-31 Time 10:56 Rev Time 0.00
Received By mwennerg Date 2005-05-31 Time 10:56 Sent To  
Notes
2005-05-31 00:00:00****DENIED****
  
 1) ALL LIFE SAFETY SHALL BE IN
 ACCORDANCE WITH NFPA 101, 2003 EDITION.
  
 2) CHAPTER 26 OF NFPA 101 IS REFERENCED
 IN REGARDS TO OCCUPANT CLASSIFICATION,
 HOWEVER CHAPTER 28 SHOULD BE USED.
  
 3) TACTILE SIGNS ARE REQUIRED AT EXITS.
  
 4) PLEASE CLARIFY THE OCCUPANT LOAD FOR
 THE HAWTHORN ROOM AND EXPLAIN EXITING.
  
 5) WHAT IS THE SEPARATION BETWEEN THE
 ELECTRIC ROOM AND THE HC SUITE ON THE
 FIRST FLOOR?
  
 6) SIGNAGE IS REQUIRED WITHIN THE STAIR
 ENCLOSURES INDICATING THE TOP, BOTTOM,
 FLOOR NUMBER AND ROOF ACCESS.
  
 7) IT APPEARS THAT AN ADDITIONAL EXIT
 SIGN MAY BE REQUIRED AT THE 6TH FLOOR
 CORRIDOR LEADING TO STAIR #1.
  
 8) THE DOOR TO THE FOOD SERVICE ROOM
 WHEN OPEN, APPEARS TO OBSTRUCT THE
 CORRIDOR BY GREATER THAN 1/2 THE WIDTH.
  
 9) THE ELEVATOR LOBBIES ABOVE THE LEVEL
 OF EXIT DISCHARGE, ARE REQUIRED TO BE
 SEPARATED FROM THE REMAINDER OF THE
 BUILDING.
  
 10) WHAT IMPACT WILL THE CARD READERS
 HAVE ON EXITING?
  
 11) AN ADDRESS NUMBER AT LEAST 6" IN
 HEIGHT AND CONTRASTING TO THE
 BACKGROUND, WILL BE REQUIRED ON THE
 BUILDING.
  
 12) PLEASE PROVIDE THE PRESCRIPTIVE
 STRENGTH REQUIREMENTS OF ALL HANDRAILS
 AND GUARDRAILS.
  
 13) PANIC HARDWARE IS REQUIRED ON DOORS
 SERVING AN OCCUPANT LOAD OF MORE THAT
 100 PERSONS.
  
 14) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR THE FIRE SPRINKLER AND
 FIRE ALARM SYSTEMS.
  
 15) NEW FIRE ALARM SYSTEMS SUPERVISING A
 SPRINKLER SYSTEM SHALL BE MONITORED BY
 UL CERTIFIED CENTRAL STATION SERVICE.
  
 16) A CHAIN AND LOCK SHALL BE PROVIDED
 ON THE DOUBLE CHECK DETECTOR ASSEMBLY IN
 ADDITION TO ELECTRONIC SUPERVISION.
  
 17) PLEASE SEE ELECTRICAL COMMENTS IN
 REGARDS TO THE FIRE PUMP REQUIREMENTS.
  
 18) SMOKE DETECTORS WIRED TO THE FIRE
 ALARM SYSTEM ARE REQUIRED IN THE
 CORRIDORS AND OTHER COMMON AREAS. SINGLE
 STATION SMOKE DETECTORS ARE REQUIRED IN
 LIVING UNITS.
  
 19) DUCT SMOKE DETECTORS WHERE PROVIDED,
 ARE TO MEET LOCAL REQUIREMENTS OF
 INITIATING A GENERAL FIRE ALARM, AND NOT
 SUPERVISORY SIGNAL.
  
 20) TEMPORARY STANDPIPES SHALL BE
 PROVIDED WHEN THE BUILDING REACHES 3
 STORIES OR 30' IN HEIGHT.
  
 21) PLEASE ILLUSTRATE IF ELEVATORS ARE
 STRETCHER ACCESSIBLE.
  
 22) A KNOX BOX WILL BE REQUIRED NEAR THE
 FRONT ENTRANCE.
  
 23) LOCKING KNOX BOX CAPS SHALL BE
 PROVIDED FOR THE FIRE DEPARTMENT
 CONNECTION.
  
 24) FIRE DEPARTMENT CONNECTION SHALL BE
 LOCATED NO FURTHER THAN 150' FROM THE
 CLOSEST FIRE HYDRANT.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2951 OR 805-6722
  
  
  
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 10 Status P Date 2008-05-02 Cont ID  
Sent By kstevens Date 2008-05-02 Time 11:13 Rev Time 0.00
Received By kstevens Date 2008-05-02 Time 11:13 Sent To  
Notes
2008-05-02 11:13:57REVISION OK - SHT P-08

Review Stop G GAS REVIEW
Rev No 9 Status P Date 2008-03-26 Cont ID  
Sent By mperson Date 2008-03-26 Time 13:13 Rev Time 0.00
Received By mperson Date 2008-03-26 Time 13:13 Sent To PC
Notes
2008-03-26 13:15:29REVISION SHEET P-08: "OK" NEW GAS RISER W/2 PSI
 DELIVERY PRESSURE AND MP REGULATORS.

Review Stop G GAS REVIEW
Rev No 8 Status F Date 2008-02-22 Cont ID  
Sent By kstevens Date 2008-02-22 Time 14:31 Rev Time 0.00
Received By kstevens Date 2008-02-22 Time 14:31 Sent To  
Notes
2008-02-22 14:32:44REVISIONDENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 ****FROM PREVIOUS REVIEW:
  
 1. SHT P-08 GAS RISER DIAGRAM 2-1/2" REQUIRED FROM THE
 METER AND UP TO THE BRANCH LINE FOR THE GAS DRYERS.
 TABLE 402(8).--POOL/BATH HOUSE GAS RISER DIAGRAM
 DOES NOT REFLECT THE GAS RISER DIAGRAM AT THE METER.
 SHOW ALL CUT LENGTHS FOR THE POOL HEATER GAS LINES FROM
 WHERE IT CONNECTS TO THE MAIN GAS RISER DIAGRAM.--
 INDICATE REGULATOR MODEL NUMBERS FOR THE GAS DRYERS,
 THE HOT WATER BOOSTER, POOL HEATER AND THE RTU'S 1, 2 &
 3.
 ****RESPONSE NOTED, BUT THE RISER DIAGRAM STILL SHOWS
 2" PIPE UP TO THE BRANCH LINE FOR THE GAS DRYERS. THERE
 WAS NO RESPONSE TO THE RISER DIAGRAM FOR THE POOL/BATH
 RISER NOT REFLECTING THE GASE RISER AT THE METER AND
 ALL CUT SECTIONS WERE NOT PROVIDED.--REGULATOR
 MODELS INDICATED FOR RTU'S 1 & 2 ARE NOT APPROVED.
 MAXIMUM 140 MBH FOR THE MODEL 325-3L, BUT 150 MBH
 INDICATED ON THE RISER DIAGRAM.
  
 ****FROM PREVIOUS PLUMBING REVIEW:
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.-- THE
 MANUF. SHEETS FOR THE POOL HEATER SHALL
 BE SUBMITTED.
 ****RESPONSE NOTED, BUT THE DRYER MANUF SHEETS ARE NOT
 APPROVED. THERE IS NO LISTING INDICATED ON THE MANUF.
 SHEETS.NO BTU LOAD INDICATED. COVER SHEET STATES
 "REFER TO PAGE 4 FOR MODEL IDENTIFICATION". PAGE 4 HAS
 NOT BEEN SUBMITTED WITH MANUF. SPECIFICATION SHEETS.
 --NO MANUF. SHEETS FOR RTU UNITS 1 & 2 SUBMITTED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 7 Status F Date 2008-01-17 Cont ID  
Sent By kstevens Date 2008-01-17 Time 12:07 Rev Time 0.00
Received By kstevens Date 2008-01-17 Time 12:07 Sent To  
Notes
2008-01-17 12:08:52DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1. SHT P-08 GAS RISER DIAGRAM 2-1/2" REQUIRED FROM THE
 METER AND UP TO THE BRANCH LINE FOR THE GAS DRYERS.
 TABLE 402(8).--POOL/BATH HOUSE GAS RISER DIAGRAM
 DOES NOT REFLECT THE GAS RISER DIAGRAM AT THE METER.
 SHOW ALL CUT LENGTHS FOR THE POOL HEATER GAS LINES FROM
 WHERE IT CONNECTS TO THE MAIN GAS RISER DIAGRAM.--
 INDICATE REGULATOR MODEL NUMBERS FOR THE GAS DRYERS,
 THE HOT WATER BOOSTER, POOL HEATER AND THE RTU'S 1, 2 &
 3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 6 Status P Date 2007-11-13 Cont ID  
Sent By kstevens Date 2007-11-13 Time 11:37 Rev Time 0.00
Received By kstevens Date 2007-11-13 Time 11:37 Sent To B1
Notes
2007-11-13 11:38:06ENERGY CALCULATIONS FOR THE WATER HEATERS APPROVED.

Review Stop G GAS REVIEW
Rev No 5 Status F Date 2007-10-15 Cont ID  
Sent By kstevens Date 2007-10-15 Time 14:31 Rev Time 0.00
Received By kstevens Date 2007-10-15 Time 14:31 Sent To  
Notes
2007-10-15 14:33:13SEE COMMENTS FROM REVIEW FOR SHT P-08 DATED 10-13-07:
  
  
 DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.--COMPLETE ISOMETRIC NOT SUBMITTED.
 SUBMIT A COMPLETE ISOMETRIC WITH THE PIPING FOR THE
 POOL HOUSE WATER HEATER SHOWN WITH ALL CUT SECTIONS AND
 CORRESPONDING LENGHTS.--INDICATE THE MODEL OF EACH
 REGULATOR ON THE ISOMETRIC.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.--NOT
 INDICATED FOR POOL HOUSE WATER HEATER.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).--POOL HOUSE WATER HEATER NOT INDICATED.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).--TO BE VERIFIED ONCE
 RESPONSE FOR COMMENT IS REVIEWED.
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.--POOL HOUSE WATER
 HEATER MANUF. SHEETS REQUIRED.
  
 6. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR ALL
 REGULATORS. INDICATED MODEL NUMBER USED FOR EACH
 REGULATOR AND INDICATE WHERE EACH REGULATOR MODEL WILL
 BE USED TO VERIFY CAPACITY.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2007-10-13 Cont ID  
Sent By kstevens Date 2007-10-13 Time 10:31 Rev Time 0.00
Received By kstevens Date 2007-10-13 Time 10:31 Sent To  
Notes
2007-10-13 10:43:34DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.--COMPLETE ISOMETRIC NOT SUBMITTED.
 SUBMIT A COMPLETE ISOMETRIC WITH THE PIPING FOR THE
 POOL HOUSE WATER HEATER SHOWN WITH ALL CUT SECTIONS AND
 CORRESPONDING LENGHTS.--INDICATE THE MODEL OF EACH
 REGULATOR ON THE ISOMETRIC.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.--NOT
 INDICATED FOR POOL HOUSE WATER HEATER.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).--POOL HOUSE WATER HEATER NOT INDICATED.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).--TO BE VERIFIED ONCE
 RESPONSE FOR COMMENT IS REVIEWED.
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.--POOL HOUSE WATER
 HEATER MANUF. SHEETS REQUIRED.
  
 6. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR ALL
 REGULATORS. INDICATED MODEL NUMBER USED FOR EACH
 REGULATOR AND INDICATE WHERE EACH REGULATOR MODEL WILL
 BE USED TO VERIFY CAPACITY.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2007-09-05 Cont ID  
Sent By kstevens Date 2007-09-05 Time 12:53 Rev Time 0.00
Received By kstevens Date 2007-09-04 Time 13:24 Sent To  
Notes
2007-09-05 12:54:56REVISION DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1. SHT P-08 GAS RISER ISOMETRIC DIAGRAM. THE GAS
 REGULATORS FOR THE DOMESTIC WATER BOILERS ARE NOT
 APPROVED. THE MAXIMUM INDIVIDUAL LOAD FOR THE MAXITROL
 MODEL 325-51 IS ONLY 250,000 BTU'S. THE RISER DIAGRAM
 INDICATES 400,000 BTU'S FOR EACH BOILER. (SEE ATTACHED
 SHEET). PLEASE SPECIFY THE CORRECT REGULATORS FOR THE
 BOILERS. SECTION 410.2(1). (ALSO CORRECT REGULATOR
 MODEL NUMBER ON DETAIL FOR WATER HEATERS SHEET P-07).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-06-19 Cont ID  
Sent By kstevens Date 2007-06-19 Time 07:55 Rev Time 0.00
Received By kstevens Date 2007-06-19 Time 07:55 Sent To  
Notes
2007-06-19 07:56:13REVISION OK - SHT P-02A--REVISION REQUIRED FOR GAS
 RISER DIAGRAM TO REFLECT THE CHANGES INDICATED ON THE
 FLOOR PLAN.

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2006-08-31 Cont ID  
Sent By kstevens Date 2006-08-31 Time 15:38 Rev Time 0.00
Received By kstevens Date 2006-08-12 Time 18:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 76 Status N Date 2008-05-14 Cont ID  
Sent By adarroug Date 2008-05-14 Time 09:11 Rev Time 0.00
Received By adarroug Date 2008-05-14 Time 09:11 Sent To E
Notes
2008-05-14 09:11:40TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 75 Status N Date 2008-04-29 Cont ID  
Sent By adarroug Date 2008-04-29 Time 11:40 Rev Time 0.00
Received By adarroug Date 2008-04-29 Time 11:40 Sent To  
Notes
2008-04-29 11:42:48TO "COMM" BD#12

Review Stop I INCOMING/PROCESSING
Rev No 74 Status N Date 2008-04-22 Cont ID  
Sent By adarroug Date 2008-04-22 Time 11:50 Rev Time 0.00
Received By adarroug Date 2008-04-22 Time 11:50 Sent To P
Notes
2008-04-22 11:51:09TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 73 Status N Date 2008-04-17 Cont ID  
Sent By adarroug Date 2008-04-17 Time 15:41 Rev Time 0.00
Received By adarroug Date 2008-04-17 Time 15:41 Sent To E
Notes
2008-04-17 15:42:11TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 72 Status N Date 2008-04-04 Cont ID  
Sent By adarroug Date 2008-04-04 Time 16:18 Rev Time 0.00
Received By adarroug Date 2008-04-04 Time 16:18 Sent To Z
Notes
2008-04-04 16:19:29TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 71 Status N Date 2008-04-04 Cont ID  
Sent By adarroug Date 2008-04-04 Time 16:16 Rev Time 0.00
Received By adarroug Date 2008-04-04 Time 16:16 Sent To Z
Notes
2008-04-04 16:17:13TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 70 Status N Date 2008-04-04 Cont ID  
Sent By adarroug Date 2008-04-04 Time 16:12 Rev Time 0.00
Received By adarroug Date 2008-04-04 Time 16:12 Sent To E
Notes
2008-04-04 16:12:19TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 69 Status N Date 2008-03-26 Cont ID  
Sent By adarroug Date 2008-03-26 Time 10:09 Rev Time 0.00
Received By adarroug Date 2008-03-26 Time 10:09 Sent To  
Notes
2008-03-26 10:12:28TO "COMM" BD#14

Review Stop I INCOMING/PROCESSING
Rev No 68 Status N Date 2008-03-26 Cont ID  
Sent By adarroug Date 2008-03-26 Time 10:00 Rev Time 0.00
Received By adarroug Date 2008-03-26 Time 10:00 Sent To Z
Notes
2008-03-26 10:00:41TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 67 Status N Date 2008-03-25 Cont ID  
Sent By adarroug Date 2008-03-25 Time 08:41 Rev Time 0.00
Received By adarroug Date 2008-03-25 Time 08:41 Sent To G
Notes
2008-03-25 08:43:09TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 66 Status N Date 2008-03-07 Cont ID  
Sent By adarroug Date 2008-03-07 Time 10:51 Rev Time 0.00
Received By adarroug Date 2008-03-07 Time 10:51 Sent To FIRE
Notes
2008-03-07 10:51:49TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 65 Status N Date 2008-03-07 Cont ID  
Sent By adarroug Date 2008-03-07 Time 10:45 Rev Time 0.00
Received By adarroug Date 2008-03-07 Time 10:45 Sent To M
Notes
2008-03-07 10:46:14TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 64 Status N Date 2008-02-01 Cont ID  
Sent By adarroug Date 2008-02-01 Time 14:44 Rev Time 0.00
Received By adarroug Date 2008-02-01 Time 14:44 Sent To P
Notes
2008-02-01 14:44:41TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 63 Status N Date 2008-01-28 Cont ID  
Sent By adarroug Date 2008-01-28 Time 09:26 Rev Time 0.00
Received By adarroug Date 2008-01-28 Time 09:24 Sent To  
Notes
2008-01-28 09:25:58TO "F" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 62 Status N Date 2007-12-26 Cont ID  
Sent By mmiller Date 2007-12-26 Time 09:58 Rev Time 0.00
Received By mmiller Date 2007-12-26 Time 09:58 Sent To P
Notes
2007-12-26 09:58:29SENT TO KEN STEVEN'S DESK MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 61 Status N Date 2007-11-19 Cont ID  
Sent By adarroug Date 2007-11-19 Time 09:44 Rev Time 0.00
Received By adarroug Date 2007-11-19 Time 09:44 Sent To E
Notes
2007-11-19 09:45:56TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 60 Status N Date 2007-11-16 Cont ID  
Sent By adarroug Date 2007-11-16 Time 14:53 Rev Time 0.00
Received By adarroug Date 2007-11-16 Time 14:53 Sent To B
Notes
2007-11-16 14:53:55TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 59 Status N Date 2007-11-07 Cont ID  
Sent By adarroug Date 2007-11-07 Time 11:29 Rev Time 0.00
Received By adarroug Date 2007-11-07 Time 11:29 Sent To B
Notes
2007-11-07 11:29:48TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 58 Status N Date 2007-10-24 Cont ID  
Sent By adarroug Date 2007-10-24 Time 10:54 Rev Time 0.00
Received By adarroug Date 2007-10-24 Time 10:54 Sent To E
Notes
2007-10-24 10:54:34TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 57 Status N Date 2007-10-17 Cont ID  
Sent By adarroug Date 2007-10-17 Time 10:49 Rev Time 0.00
Received By adarroug Date 2007-10-17 Time 10:49 Sent To  
Notes
2007-11-05 10:11:23TO "COMM" BD#13
2007-10-17 10:51:23WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 56 Status N Date 2007-09-25 Cont ID  
Sent By adarroug Date 2007-09-25 Time 09:50 Rev Time 0.00
Received By adarroug Date 2007-09-25 Time 09:50 Sent To E
Notes
2007-09-25 09:50:48TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 55 Status N Date 2007-09-25 Cont ID  
Sent By adarroug Date 2007-09-25 Time 09:31 Rev Time 0.00
Received By adarroug Date 2007-09-25 Time 09:31 Sent To B
Notes
2007-09-25 09:31:57TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 54 Status N Date 2007-09-25 Cont ID  
Sent By adarroug Date 2007-09-25 Time 09:27 Rev Time 0.00
Received By adarroug Date 2007-09-25 Time 09:27 Sent To M
Notes
2007-09-25 09:27:47TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 53 Status N Date 2007-09-13 Cont ID  
Sent By adarroug Date 2007-09-13 Time 10:54 Rev Time 0.00
Received By adarroug Date 2007-09-13 Time 10:54 Sent To B
Notes
2007-09-13 10:54:33TO "JWITMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 52 Status N Date 2007-09-10 Cont ID  
Sent By adarroug Date 2007-09-10 Time 10:42 Rev Time 0.00
Received By adarroug Date 2007-09-10 Time 10:42 Sent To B
Notes
2007-09-10 10:43:31WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 51 Status N Date 2007-08-28 Cont ID  
Sent By adarroug Date 2007-08-28 Time 16:11 Rev Time 0.00
Received By adarroug Date 2007-08-28 Time 16:11 Sent To P
Notes
2007-08-28 16:12:13TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 50 Status N Date 2007-08-21 Cont ID  
Sent By adarroug Date 2007-08-21 Time 09:53 Rev Time 0.00
Received By adarroug Date 2007-08-21 Time 09:53 Sent To E
Notes
2007-08-21 09:53:24TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 49 Status N Date 2007-08-21 Cont ID  
Sent By adarroug Date 2007-08-21 Time 09:40 Rev Time 0.00
Received By adarroug Date 2007-08-21 Time 09:40 Sent To E
Notes
2007-08-21 09:40:56TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 48 Status N Date 2007-08-21 Cont ID  
Sent By adarroug Date 2007-08-21 Time 09:38 Rev Time 0.00
Received By adarroug Date 2007-08-21 Time 09:38 Sent To B
Notes
2007-08-21 09:38:33TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 47 Status N Date 2007-08-16 Cont ID  
Sent By adarroug Date 2007-08-16 Time 08:25 Rev Time 0.00
Received By adarroug Date 2007-08-16 Time 08:25 Sent To E
Notes
2007-08-16 08:26:02TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 46 Status N Date 2007-08-16 Cont ID  
Sent By adarroug Date 2007-08-16 Time 08:19 Rev Time 0.00
Received By adarroug Date 2007-08-16 Time 08:19 Sent To B
Notes
2007-08-16 08:20:12TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 45 Status N Date 2007-08-16 Cont ID  
Sent By adarroug Date 2007-08-16 Time 08:15 Rev Time 0.00
Received By adarroug Date 2007-08-16 Time 08:15 Sent To M
Notes
2007-08-16 08:15:30TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 44 Status N Date 2007-07-27 Cont ID  
Sent By adarroug Date 2007-07-27 Time 16:08 Rev Time 0.00
Received By adarroug Date 2007-07-27 Time 16:08 Sent To B
Notes
2007-07-27 16:08:32TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 43 Status N Date 2007-07-24 Cont ID  
Sent By adarroug Date 2007-07-24 Time 14:01 Rev Time 0.00
Received By adarroug Date 2007-07-24 Time 14:01 Sent To M
Notes
2007-07-24 14:02:04TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 42 Status N Date 2007-07-18 Cont ID  
Sent By adarroug Date 2007-07-18 Time 16:51 Rev Time 0.00
Received By adarroug Date 2007-07-18 Time 16:51 Sent To E
Notes
2007-07-18 16:51:32TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 41 Status N Date 2007-07-18 Cont ID  
Sent By adarroug Date 2007-07-18 Time 16:49 Rev Time 0.00
Received By adarroug Date 2007-07-18 Time 16:49 Sent To B
Notes
2007-07-18 16:49:48TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 40 Status N Date 2007-07-18 Cont ID  
Sent By adarroug Date 2007-07-18 Time 16:45 Rev Time 0.00
Received By adarroug Date 2007-07-18 Time 16:45 Sent To P
Notes
2007-07-18 16:46:13TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 39 Status N Date 2007-07-06 Cont ID  
Sent By adarroug Date 2007-07-06 Time 10:51 Rev Time 0.00
Received By adarroug Date 2007-07-06 Time 10:51 Sent To E
Notes
2007-07-06 10:52:06TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 38 Status N Date 2007-07-05 Cont ID  
Sent By adarroug Date 2007-07-05 Time 09:04 Rev Time 0.00
Received By adarroug Date 2007-07-05 Time 09:04 Sent To E
Notes
2007-07-05 09:04:34TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 37 Status N Date 2007-06-29 Cont ID  
Sent By adarroug Date 2007-06-29 Time 16:50 Rev Time 0.00
Received By adarroug Date 2007-06-29 Time 16:50 Sent To M
Notes
2007-06-29 16:50:49TO"M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 36 Status N Date 2007-06-29 Cont ID  
Sent By adarroug Date 2007-06-29 Time 16:35 Rev Time 0.00
Received By adarroug Date 2007-06-29 Time 16:35 Sent To B
Notes
2007-06-29 16:35:49TO "JWITMER' DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 35 Status N Date 2007-06-22 Cont ID  
Sent By adarroug Date 2007-06-22 Time 16:18 Rev Time 0.00
Received By adarroug Date 2007-06-22 Time 16:18 Sent To B
Notes
2007-06-22 16:18:59TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 34 Status N Date 2007-06-20 Cont ID  
Sent By adarroug Date 2007-06-20 Time 14:32 Rev Time 0.00
Received By adarroug Date 2007-06-20 Time 14:32 Sent To B
Notes
2007-06-20 14:33:01TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 33 Status N Date 2007-06-20 Cont ID  
Sent By adarroug Date 2007-06-20 Time 14:29 Rev Time 0.00
Received By adarroug Date 2007-06-20 Time 14:29 Sent To B
Notes
2007-06-20 14:29:28TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 32 Status N Date 2007-06-20 Cont ID  
Sent By adarroug Date 2007-06-20 Time 14:28 Rev Time 0.00
Received By adarroug Date 2007-06-20 Time 14:28 Sent To B
Notes
2007-06-20 14:28:52TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 31 Status N Date 2007-06-20 Cont ID  
Sent By adarroug Date 2007-06-20 Time 14:28 Rev Time 0.00
Received By adarroug Date 2007-06-20 Time 14:28 Sent To B
Notes
2007-06-20 14:28:10TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 30 Status N Date 2007-06-20 Cont ID  
Sent By adarroug Date 2007-06-20 Time 14:27 Rev Time 0.00
Received By adarroug Date 2007-06-20 Time 14:27 Sent To B
Notes
2007-06-20 14:27:39TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 29 Status N Date 2007-06-20 Cont ID  
Sent By adarroug Date 2007-06-20 Time 14:26 Rev Time 0.00
Received By adarroug Date 2007-06-20 Time 14:26 Sent To B
Notes
2007-06-20 14:26:55TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 28 Status N Date 2007-06-13 Cont ID  
Sent By adarroug Date 2007-06-13 Time 14:26 Rev Time 0.00
Received By adarroug Date 2007-06-13 Time 14:26 Sent To B
Notes
2007-06-13 14:27:04TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 27 Status N Date 2007-06-13 Cont ID  
Sent By adarroug Date 2007-06-13 Time 14:25 Rev Time 0.00
Received By adarroug Date 2007-06-13 Time 14:25 Sent To B
Notes
2007-06-13 14:25:57TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 26 Status N Date 2007-05-23 Cont ID  
Sent By adarroug Date 2007-05-23 Time 08:55 Rev Time 0.00
Received By adarroug Date 2007-05-23 Time 08:55 Sent To E
Notes
2007-05-23 08:55:37TO "E" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 25 Status N Date 2007-05-23 Cont ID  
Sent By adarroug Date 2007-05-23 Time 08:53 Rev Time 0.00
Received By adarroug Date 2007-05-23 Time 08:53 Sent To P
Notes
2007-05-23 08:54:07TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2007-05-22 Cont ID  
Sent By adarroug Date 2007-05-22 Time 16:41 Rev Time 0.00
Received By adarroug Date 2007-05-22 Time 16:41 Sent To M
Notes
2007-05-22 16:41:27TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date 2007-05-16 Cont ID  
Sent By adarroug Date 2007-05-16 Time 09:58 Rev Time 0.00
Received By adarroug Date 2007-05-16 Time 09:58 Sent To I
Notes
2007-05-16 09:59:16TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2007-05-02 Cont ID  
Sent By adarroug Date 2007-05-02 Time 09:32 Rev Time 0.00
Received By adarroug Date 2007-05-02 Time 09:32 Sent To B
Notes
2007-05-02 09:32:56TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2007-05-02 Cont ID  
Sent By adarroug Date 2007-05-02 Time 08:54 Rev Time 0.00
Received By adarroug Date 2007-05-02 Time 08:54 Sent To B
Notes
2007-05-02 08:54:58TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2007-04-13 Cont ID  
Sent By adarroug Date 2007-04-13 Time 14:53 Rev Time 0.00
Received By adarroug Date 2007-04-13 Time 14:53 Sent To B
Notes
2007-04-13 14:54:01TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2007-04-12 Cont ID  
Sent By adarroug Date 2007-04-12 Time 09:42 Rev Time 0.00
Received By adarroug Date 2007-04-12 Time 09:42 Sent To B
Notes
2007-04-12 09:42:39TO "JWITMER' DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2007-03-14 Cont ID  
Sent By adarroug Date 2007-03-14 Time 11:22 Rev Time 0.00
Received By adarroug Date 2007-03-14 Time 11:22 Sent To B
Notes
2007-03-14 11:23:18TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2007-03-08 Cont ID  
Sent By adarroug Date 2007-03-08 Time 15:58 Rev Time 0.00
Received By adarroug Date 2007-03-08 Time 15:58 Sent To B
Notes
2007-03-08 15:59:12TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2007-03-08 Cont ID  
Sent By adarroug Date 2007-03-08 Time 11:10 Rev Time 0.00
Received By adarroug Date 2007-03-08 Time 11:10 Sent To B
Notes
2007-03-08 11:13:22TO "JWITMER" DESK/3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2007-02-21 Cont ID  
Sent By adarroug Date 2007-02-21 Time 08:40 Rev Time 0.00
Received By adarroug Date 2007-02-21 Time 08:40 Sent To B
Notes
2007-02-21 08:40:22TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2007-02-15 Cont ID  
Sent By adarroug Date 2007-02-15 Time 13:24 Rev Time 0.00
Received By adarroug Date 2007-02-15 Time 13:24 Sent To B
Notes
2007-02-15 13:24:45TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2007-01-22 Cont ID  
Sent By adarroug Date 2007-01-22 Time 09:34 Rev Time 0.00
Received By adarroug Date 2007-01-22 Time 09:34 Sent To B
Notes
2007-01-22 09:34:43TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2007-01-10 Cont ID  
Sent By adarroug Date 2007-01-10 Time 09:18 Rev Time 0.00
Received By adarroug Date 2007-01-10 Time 09:18 Sent To FIRE
Notes
2007-01-10 09:18:36TO "F" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-12-26 Cont ID  
Sent By adarroug Date 2006-12-26 Time 09:14 Rev Time 0.00
Received By adarroug Date 2006-12-26 Time 09:13 Sent To B
Notes
2006-12-26 09:14:28TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 10 Status   Date 2006-11-29 Cont ID  
Sent By mmiller Date 2006-11-29 Time 18:59 Rev Time 0.00
Received By mmiller Date 2006-11-29 Time 18:59 Sent To B
Notes
2006-11-29 18:59:30SENT TO JIM WITMER'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 9 Status   Date 2006-11-29 Cont ID  
Sent By mmiller Date 2006-11-29 Time 19:00 Rev Time 0.00
Received By mmiller Date 2006-11-29 Time 19:00 Sent To B
Notes
2006-11-29 18:57:45SENT TO JIM WITMER'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-11-04 Cont ID  
Sent By adarroug Date 2006-11-04 Time 16:10 Rev Time 0.00
Received By adarroug Date 2006-11-04 Time 16:10 Sent To B
Notes
2006-11-04 16:10:58TO "JWITMER" DESK/ 2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-10-19 Cont ID  
Sent By adarroug Date 2006-10-19 Time 10:17 Rev Time 0.00
Received By adarroug Date 2006-10-19 Time 10:17 Sent To B
Notes
2006-10-19 10:18:09TO "JWITMER" DESK/ 2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-10-14 Cont ID  
Sent By adarroug Date 2006-10-14 Time 16:36 Rev Time 0.00
Received By adarroug Date 2006-10-14 Time 16:36 Sent To B
Notes
2006-10-14 16:36:34TO "JWITMER" DESK/3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-10-11 Cont ID  
Sent By adarroug Date 2006-10-11 Time 09:12 Rev Time 0.00
Received By adarroug Date 2006-10-11 Time 09:12 Sent To ENG
Notes
2006-10-11 09:13:27TO "ENG" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-14 Cont ID  
Sent By adarroug Date 2006-07-14 Time 17:00 Rev Time 0.00
Received By adarroug Date 2006-07-14 Time 17:00 Sent To  
Notes
2006-07-14 00:00:00TO "COMM" BD#30/PLANS ON RACK/4 ROLLS
 AND BINDERS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-03-14 Cont ID  
Sent By adarroug Date 2006-03-09 Time 09:25 Rev Time 0.00
Received By adarroug Date 2006-03-09 Time 09:25 Sent To  
Notes
2006-04-06 00:00:00TO "COMM" BD#43
2006-03-14 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-30 Cont ID  
Sent By adarroug Date 2005-09-30 Time 09:00 Rev Time 0.00
Received By adarroug Date 2005-09-30 Time 09:00 Sent To  
Notes
2005-10-06 00:00:00TO "COMM" BD#18/PLANS ON RACK 4 ROLLS
 AND BINDERS
2005-09-30 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-16 Cont ID  
Sent By pkrauss Date 2005-06-16 Time 16:40 Rev Time 0.00
Received By pkrauss Date 2005-05-02 Time 16:58 Sent To  
Notes
2005-05-02 00:00:00TO "COMM" BD#13/PLANS ON RACK, 3 ROLLS

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2008-04-08 Cont ID  
Sent By lfranco Date 2008-04-08 Time 17:19 Rev Time 0.00
Received By RKUSSNER Date 2008-04-08 Time 17:19 Sent To  
Notes
2008-04-08 17:20:26LANDSCAPING: **** PASSED WITH PROVISO ***
  
 SEE ZONING NOTES:CONTACT ROBERT KUSSNER FOR
 LANDSCAPING COMMENTS.
  
  
 ROBERT KUSSNER
 LANDSCAPE PLANNER
 TEL (561) 822-1462
  
 PLANNING AND ZONING: **** PASSED WITH THE PROVISO THAT
 THE MINOR AMENDMENT NOTED ON COMM. #2 IS APPROVED BY
 THE PLANNING AND ZONING DEPT. PRIOR TO FINAL
 CERTIFICATE OF OCCUPANCY ("CO").****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. THIS PERMIT IS PART OF AN APPLICATION UNDER REVIEW
 FOR A MINOR AMENDMENT (PB1402F) TO THE COURTNEY LAKES
 RESIDENTIAL PLANNED DEVELOPMENT (RPD), HAWTHORN SUITES
 HOTEL.SIGN-OFF FROM THE PLANNING AND ZONING DEPT. FOR
 THE FINAL CO. IS CONTINGENT UPON THE APPROVAL OF THE
 MINOR AMENDMENT.THE DRAWINGS SHALL REFLECT ALL
 REVISIONS PERTAINING TO LANDSCAPING, RE-LOCATION OF THE
 COMPACT SPACES, SCREENING OF THE GENERATOR AND
 MECHANICAL EQUIPMENT ON ROOF-TOP, INCLUDING DETAILS.
 PROVIDE ALL SHEETS INCLUDING, BUT NOT LIMITED TO MSP 1
 AND 2, PD/SHEET C1, FH/SHEET C2 AND LANDSCAPING SHEETS
 (LA-1 AND LA-2) THAT ARE PART OF PERMIT NUMBER.
 05041760 - "RE-SUBMITTAL TO GO WITH ENGINEERING
 DRAWINGS" (RECEIVED ON APRIL 4, 2008) UNDER COMMENTS
 COVER FORM (THE WEITZ CO.).
 *** NOTE: ADDRESS ALL LANDSCAPING COMMENTS FROM ROBERT
 KUSSNER.
  
 3.THE BOLLARD(S) NEED TO BE RELOCATED/RECONFIGURED
 OUT OF THE PARKING SPACE LOCATED NEXT TO THE LARGE
 GENERATOR.
  
 4.LANDSCAPING PLANS - LABEL COMPACT SPACES ON
 LANDSCAPE PLANS AS NOTED ON SITE PLANS (SHEETS MSP1 AND
 MSP2).
  
 5.SHEET MSP2 OF 2 - LOCATION OF HANDICAP SYMBOL'S
 LOWER-END SHALL BE TWO (2) FEET FROM THE PARKING STRIPE
 DETAIL INSTEAD OF FOUR (4) FEET SIX (6) INCHES.
  
 6.PROVIDE AN ENLARGED DETAIL OF THE HOTEL SITE PLAN
 AREA FOR THE DIMENSIONS, ETC. TO BE LEGIBLE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE
 NUMBER BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
  
 TEL: (561) 822-1443
 EMAIL: [email protected]

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2008-03-27 Cont ID  
Sent By rkussner Date 2008-03-27 Time 15:50 Rev Time 0.00
Received By rkussner Date 2008-03-27 Time 16:15 Sent To  
Notes
2008-03-27 16:02:31MUST PROCESS THE MINOR AMENDMENT WHICH WILL INCLUDE ALL
 CHANGES TO SITE AND LANDSCAPE PLANS PRIOR TO APPROVAL
 OF PERMIT.
 REFER TO PREVIOUS INSPECTION COMMENTS.

Review Stop M MECHANICAL (A/C)
Rev No 15 Status P Date 2008-07-16 Cont ID  
Sent By tgordon Date 2008-07-16 Time 10:36 Rev Time 0.20
Received By tgordon Date 2008-07-16 Time 10:36 Sent To  
Notes
2008-07-16 10:38:25RECIVED SUBMITTAL SHOWING GENERATOR FUEL TANK 10.9 FEET
 FROM PROPERTY LINE.

Review Stop M MECHANICAL (A/C)
Rev No 14 Status F Date 2008-06-02 Cont ID  
Sent By tgordon Date 2008-06-02 Time 14:25 Rev Time 0.45
Received By tgordon Date 2008-06-02 Time 14:25 Sent To FIRE
Notes
2008-06-02 15:03:29PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) IT HAS BEEN BROUGHT TO MY ATTENTION THAT THE FUEL
 STORAGE TANK FOR THE GENERATOR IS 550 GAL. DIESEL FUEL.
 PER NFPA 30 TABLE 4.3.2.1.1 (B), THE STORAGE TANK MUST
 BE 10 FEET FROM THE PROPERTY LINE. PLEASE SUBMIT
 DOCUMENTATION SHOWING THE DISTANCE BETWEEN THE FUEL
 STORAGE TANK AND THE PROPERTY LINE.
  
 2) PLEASE SUBMIT DOCUMENTATION STATING THE SIZE OF THE
 GENERATOR'S FUEL STORAGE TANK AND TYPE OF FUEL. PER
 2004 FBC 106.3, 106.4, AND 106.5.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 13 Status P Date 2008-03-20 Cont ID  
Sent By hmoser Date 2008-03-20 Time 19:25 Rev Time 0.00
Received By hmoser Date 2008-03-20 Time 19:25 Sent To  
Notes
2008-03-20 19:27:02TEST & BALANCE REPORT

Review Stop M MECHANICAL (A/C)
Rev No 12 Status P Date 2007-11-28 Cont ID  
Sent By rregueir Date 2007-11-28 Time 17:54 Rev Time 0.00
Received By rregueir Date 2007-11-28 Time 17:53 Sent To B
Notes
2007-11-28 17:54:11REVISED ENERGY CALCULATIONS DATED 11/13/07 MECH OK

Review Stop M MECHANICAL (A/C)
Rev No 11 Status P Date 2007-11-05 Cont ID  
Sent By tgordon Date 2007-11-05 Time 14:23 Rev Time 0.45
Received By tgordon Date 2007-11-05 Time 14:23 Sent To P
Notes
2007-11-05 14:25:09SUBMITTED ENERGY CALCULATIONS FORM 400A-2001 (2001 FBC)

Review Stop M MECHANICAL (A/C)
Rev No 10 Status F Date 2007-09-26 Cont ID  
Sent By tgordon Date 2007-09-26 Time 10:29 Rev Time 2.00
Received By tgordon Date 2007-09-26 Time 10:29 Sent To  
Notes
2007-09-26 11:05:10PLAN REVIEW UNDER THE 2001 FLORIDA BUILDING CODE &
 REFERENCED CODES, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 *** DENIED ***
 THE FOLLOWING COMMENTS MAY HAVE BEEN PROVISO-ED IN
 PREVIOUS REVIEWS BUT REVISED MECHANICAL PLANS STILL DO
 NOT SHOW COMPLIANCE WITH 2001 FBC/M 607.1.2 OR
 EXCEPTIONS 607.1.3.
  
 1) REVISED MECHANICAL PLAN PAGE M-03 SHOWS A 22" X 10"
 SUPPLY AIR DUCT PENETRATING TWO 1 HOUR FIRE RATED WALLS
 TO THE ELECTRICAL ROOM #120, THE DUCTS WILL NEED FIRE
 DAMPERS, SEE 2001 FBC/M 607.1.2.
  
 2) REVISED MECHANICAL PLAN PAGE M-04 SHOWS A 12" X 8"
 SUPPLY AIR DUCT PENETRATING A ONE HOUR FIRE RATED WALL
 FROM STORAGE ROOM #228 TO CORRIDOR #223, AND A 8" X 6"
 DUCT FROM STORAGE ROOM #213 TO CORRIDOR #223, THE DUCTS
 WILL NEED A FIRE DAMPERS, SEE 2001 FBC/M 607.1.2.
  
 3) REVISED MECHANICAL PLAN PAGE M-05 SHOWS A 12" X 15"
 SUPPLY AIR DUCT PENETRATING A ONE HOUR FIRE RATED WALL
 FROM STORAGE ROOM #623 TO MULTIPURPOSE ROOM #621, THE
 DUCT WILL NEED A FIRE DAMPER, SEE 2001 FBC/M 607.1.2.
  
 4) REVISED MECHANICAL PLAN PAGE M-02 PASSED REVIEW AND
 WAS STAMPED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2007-08-17 Cont ID  
Sent By tgordon Date 2007-08-17 Time 08:23 Rev Time 0.30
Received By tgordon Date 2007-08-17 Time 08:23 Sent To  
Notes
2007-08-17 08:23:48MECH. REVISION PAGE M-04.

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2007-07-25 Cont ID  
Sent By tgordon Date 2007-07-25 Time 10:39 Rev Time 0.45
Received By tgordon Date 2007-07-25 Time 10:39 Sent To  
Notes
2007-07-25 10:46:34** MECHANICAL REVISION TO PLANS PAGES M-03, M-04, AND
 M-05.
 *** PROVISO ***
 1) 2001 FBC/M 504.7 COMMERCIAL CLOTHES DRYERS.
 THE INSTALLATION OF DRYER EXHAUST DUCTS SERVING TYPE 2
 CLOTHES DRYERS SHALL COMPLY WITH THE APPLIANCE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS. EXHAUST FAN
 MOTORS INSTALLED IN EXHAUST SYSTEMS SHALL BE LOCATED
 OUTSIDE OF THE AIRSTREAM. IN MULTIPLE INSTALLATIONS,
 THE FAN SHALL OPERATE CONTINUOUSLY OR BE INTERLOCKED TO
 OPERATE WHEN ANY INDIVIDUAL UNIT IS OPERATING. DUCTS
 SHALL HAVE A MINIMUM CLEARANCE OF 6 INCHES (152 MM) TO
 COMBUSTIBLE MATERIALS. CLOTHES DRYER TRANSITION DUCTS
 USED TO CONNECT THE APPLIANCE TO THE EXHAUST DUCT
 SYSTEM SHALL BE LIMITED TO SINGLE LENGTHS NOT TO EXCEED
 8 FEET (2438 MM) IN LENGTH AND SHALL BE LISTED AND
 LABELED FOR THE APPLICATION. TRANSITION DUCTS SHALL NOT
 BE CONCEALED WITHIN CONSTRUCTION.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2007-07-03 Cont ID  
Sent By tgordon Date 2007-07-03 Time 11:07 Rev Time 0.45
Received By tgordon Date 2007-07-03 Time 11:07 Sent To  
Notes
2007-07-03 11:15:33REVISION TO MECH. PLANS PAGES M-04, M-05 AND M-06.
  
 *** PROVISO ***
 1) FRESH AIR INTAKE TO COMPLY WITH 2004 FBC/M 401.5.1
 INTAKE OPENINGS.
 MECHANICAL AND GRAVITY OUTSIDE AIR INTAKE OPENINGS
 SHALL BE LOCATED A MINIMUM OF 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS, EXCEPT AS OTHERWISE SPECIFIED IN
 THIS CODE. FRESH AIR INTAKES SHALL NOT BE LOCATED
 CLOSER THAN 10 FEET (3048 MM) FROM ANY CHIMNEY OR VENT
 OUTLET, OR SANITARY SEWER VENT OUTLET.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2007-05-23 Cont ID  
Sent By tgordon Date 2007-05-23 Time 12:13 Rev Time 1.15
Received By tgordon Date 2007-05-23 Time 12:13 Sent To  
Notes
2007-05-23 12:15:22REVISION TO MECH. PLANS PAGES M-03, M-04, M-06, AND
 M-07.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-03-19 Cont ID  
Sent By tgordon Date 2007-03-19 Time 15:58 Rev Time 0.45
Received By tgordon Date 2007-03-19 Time 15:58 Sent To  
Notes
2007-03-19 15:59:23REVISION TO MECHANICAL PLANS PAGES M-02, M-04, M-05,
 AND M-06.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-09-06 Cont ID  
Sent By pkrauss Date 2006-09-06 Time 10:59 Rev Time 0.00
Received By pkrauss Date 2006-09-06 Time 10:59 Sent To  
Notes
2006-09-06 00:00:00PROVISO:
 PER RESPONSE LETTER DATED JUNE 19, 2006
 THE FOLLOWING ITEMS WILL BE REVISED
 AFTER PERMIT IS ISSUED.
  
 PLAN SHEET M-04 8 X 4 DUCT PENETRATING
 STORAGE ROOM 213 & 228, DUCT SHALL
 COMPLY WITH 2001 FMC 607.1.3 #3 ITEMS 1
 THROUGH 4.
  
 PER 2001 FBC 705.2.4.6, AUTOMATIC
 SPRINKLERS - AN APPROVED AUTOMATIC
 SPRINKLER SYSTEM SHALL BE INSTALLED AT
 THE TOP AND AT ALTERNATE FLOOR LEVELS IN
 REFUSE AND LAUNDRY CHUTES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719 OR
 E-MAIL [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-06-04 Cont ID  
Sent By pkrauss Date 2006-06-04 Time 12:12 Rev Time 0.00
Received By pkrauss Date 2006-06-04 Time 12:12 Sent To  
Notes
2006-06-04 00:00:00DENIED:
 COMMENT FROM REVIEW DATED
 PLANS ARE TO BE DATED IN ACCORDANCE WITH
 FS 471.025 & FAC 61G15-23.002 (2)
 SIGNATURE AND DATE SHALL BE LOCATED ON
 SEAL.PLEASE NOTE, PLANS REVISED AND
 SUBMITTED AFTER JANUARY 1,2006 THE SEAL
 SHALL INDICATE "LICENSE" NUMBER NOT
 "CERTIFICATE" NUMBER.
  
 PROVISO:
 PLAN SHEET M-04 8 X 4 DUCT PENETRATING
 STORAGE ROOM 213 & 228, DUCT SHALL
 COMPLY WITH 2001 FMC 607.1.3 #3 ITEMS 1
 THROUGH 4.
  
 PER 2001 FBC 705.2.4.6, AUTOMATIC
 SPRINKLERS - AN APPROVED AUTOMATIC
 SPRINKLER SYSTEM SHALL BE INSTALLED AT
 THE TOP AND AT ALTERNATE FLOOR LEVELS IN
 REFUSE AND LAUNDRY CHUTES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719 OR
 E-MAIL [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-12-07 Cont ID  
Sent By pkrauss Date 2005-12-07 Time 12:46 Rev Time 0.00
Received By pkrauss Date 2005-12-07 Time 11:04 Sent To  
Notes
2005-12-07 00:00:00DENIED:
 PLEASE CLARIFY THE FOLLOWING RESPONSES
 TO 2ND REVIEW (1ST REVIEW DATE 6/16/05):
  
 COMMENT #2 - RESPONSE INDICATES BIRD
 SCREEN REMOVED FROM DRYER VENTS.PER
 2001 FMC 504.4, DRYER EXHAUST IS TO BE
 EQUIPPED WITH A BACKDRAFT DAMPER.
  
 COMMENT #3 & 1 - PLEASE PROVIDE
 SUBMITTAL FOR THE COMMERCIAL GAS DRYERS
 & EXHAUST FANS.APPROVAL CANNOT BE
 GIVEN WITHOUT MANUFACTURER'S SUBMITTAL &
 INSTALLATION DATA FOR EQUIPMENT &
 APPLIANCES.
  
 PLEASE NOTE, PLANS ARE TO BE DATED IN
 ACCORDANCE WITH FS 471.025 & FAC
 61G15-23.002 (2).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-06-16 Cont ID  
Sent By pkrauss Date 2005-06-16 Time 13:58 Rev Time 6.50
Received By pkrauss Date 2005-06-16 Time 13:17 Sent To  
Notes
2005-06-16 00:00:00DENIED:
 1.SUBMITTAL BOOK DOES NOT INCLUDE
 SUBMITTAL DATA FOR MECHANICAL EQUIPMENT;
 RTU'S, SPLIT SYSTEMS, EXHAUST FANS
 DRYERS, ETC.
  
 2.PLAN SHEET M-02 FAN SCHEDULE - FAN
 #7 &8 ARE INDICATED FOR DRYERS. THE
 "REMARK" COLOUM IT INDICATES #4 A
 BIRDSCREEN.PER 2001 FBC(M)504.4,
 SCREENS SHALL NOT BE INSTALLEDAT DUCT
 TERMINATION.
  
 3.PLAN SHEET M-03, GUEST LAUNDRY -
 2001 FBC(M)504.6 DOESNOT ALLOW FOR
 IN-LINE FANS IN THE DRYER EXHAUST DUCT.
 IS THIS APPLICATION PERMITTED BY THE
 DRYER MANUFACTURER?COMMERCIAL LAUNDRY
 ROOM - 2001 FBC(M) 504.7, EXHAUST FAN
 MOTORS SHALL BE LOCATED OUTSIDE THE
 AIRSTREAM. IN MULTIPLE INSTALLATIONS THE
 FAN SHALL RUN CONTINUOUSLY OR BE
 INTERLOCKED TO RUN WHEN ANY INDIVIDUAL
 UNIT IS RUNNING.
  
 4.PLEASE NOTE, PER 2001 FBC(M)504.2
 CLOTHES DRYER EXHAUST DUCTS SHALL NOTE
 PENETRATE OR TERMINATE WITHIN ANY FIRE
 BLOCKING OR ANY FIRE RATED ASSEMBLY
 UNLESS DUCT IS CONSTRUCTED OF GALVENIZED
 OR ALUMINUM AS SPECIFIED IN TABLE 603.3.
  
 5.EXHAUST SHALL NOT BE DIRECTED ONTO
 WALK-WAYS, OR TERMINATE IN A MANNER THAT
 CREATES A NUISANCE. 2001 FBC(M) 401.5.2.
  
 6.OUTSIDE AIR INTAKES SHALL BE LOCATED
 A MINIMUM OF 10 FT FORM ANY NOXIOUS
 CONTAMINANT, PARKING LOTS, AND LOADING
 DOCKS.2001 FBC(M)401.5.1
  
 7.PLAN SHEET M-04, CLARIFY LOCATION OF
 TW-2.IT APPEARS TO BE IN A CLOSET IN
 BEDROOM 1 & INDICATES 18" X 18" LOUVER
 DOOR.SHOULD THIS READ GRILLE?
 RETURN AIR FROM BEDROOM 2 REQUIRED.
 RETURN FROM BEDROOM 2 SHALL BE SIZED IN
 ACCORDANCE WITH 2001 FBC(M)601.4.
  
 8.PLAN SHEET M-05 & M-03, INDICATE
 RETURN AIR PLENUMS IN THE COMMON AREAS.
 NO COMBUSTIBLES ALLOWED ABOVE THE
 CEILING IN THE RETURN AIR PLENUM, 2001
 FBC(M) 602.2.1.
  
 9.PLAN SHEET M-07 NOTE #1, PLEASE NOTE
 AUXILIARY DRAIN PAN SHALL HAVE OVERFLOW
 ROTECTION.PLEASE INDICATE WHICH METHOD
 WILL BE USED AS SPECIFIED IN 307.2.3.
  
 10.PLEASE PROVIDE OUSTIDE AIR
 CALUCALTIONS FOR ALL AREAS PER 2001
 FBC(M) TABLE 403.3.
  
 11.PLEASE CLARIFY SMOKE CONTROL (IF
 ANY).PROVIDE SEQUENCE OF OPERATION.
  
 12. PROVIDE DETAIL FOR THE CONDESING
 UNIT STANDS LOCATED ON THE ROOF. HEIGHT
 FROM THE ROOF SURFACE TO THE BOTTOM OF
 THE SUPPORT RAIL SHALL BE IN ACCORDANCE
 WITH 2001 FBC 1511.7.PROVIDE DETAIL
 FOR SECURING UNITS.
  
 IF YOU HAVE ANY QUESTIONSS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  

Review Stop P PLUMBING
Rev No 13 Status F Date 2008-02-22 Cont ID  
Sent By kstevens Date 2008-02-22 Time 14:18 Rev Time 0.00
Received By kstevens Date 2008-02-22 Time 14:18 Sent To  
Notes
2008-02-22 14:30:47DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 FUEL GAS
  
 1. OK
 2. OK
  
 3. SHT P-08 GAS RISER DIAGRAM 2-1/2" REQUIRED FROM THE
 METER AND UP TO THE BRANCH LINE FOR THE GAS DRYERS.
 TABLE 402(8).--POOL/BATH HOUSE GAS RISER DIAGRAM
 DOES NOT REFLECT THE GAS RISER DIAGRAM AT THE METER.
 SHOW ALL CUT LENGTHS FOR THE POOL HEATER GAS LINES FROM
 WHERE IT CONNECTS TO THE MAIN GAS RISER DIAGRAM.--
 INDICATE REGULATOR MODEL NUMBERS FOR THE GAS DRYERS,
 THE HOT WATER BOOSTER, POOL HEATER AND THE RTU'S 1, 2 &
 3.
 ****RESPONSE NOTED, BUT THE RISER DIAGRAM STILL SHOWS
 2" PIPE UP TO THE BRANCH LINE FOR THE GAS DRYERS. THERE
 WAS NO RESPONSE TO THE RISER DIAGRAM FOR THE POOL/BATH
 RISER NOT REFLECTING THE GAS RISER AT THE METER AND ALL
 CUT SECTIONS WERE NOT PROVIDED.--REGULATOR MODELS
 INDICATED FOR RTU'S 1 & 2 ARE NOT APPROVED. MAXIMUM 140
 MBH FOR THE MODEL 325-3L, BUT 150 MBH INDICATED ON THE
 RISER DIAGRAM.
  
 4. SHT P-08 REVISION HISTORY ON STAMPED/REVIEWED SHEET
 INDICATES REVISIONS 2 & 3. THESE HAVE BEEN DELETED FROM
 THE REVISION HISTORY.--NEW REVISIONS THIS SUBMITTAL
 INDICATE REVISIONS 5, 7 & 8, BUT ONLY REVISION 8 HAS
 BEEN LOCATED. PLEASE INDICATE WHERE REVISIONS 5 & 7 CAN
 BE FOUND. SHOW THE COMPLETE REVISION HISTORY ON THE
 REVISION INDEX. SECTION 104.2.1.3.
 ****RESPONSE NOTED, BUT THE SHEET ON FILE AND REVIEWED
 SHOWS REVISION 2, DATED 1-13-06, AND REVISION 3, DATED
 6-12-06. PLEASE SHOW COMPLETE REVISION HISTORY ON THE
 REVISION INDEX. SECTION 104.2.1.3.
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.-- THE
 MANUF. SHEETS FOR THE POOL HEATER SHALL
 BE SUBMITTED.
 ****RESPONSE NOTED, BUT THE DRYER MANUF SHEETS ARE NOT
 APPROVED. THERE IS NO LISTING INDICATED ON THE MANUF.
 SHEETS.NO BTU LOAD INDICATED. COVER SHEET STATES
 "REFER TO PAGE 4 FOR MODEL IDENTIFICATION". PAGE 4 HAS
 NOT BEEN SUBMITTED WITH MANUF. SPECIFICATION SHEETS. --
 NO MANUF. SHEETS FOR THE RTU UNITS1 & 2 SUBMITTED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 12 Status P Date 2008-02-22 Cont ID  
Sent By kstevens Date 2008-02-22 Time 14:16 Rev Time 0.00
Received By kstevens Date 2008-02-22 Time 14:15 Sent To  
Notes
2008-02-22 14:18:36REVISIONS OK--SHTS P-05A, P-05B & P-06

Review Stop P PLUMBING
Rev No 11 Status F Date 2008-01-17 Cont ID  
Sent By kstevens Date 2008-01-17 Time 08:30 Rev Time 0.00
Received By kstevens Date 2008-01-16 Time 16:53 Sent To  
Notes
2008-01-17 12:06:39DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 FUEL GAS
  
 1. SHTS P-05A, P-O5B & P-06 PER SECTION 1107.3 THE
 CROSS-SECTIONAL AREA OF AN OVERFLOW SCUPPER SHALL BE
 THREE TIMES THE CROSS-SECTIONAL AREA OF THE PRIMARY
 ROOF DRAIN AND THE SCUPPER SHALL HAVE A MINIMUM OPENING
 DIMENSION OF 4 INCHES.
  
 2. SHTS P-05A, P-05B & P-06 PER SECTION 1503.4.2
 OVERFLOW SCUPPERS SHALL HAVE A MINIMUM OPENING
 DIMENSION OF 4 INCHES IN HEIGHT AND SHALL BE PLACED IN
 WALLS OR PARAPETS WITH THE INLET FLOW LINE NOT LESS
 THAN 2 INCHES ABOVE THE ROOF SURFACE, EXCLUDING SUMPS,
 OR MORE THAN 4 INCHES ABOVE THE ROOF SURFACE AND SHALL
 BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED VERTICAL
 LEADERS. EACH VERTICAL LEADER SHALL BE SUPPLIED WITH AN
 EMERGENCY OVERFLOW SCUPPER SIZED PER SECTION 1107.3 OF
 THE PLUMBING CODE.
  
 3. SHT P-08 GAS RISER DIAGRAM 2-1/2" REQUIRED FROM THE
 METER AND UP TO THE BRANCH LINE FOR THE GAS DRYERS.
 TABLE 402(8).--POOL/BATH HOUSE GAS RISER DIAGRAM
 DOES NOT REFLECT THE GAS RISER DIAGRAM AT THE METER.
 SHOW ALL CUT LENGTHS FOR THE POOL HEATER GAS LINES FROM
 WHERE IT CONNECTS TO THE MAIN GAS RISER DIAGRAM.--
 INDICATE REGULATOR MODEL NUMBERS FOR THE GAS DRYERS,
 THE HOT WATER BOOSTER, POOL HEATER AND THE RTU'S 1, 2 &
 3.
  
 4. SHT P-08 REVISION HISTORY ON STAMPED/REVIEWED SHEET
 INDICATES REVISIONS 2 & 3. THESE HAVE BEEN DELETED FROM
 THE REVISION HISTORY.--NEW REVISIONS THIS SUBMITTAL
 INDICATE REVISIONS 5, 7 & 8, BUT ONLY REVISION 8 HAS
 BEEN LOCATED. PLEASE INDICATE WHERE REVISIONS 5 & 7 CAN
 BE FOUND. SHOW THE COMPLETE REVISION HISTORY ON THE
 REVISION INDEX. SECTION 10104.2.1.3.
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.-- THE
 MANUF. SHEETS FOR THE POOL HEATER SHALL
 BE SUBMITTED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 10 Status F Date 2007-10-15 Cont ID  
Sent By kstevens Date 2007-10-15 Time 14:35 Rev Time 0.00
Received By kstevens Date 2007-10-15 Time 14:35 Sent To  
Notes
2007-10-15 14:44:50DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 A. SHT P-02C REVISION #5 DATED 07/11/07 & REVISION #6
 DATED 07/22/07 WERE APPROVED PREVIOUSLY. NO
 CHANGE/REVISION NOTED. SHEET NOT APPROVED.
  
 B. SHT P-06 THE ROOF DRAINAGE AREA SHOWN DOES NOT
 APPEAR TO BE CORRECT. SEE PREVIOUS REVISION COMMENTS
 FOR THIS SHEET. NO CALCULATIONS WERE SUBMITTED, AND NO
 INFORMATION FOR THE SCUPPERS AS REQUESTED. (SEE
 FOLLOWING FROM PREVIOUS REVIEW DATED 09/05/07):
  
 (5). SHT P-06 INDICATES A ROOF DRAIN ON WHAT APPEARS TO
 BE A HIP ROOF. PLEASE CLARIFY.--SUBMIT A DETAIL FOR
 THE ROOF DRAIN CONNECTION TO THE PEAK OF THE ROOF. --
 SUBMIT CALCULATIONS FOR THE PRIMARY AND SECONDARY ROOF
 DRAINS, (IF ROOF HAS A PARAPET) PER SECTIONS 1106 &
 1107 WITH ALL SUBSECTIONS & TABLES. SHOW THE SQUARE
 FOOTAGE OF THE ROOF AND 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS ADDED TO THE ROOF AREA IN THE
 CALCULATIONS.--ROOF DRAIN IS NOT SHOWN ON THE
 STORM DRAIN TABLE. PLEASE CLARIFY. SECTION 104.2.1.--
 SHOW THE LOCATION OF ALL SECONDARY ROOF DRAINS OR
 EMERGENCY ROOF SCUPPERS. SECTION 104.2.1.--NOTE ON
 PLANS STATES "FOR RELIEF SCUPPER DRAINS SEE ARCH.
 DRAWINGS". PLEASE INDICATE WHERE IN THE ARCHITECTURAL
 DRAWINGS THESE CAN BE FOUND. SECTION 104.2.1.--
 PLEASE RESPOND TO ALL OF THIS AFTER AND INCLUDING
 "SUBMIT CALCULATIONS.....
  
 C. SHT P-08 SEE THE FOLLOWING COMMENTS FROM 10/13/07
 FOR THE GAS ISOMETRIC RISER DIAGRAM:
  
 DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.--COMPLETE ISOMETRIC NOT SUBMITTED.
 SUBMIT A COMPLETE ISOMETRIC WITH THE PIPING FOR THE
 POOL HOUSE WATER HEATER SHOWN WITH ALL CUT SECTIONS AND
 CORRESPONDING LENGHTS.--INDICATE THE MODEL OF EACH
 REGULATOR ON THE ISOMETRIC.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.--NOT
 INDICATED FOR POOL HOUSE WATER HEATER.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).--POOL HOUSE WATER HEATER NOT INDICATED.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).--TO BE VERIFIED ONCE
 RESPONSE FOR COMMENT IS REVIEWED.
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.--POOL HOUSE WATER
 HEATER MANUF. SHEETS REQUIRED.
  
 6. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR ALL
 REGULATORS. INDICATED MODEL NUMBER USED FOR EACH
 REGULATOR AND INDICATE WHERE EACH REGULATOR MODEL WILL
 BE USED TO VERIFY CAPACITY.
  
 ****END OF GAS COMMENTS FROM 10-13-07****
  
 D. SHT P-11 NO CHANGE FROM REVISION #4 ON SHEET SEALED
 07/06/07. SHEET NOT APPROVED AS THERE ARE NO NEW
 REVISIONS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 9 Status P Date 2007-10-15 Cont ID  
Sent By kstevens Date 2007-10-15 Time 14:33 Rev Time 0.00
Received By kstevens Date 2007-10-15 Time 14:33 Sent To  
Notes
2007-10-15 14:34:52REVISIONS OK--SHTS P-03A, P-04A, P-05A & P-11

Review Stop P PLUMBING
Rev No 8 Status P Date 2007-10-13 Cont ID  
Sent By kstevens Date 2007-10-13 Time 10:22 Rev Time 0.00
Received By kstevens Date 2007-10-13 Time 10:22 Sent To  
Notes
2007-10-13 10:24:18REVISION OK--SHT P-02C CHANGES TO GAS SIZING AND
 INDICATING NEW LINE TO POOL HOUSE HEATER.

Review Stop P PLUMBING
Rev No 7 Status P Date 2007-09-05 Cont ID  
Sent By kstevens Date 2007-09-05 Time 13:00 Rev Time 0.00
Received By kstevens Date 2007-09-05 Time 13:00 Sent To  
Notes
2007-09-05 14:06:19REVISIONS OK--SHTS P-01, P-02A, P-05B & P-11

Review Stop P PLUMBING
Rev No 6 Status F Date 2007-09-05 Cont ID  
Sent By kstevens Date 2007-09-05 Time 12:01 Rev Time 0.00
Received By kstevens Date 2007-09-04 Time 13:24 Sent To  
Notes
2007-09-05 12:53:05REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1. SHT P-02C REVISION #5 TO BE INDICATED ON ALL
 REVISIONS ON SHEET. CLOUDS INDICATED, BUT WITHOUT THE
 REVISION NUMBERS. SECTION 104.2.1.3.
  
 2. SHT P-03A DRAWING NOTES (14) & (15). ICE MACHINE AND
 FLOOR SINK DELETED FROM THE FLOOR PLAN, BUT NOTES STILL
 SHOWN. DELETE NOTES ALSO. SECTION 104.2.1.
  
 3. SHT P-04A DRAWING NOTES (14) & (15). ICE MACHINE AND
 FLOOR SINK DELETED FROM THE FLOOR PLAN, BUT NOTES STILL
 SHOWN. DELETE NOTES ALSO. SECTION 104.2.1.-- REVISION
 #5 HAS NOT BEEN LOCATED. MANY REVISIONS INDICATED
 WITHOUT REVISION NUMBERS. ALL REVISIONS TO BE CLOUDED
 AND NUMBERED. SECTION 104.2.1.3.--REVISION #4 CLOUD
 VERY FAINT AND NOT VERY LEGIBLE. DARKEN CLOUDS TO MAKE
 REVISIONS NOTICIBLE. SECTION 104.2.1.3.-- REVISION #4
 SHOWS WATER LINES UP TO A SHOWER, A TUB & LAV, BUT SHT
 P-05A SHOWS NOT UNIT ABOVE. PLEASE CLARIFY. SECTION
 104.2.1.
  
 4. SHT P-05A REVISION INDICATED FOR THE GAS RISER WITH
 A CLOUD, BUT NO REVISION NUMBER INDICATED. PLEASE CLOUD
 AND NUMBER ALL REVISIONS. SECTION 104.2.1.3.
  
 5. SHT P-06 INDICATES A ROOF DRAIN ON WHAT APPEARS TO
 BE A HIP ROOF. PLEASE CLARIFY.--SUBMIT A DETAIL FOR
 THE ROOF DRAIN CONNECTION TO THE PEAK OF THE ROOF. --
 SUBMIT CALCULATIONS FOR THE PRIMARY AND SECONDARY ROOF
 DRAINS, (IF ROOF HAS A PARAPET) PER SECTIONS 1106 &
 1107 WITH ALL SUBSECTIONS & TABLES. SHOW THE SQUARE
 FOOTAGE OF THE ROOF AND 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS ADDED TO THE ROOF AREA IN THE
 CALCULATIONS.--ROOF DRAIN IS NOT SHOWN ON THE
 STORM DRAIN TABLE. PLEASE CLARIFY. SECTION 104.2.1.--
 SHOW THE LOCATION OF ALL SECONDARY ROOF DRAINS OR
 EMERGENCY ROOF SCUPPERS. SECTION 104.2.1.--NOTE ON
 PLANS STATES "FOR RELIEF SCUPPER DRAINS SEE ARCH.
 DRAWINGS". PLEASE INDICATE WHERE IN THE ARCHITECTURAL
 DRAWINGS THESE CAN BE FOUND. SECTION 104.2.1.
  
 6. SHT P-08 GAS RISER ISOMETRIC DIAGRAM. THE GAS
 REGULATORS FOR THE DOMESTIC WATER BOILERS ARE NOT
 APPROVED. THE MAXIMUM INDIVIDUAL LOAD FOR THE MAXITROL
 MODEL 325-51 IS ONLY 250,000 BTU'S. THE RISER DIAGRAM
 INDICATES 400,000 BTU'S FOR EACH BOILER. (SEE ATTACHED
 SHEET). PLEASE SPECIFY THE CORRECT REGULATORS FOR THE
 BOILERS. SECTION 410.2(1). (ALSO CORRECT REGULATOR
 MODEL NUMBER ON DETAIL FOR WATER HEATERS SHEET P-07).
  
 7. SHT P-16 WATER RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. RISER SHOWS 2 TUBS, WHEREAS THE FLOOR PLAN
 SHOWS ONE TUB. ALSO SEE SHT P-04A THE WATER SUPPLY IS
 SHOWN IN UNIT 214 WHICH IS RISER W2, BUT THE WATER
 SUPPLY FOR UNIT ON THE 6TH FLOOR IS SHOWN ON RISER W4
 ON THE RISER DIAGRAM. PLEASE CORRELATE. SECTION
 104.2.1.
  
 8. NOTE: WHEN SUBMITTING REVISIONS, PLEASE TURN OFF ALL
 PREVIOUSLY APPROVED REVISION CLOUDS AND REVISION
 NUMBERS. LEAVING THE PREVIOUS CLOUDS AND REVISION
 NUMBERS CAUSES CONFUSION AND INCREASES THE TURN AROUND
 TIME FOR THE REVIEWS. THANK YOU.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 5 Status P Date 2007-06-19 Cont ID  
Sent By kstevens Date 2007-06-19 Time 07:56 Rev Time 0.00
Received By kstevens Date 2007-06-18 Time 19:02 Sent To  
Notes
2007-06-19 07:58:13 
  
  
 REVISION OK--SHTS P-02A & P-02B--REVISIONS
 REQUIRED FOR THE GAS, WATER, SANT, OR CONDENSATE RISER
 DIAGRAMS TO REFLECT THE CHANGES SHOWN ON THE FLOOR
 PLAN.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 .

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-08-15 Cont ID  
Sent By kstevens Date 2006-08-15 Time 13:02 Rev Time 0.00
Received By kstevens Date 2006-08-12 Time 18:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-05-08 Cont ID  
Sent By kstevens Date 2006-05-08 Time 17:10 Rev Time 0.00
Received By kstevens Date 2006-05-05 Time 18:57 Sent To  
Notes
2006-05-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
 1. PLANS SHALL BE ROUTED TO DBPR
 DIVISION OF HOTEL AND RESTURANTS FOR
 REVIEW. MINIMUM OF 2 STAMPED SETS OF
 PLANS SHALL BE SUBMITTED TO THE CITY FOR
 REVIEW WITH 2 PAGE "WORK SHEETS"
 ATTACHED TO EACH SET. SECTION 101.4.7. -
 PER RESPONSE SHEET CONTRACTOR WAS
 SUPPOSED TO DO THIS. NO STAMPED SETS OF
 PLANS OR WORKSHEETS SUBMITTED.
 ***RESPONSE NOTED, BUT "SULLIVAN HAS NOT
 DONE THIS.
  
 4. SHT C-8 CIVIL WATER AND SEWER PLANS.
 NO WATER SERVICE TO THE BUILDING IS
 SHOWN. PLEASE INDICATE WATER SERVICE ON
 PLANS INCLUDING PIPE SIZE, VALVES,
 BACKFLOW ECT. - SHT C-9 INDICATES A 3"
 DIP WATER SERVICE, BUT NO BACKFLOW SHOWN
 FOR WATER SERVICE TO BUILDING.
 ***RESPONSE NOTED, BUT I CONTACTED MR.
 DEAN LAUDERMILK FROM WPB ENGINEERING,
 AND HE ADVISED ME THAT NEW SHEETS, DATED
 4-4-06, SHOWING A SEPARATE 8" LINE FOR
 FIRE AND 4" LINE FOR DOMESTIC WATER WITH
 A 3" METER ARE SHOWN. PLEASE SUBMIT NEW
 SHEETS FOR CIVIL WITH NEXT RESUBMITTAL.
 SECTION 106.1.1.
  
 9. SHT A-6.2 SHOW THE ACCESSIBLE W/C'S
 TO BE 18" OFF THE WALL TO THE CENTERLINE
 OF THE FIXTURE, AS REQUIRED IN FIG. 28.
 - NOT ADDRESSED, ALSO SEE FIG 30E.
 ***RESPONSE NOTED, MEASUREMENTS FOUND ON
 SHEETS A-1.1, A-1.4 & A-6.0,BUT THIS IS
 NOT SHOWN ON ANY OF THE ELEVATIONS ON
 SHEET A-6.2 AS INDICATED.
  
 10) SHT A-6.2 SHOW THE FOLLOWING FOR THE
 ACCESSIBLE FIXTURES:
 FOR W/C'S
 E. DISPENSERS 11-4.16.6 INDICATE HEIGHT
 AS REQUIRED. (PLANS SHOW WITHIN REACH)
 FOR LAVS
 A. HEIGHT & CLEARANCES 11-4.19.2 -
 CLEARANCE MEASUREMENT NOT SHOWN. NO
 CLEARANCE SHOWN AS OF YET.
 ***RESPONSE NOTED, BUT RESPONSE NOT
 ADEQUATE. W/C 'C' INDICATES GRAB BARS TO
 BE 36" MIN. WHEN THEY ARE TO BE 33" TO
 36". DETAIL FOR ACCESSIBLETOILET
 ACCESSORIES INDICATE THAT THE LIP OF THE
 URINAL TO BE 20". IT IS SUPPOSED TO BE
 17" MAX. PLUS SEE NOTES "C" FOR W/C AND
 "A" FOR LAVS.
  
 12. ALL MECH., ELECT., & PLMB. SHEETS.
 EACH SHEET OF PLANS WHICH MUST BE SEALED
 UNDER THE PROVISIONS OF CHAPTER 471
 SHALL BE SEALED, SIGNED AND DATED BY THE
 PROFESSIONAL ENGINEER. 61G15-23.002(1).
 NO DATE AFFIXED TO SEAL/SIGNATURE. -
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS THE
 NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. 61G15-23.002(2)
 FAC, & FS 471.025. - THE DATE SEAL AND
 SIGNATURE SHALL BE PLACED ON SEAL.
 ***RESPONSE NOTED, BUT THE SEAL IS NOT
 DATED YET ON MANY SHEETS. ALSO SHEETS
 SEALED AFTER JAN. 1, 2006 SHALL BE
 SEALED WITH THE NEW "LICENCE" SEAL PER
 ATTACHED LETER FROM THE FLORIDA BOARD OF
 PROFESSIONAL ENGENEERS.
  
 30. THE FOLLOWING INFORMATION IS RQUIRED
 FOR GAS PERMIT:
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3). - WILL CHECK
 WHEN ALL LENGTHS ARE SHOWN. ***RESPONSE
 NOTED, BUT THE TOTAL DEVELOPED LENGTH
 ADDS UP TO 232FT TO R.T.U #2, NOT 244
 FT. AS SHOWN.
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. -
 DELEVERY PRESSURE IS USUALLY 11 TO 14
 INCHES OF WATER COLUMN OR 56 INCHES OF
 WATER COLUMN, AND PLANS SHOW 7". PLEASE
 CHECK WITH GAS PROVIDER AND VERIFY THE
 DELIVERY PRESSURE. -RESPONSE NOTED,
 BUT PLANS STILL SHOW 7" WATER COLUMN.
 ***RESPONSE NOTED, BUT THE PLANS STILL
 SHOW 7"WC PRESSURE. PLEASE CALL MR.
 ROLAND PARKER, SERVICE MANAGER FLORIDA
 PUBLIC UTILITIES AT (561) 838-1818 AS HE
 HAS INDICATED TO ME THAT FPU DELIVERS
 12" TO 14" WATER COLUMN MINIMUM
 PRESSURE.
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2. - GAS
 DRYER AND RTU'S MANUF. SHEETS NOT FOUND.
 ***RESPONSE NOTED, BUT MANUF. SHEETS FOR
 THE RTU-2 UNITS HAVE NOT BEEN SUBMITTED.
 ALSO DRYER MANUF. SPECIFICATION SHEET
 INDICATES THE BTU'SARE 165,000 WHERE
 AS THE RISER DIAGRAM INDICATES 215,000
 BTU'S. PLEASE CLARIFY AND CORRELATE THE
 MANUF. INFORMATION WITH THE RISER
 DIAGRAM.
  
 ***************NEW COMMENT**************
 1C. SHT P-08 THE FOLLOWING INFORMATION
 HAS BEEN DELETED FROM PREVIOUS SUBMITTED
 SHEETS:
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 2C. SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS 553.80(2)(B).
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-11-26 Cont ID  
Sent By kstevens Date 2005-11-26 Time 20:13 Rev Time 7.00
Received By kstevens Date 2005-11-26 Time 20:13 Sent To  
Notes
2005-11-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
 1. PLANS SHALL BE ROUTED TO DBPR
 DIVISION OF HOTEL AND RESTURANTS FOR
 REVIEW. MINIMUM OF 2 STAMPED SETS OF
 PLANS SHALL BE SUBMITTED TO THE CITY FOR
 REVIEW WITH 2 PAGE "WORK SHEETS"
 ATTACHED TO EACH SET. SECTION 101.4.7. -
 PER RESPONSE SHEET CONTRACTOR WAS
 SUPPOSED TO DO THIS. NO STAMPED SETS OF
 PLANS OR WORKSHEETS SUBMITTED.
 3. GREASE INTERCEPTOR SHALL BE SIZED BY
 RODNEY COMPO, ENVIRONMENTAL COMPLIANCE.
 (561) 837-4074, E-MAIL [email protected],
 OR FAX (561) 659-7458. THE DETERMINATION
 WORKSHEET FROM MR. COMPO SHALL BE
 ATTACHED TO PLANS WHEN RESUBMITTING FOR
 REVIEW. - NO INFORMATION FROM MR. COMPO
 AS OF YET. I WILL CHECK TO SEE IF HE HAS
 A DETERMINATION FOR THIS JOB.
 4. SHT C-8 CIVIL WATER AND SEWER PLANS.
 NO WATER SERVICE TO THE BUILDING IS
 SHOWN. PLEASE INDICATE WATER SERVICE ON
 PLANS INCLUDING PIPE SIZE, VALVES,
 BACKFLOW ECT. - SHT C-9 INDICATES A 3"
 DIP WATER SERVICE, BUT NO BACKFLOW SHOWN
 FOR WATER SERVICE TO BUILDING.
 5. SHTS A-1.0, & A-6.1,(DETAILS 10 & 11)
 LOUNGE SINK SHALL COMPLY WITH 11-4.24
 AND ALL SUBSECTIONS. SHOW THE FOLLOWING:
 B. KNEE CLEARANCE 11-4.24.3 - KNEE
 CLEARANCE NOT SHOWN.
 C. SINK DEPTH 11-4.24.4 - SINK DEPTH
 NOT SHOWN.
 D. CLEAR FLOOR SPACE 11-4.24.5 SHALL BE
 FORWARD APPROACH, AND SHALL EXTEND A
 MAXIMUM 19" UNDERNEATH THE SINK. CABINET
 DOORS ARE NOT APPROVED, MUST BE "CLEAR"
 FLOOR SPACE. - CLEAR FLOOR SPACE SHALL
 BE SHOWN ON THE FLOOR PLAN.
 E. EXPOSED PIPES & SURFACES 11-4.24.6 -
 NO RESPONSE TO THIS REQUIREMENT.
 F. FAUCETS 11-4.24.7 - NO RESPONSE TO
 THIS REQUIREMENT.
 6. SHOW COMPLIANCE WITH SECTION 11-9.1.4
 INDICATE ROOM NUMBERS FOR EACH
 REQUIREMENT. - THERE ARE 6 DIFFERENT
 TYPES OF UNITS SHOWN, BUT ONLY SUITES 1,
 2, AND A SHOW ACCESSIBLE UNITS. PLEASE
 INDICATE WHY SUITES B, C, AND D HAVE NO
 ACCESSIBLE UNITS AS REQUIRED BY SECTION
 11-9.1.4.
 9. SHT A-6.2 SHOW THE ACCESSIBLE W/C'S
 TO BE 18" OFF THE WALL TO THE CENTERLINE
 OF THE FIXTURE, AS REQUIRED IN FIG. 28.
 - NOT ADDRESSED, ALSO SEE FIG 30E.
 10) SHT A-6.2 SHOW THE FOLLOWING FOR THE
 ACCESSIBLE FIXTURES:
 FOR W/C'S
 A. CLEAR FLOOR SPACE. 11-4.16.2 -
 SUPERIMPOSE CLEAR FLOOR SPACE ON PLANS.
 SEE FIG'S 28 & 30E.
 D. FLUSH CONTROLS 11-4.16.5 - NOT
 INDICATED TO WIDE SIDE OF W/C.
 E. DISPENSERS 11-4.16.6 - INDICATE
 HEIGHT AS REQUIRED.
 FOR URINAL
 B. CLEAR FLOOR SPACE 11-4.18.3 - NOT
 SHOWN.
 FOR LAVS
 A. HEIGHT & CLEARANCES 11-4.19.2 -
 CLEARANCE MEASUREMENT NOT SHOWN.
 B. CLEAR FLOOR SPACE 11-4.19.3 - SHOW
 ON PLANS.
 C. EXPOSED PIPES & SURFACES 11-4.19.4 -
 INDICATE METHOD.
 D. FAUCETS 11-4.19.5 - NOT ADDRESSED.
 12. ALL MECH., ELECT., & PLMB. SHEETS.
 EACH SHEET OF PLANS WHICH MUST BE SEALED
 UNDER THE PROVISIONS OF CHAPTER 471
 SHALL BE SEALED, SIGNED AND DATED BY THE
 PROFESSIONAL ENGINEER. 61G15-23.002(1).
 NO DATE AFFIXED TO SEAL/SIGNATURE. -
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS THE
 NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. 61G15-23.002(2)
 FAC, & FS 471.025. - THE DATE SEAL AND
 SIGNATURE SHALL BE PLACED ON SEAL.
 13. SHT P-01 DOMESTIC PUMPS SHALL BE
 LISTED. SUBMIT MANUF. SPECIFICATION
 SHEETS. SECTION 303.4. - NO LISTING
 SHOWN ON SHEETS.
 19. SHT P-02C KITCHEN EQUIPMENT
 CONNECTION NOTES 1 & 4. THE AIR GAP
 SHALL BE TWICE THE DIAMETER OF THE
 EFFECTIVE OPENING OF THE INDIRECT WASTE
 PIPE. SECTION 802.2.1. - NOTE #1 3" AIR
 GAP REQUIRED. 1-1/2" SHOWN.
 30. THE FOLLOWING INFORMATION IS RQUIRED
 FOR GAS PERMIT:
 A. SHT P-08 SUBMIT AN ISOMETRIC DRAWING
 THAT CLEARLY SHOWS ALL CUT SECTIONS OF
 PIPE AND CORRESPONDING LENGTHS PER
 FBC-2001 FUEL GAS CODE. - NOT ALL
 SECTIONS SHOW THE LENGTH OF THE PIPES.
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3). - WILL CHECK
 WHEN ALL LENGTHS ARE SHOWN.
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. -
 DELEVERY PRESSURE IS USUALLY 11 TO 14
 INCHES OF WATER COLUMN OR 56 INCHES OF
 WATER COLUMN, AND PLANS SHOW 7". PLEASE
 CHECK WITH GAS PROVIDER AND VERIFY THE
 DELIVERY PRESSURE. -RESPONSE NOTED,
 BUT PLANS STILL SHOW 7" WATER COLUMN.
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2. - GAS
 DRYER AND RTU'S MANUF. SHEETS NOT FOUND.
 ***************NEW COMMENT**************
 1B. GREASE INTERCEPTOR SHOWN IN STORAGE
 ROOM NOT APPROVED. GREASE INTERCEPTOR
 SHALL BE LOCATED OUTSIDE OF THE BUILDING
 FOR SERVICING. MISSED LOCATION ON FIRST
 REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-06-07 Cont ID  
Sent By kstevens Date 2005-06-07 Time 12:50 Rev Time 18.50
Received By kstevens Date 2005-06-06 Time 16:36 Sent To  
Notes
2005-06-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. PLANS SHALL BE ROUTED TO DBPR
 DIVISION OF HOTEL AND RESTURANTS FOR
 REVIEW. MINIMUM OF 2 STAMPED SETS OF
 PLANS SHALL BE SUBMITTED TO THE CITY FOR
 REVIEW WITH 2 PAGE "WORK SHEETS"
 ATTACHED TO EACH SET. SECTION 101.4.7.
 2. SUBMIT CALCULATIONS FOR MINIMUM
 FACILITIES FOR 1ST AND 6TH FLOOR COMMON
 AREAS PER TABLES 1003.2 (BLDG) AND 104.3
 (PLMG). SHOW SQUARE FEET OF EACH COMMON
 AREA. ASSEMBLY AREAS SHALL HAVE POTTY
 PARITY PER SECTION 403.1.1.
 3. GREASE INTERCEPTOR SHALL BE SIZED BY
 RODNEY COMPO, ENVIRONMENTAL COMPLIANCE.
 (561) 837-4074, E-MAIL [email protected],
 OR FAX (561) 659-7458. THE DETERMINATION
 WORKSHEET FROM MR. COMPO SHALL BE
 ATTACHED TO PLANS WHEN RESUBMITTING FOR
 REVIEW.
 4. SHT C-8 CIVIL WATER AND SEWER PLANS.
 NO WATER SERVICE TO THE BUILDING IS
 SHOWN. PLEASE INDICATE WATER SERVICE ON
 PLANS INCLUDING PIPE SIZE, VALVES,
 BACKFLOW ECT.
 5. SHTS A-1.0, & A-6.1,(DETAILS 10 & 11)
 LOUNGE SINK SHALL COMPLY WITH 11-4.24
 AND ALL SUBSECTIONS. SHOW THE FOLLOWING:
 A. HEIGHT 11-4.24.2
 B. KNEE CLEARANCE 11-4.24.3
 C. SINK DEPTH 11-4.24.4
 D. CLEAR FLOOR SPACE 11-4.24.5 SHALL BE
 FORWARD APPROACH, AND SHALL EXTEND A
 MAXIMUM 19" UNDERNEATH THE SINK. CABINET
 DOORS ARE NOT APPROVED, MUST BE "CLEAR"
 FLOOR SPACE.
 E. EXPOSED PIPES & SURFACES 11-4.24.6
 F. FAUCETS 11-4.24.7
 6. SHOW COMPLIANCE WITH SECTIONS
 11-9.1.2, 11-9.1.3, 11-9-1-4, & 11-9.2.3
 INDICATE ROOM NUMBERS FOR EACH
 REQUIREMENT.
 7. SHT A-1.5 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106 & 1107 AND ALL SUBSECTIONS
 INDICATE THE SQUARE FOOTAGE OF EACH
 AREA, AND SHOW 1/2 AREA OF ALL VERTICAL
 WALLS INCLUDING PARAPETS ADDED TO THE
 SQUARE FOOTAGE OF EACH AREA AS WELL AS
 ANY ROOF AREA DRAINING ON TO THE FOOR
 FROM ABOVE IN THE CALCULATIONS. SHOW THE
 LOCATIONS FOR ALL SECONDARY ROOF DRAINS.
 8. SHT A-6.0 SHOW CLEAR FLOOR SPACE FOR
 LAVS. SECTION 11-4.19.3.
 9. SHT A-6.2 SHOW THE ACCESSIBLE W/C'S
 TO BE 18" OFF THE WALL TO THE CENTERLINE
 OF THE FIXTURE, AS REQUIRED IN FIG. 28.
 10) SHT A-6.2 SHOW THE FOLLOWING FOR THE
 ACCESSIBLE FIXTURES:
 FOR W/C'S
 A. CLEAR FLOOR SPACE. 11-4.16.2
 B. HEIGHT 11-4.16.3 (ONE SHOWS 15")
 C. GRAB BARS 11-4.16.4 (ONE SHOWS 37")
 D. FLUSH CONTROLS 11-4.16.5
 E. DISPENSERS 11-4.16.6
 FOR URINAL
 A. HEIGHT 11-4.18.2
 B. CLEAR FLOOR SPACE 11-4.18.3
 C. FLUSH CONTROLS 11-4.18.4
 FOR LAVS
 A. HEIGHT & CLEARANCES 11-4.19.2
 B. CLEAR FLOOR SPACE 11-4.19.3
 C. EXPOSED PIPES & SURFACES 11-4.19.4
 D. FAUCETS 11-4.19.5
 11. SHT A-8.0 ROOM FINISH SCHEDULE. 1ST
 FLOOR AND 6TH FLOOR TOILET ROOMS. WALLS
 SHALL BE NON-ABSORBENT UP TO 4' ABOVE
 THE FLOOR. EXPLAIN HOW THIS WILL
 ACHIEVED BY PAINTING GWB. SECTION 1204.2
 12. ALL MECH., ELECT., & PLMB. SHEETS.
 EACH SHEET OF PLANS WHICH MUST BE SEALED
 UNDER THE PROVISIONS OF CHAPTER 471
 SHALL BE SEALED, SIGNED AND DATED BY THE
 PROFESSIONAL ENGINEER. 61G15-23.002(1).
 NO DATE AFFIXED TO SEAL/SIGNATURE. -
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS THE
 NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. 61G15-23.002(2)
 FAC, & FS 471.025.
 13. SHT P-01 DOMESTIC PUMPS SHALL BE
 LISTED. SUBMIT MANUF. SPECIFICATION
 SHEETS. SECTION 303.4
 14. SHT P-01 170 GAL. SYNCROFLO
 HYDROCUMULATOR TANK HAS NO PIPING TO IT.
 PLEASE INDICATE HOW THIS WILL BE PIPED.
 SECTION 104.2.1.
 15. SHTS P-02A & P-04B 2" EXPRESS DRAIN
 FOR FIRE SPRINKLER SYSTEM TO DRAIN TO
 THE SANT. SYSTEM. SECTION 701.4
 16. SHT P-02A INDICATE SANT. RISER
 NUMBER FOR LINE NEXT TO ST/10 RISER.
 SECTION 104.2.1.
 17. SHT P-02A LINES AT MATCH LINE ABOVE
 BUILDING SANT. DRAIN LINE (GAS, HOT
 WATER ECT.) NOT SHOWN AS CONTINUING ON
 SHT P-02B. PLEASE INDICATE WHERE THESE
 LINES CONTINUE TO RUN, LABEL AND
 IDENTIFY ALL LINES. SECTION 104.2.1.
 18. SHTS P-02A & P-02C 2-WAY CLEANOUTS
 ARE REQUIRED ON THE INLET AND OUTLET OF
 THE GREASE INTERCEPTOR. CITY STANDARD. -
 ALSO A 2-WAY CLEANOUT IS REQUIRED NEAR
 THE JUNCTION OF THE BUILDING DRAIN AND
 THE BUILDING SEWER. SECTION 708.3.
 19. SHT P-02C KITCHEN EQUIPMENT
 CONNECTION NOTES 1 & 4. THE AIR GAP
 SHALL BE TWICE THE DIAMETER OF THE
 EFFECTIVE OPENING OF THE INDIRECT WASTE
 PIPE. SECTION 802.2.1.
 20. SHT P-02C MORE INFORMATION IS
 REQUIRED ON THE "OPEN SITE DRAINS".
 PLEASE INDICATE WHAT TYPE OF FIXTURE
 THIS IS, AND WHAT IS THE PURPOSE FOR
 THIS FIXTURE. SECTION 104.2.1.
 21. SUBMIT A BUILDING DRAIN SANITARY
 RISER DIAGRAM IN ISOMETRIC FORM SHOWING
 ALL PIPE SIZES, CLEANOUTS, VENTS, RISER
 LOCATIONS, AND DRAINAGE FIXTURE UNITS AS
 THEY ACCUMULATE IN THE SYSTEM. SECTIONS
 104.2.1. & 140.3.1.1.
 22. SHT P-02B SANT. BRANCH LINE
 CONNECTING DOWNSTREAM OF RISER P/8.
 PLEASE INDICATE WHAT FIXTURES CONNECT TO
 THIS BRANCH LINE. SECTION 104.2.1.
 23. SHT P-07 WATER HEATER DETAIL. BOTTOM
 FED WATER HEATERS SHALL HAVE A VACUUM
 RELIEF VALVE INSTALLED. SECTION 504.2. -
 ONE WATER HEATER DETAIL INDICATES (3
 REQUIRED) AND THE OTHER DETAIL INDICATES
 (6 REQUIRED). PLEASE CLARIFY. SECTION
 104.2.1.
 24. SHT P-08 ROOFTOP PIPING SUPPORT TO
 COMPLY WITH TABLE 308.5. - INDICATE HOW
 SUPPORT IS ATTACHED TO ROOF AND HOW THE
 SUPPORTS COMPLY WITH 140 MPH WIND LOADS.
 SECTION 104.2.1.
 25. SHT P-10 RISER P/3 DOES NOT REFLECT
 THE FLOOR PLAN AT 6TH FLOOR. SECTION
 104.2.1.
 RISERS P/7 & P7A DOES NOT REFLECT THE
 FLOOR PLAN 6TH FLOOR. SECTION 104.2.1.
 26. SHT P-11 BLDG DRAIN DOES NOT REFLECT
 THE FLOOR PLAN. CLEANOUT IS NOT SHOWN ON
 THE FLOOR PLAN UPSTREAM OF BRANCH LINE
 TO RISER P/2. SECTION 104.2.1.
 26. SHT P-11 RISER P/4 DOES NOT REFLECT
 THE FLOOR PLAN AT 6TH FLOOR. SECTION
 104.2.1.
 27. SHT P-11 PARTIAL SANITARY RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
 F2 ON FLOOR PLAN SHOWN AS F1 ON RISER
 DIAGRAM. PLEASE CORRELATE RISER WITH
 FLOOR PLAN. SECTION 104.2.1.
 28. SHT P-13 RISER DOES NOT REFLECT
 FLOOR PLAN. FLOOR DRAINS UPSTREAM OF
 P/14 SHOWN AS 3" ON FLOOR PLAN AND 4"
 ON THE RISER DIAGRAM. SECTION 104.2.1.
 ALSO PIPE SHALL NOT REDUCE IN THE
 DIRECTION OF FLOW. SECTION 704.2
 29. SHT P-14 THE FOLLOWING CORRECTIONS
 ON THE FOLLOWING RISER REQUIRED:
 A. ST/3 5" MINIMUM ON HORIZONTAL
 B. ST/9 4" MINIMUM ON HORIZONTAL
 C. ST/11 4" MINIMUM ON HORIZONTAL
 D. ST/13 4" MINIMUM ON HORIZONTAL
 E. ST/15 4" MINIMUM ON HORIZONTAL
 30. THE FOLLOWING INFORMATION IS RQUIRED
 FOR GAS PERMIT:
 A. SHT P-08 SUBMIT AN ISOMETRIC DRAWING
 THAT CLEARLY SHOWS ALL CUT SECTIONS OF
 PIPE AND CORRESPONDING LENGTHS PER
 FBC-2001 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304. - THIS IS FOR THE
 WATER BOOSTER.
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. -
 DELEVERY PRESSURE IS USUALLY 11 TO 14
 INCHES OF WATER COLUMN OR 56 INCHES OF
 WATER COLUMN, AND PLANS SHOW 7". PLEASE
 CHECK WITH GAS PROVIDER AND VERIFY THE
 DELIVERY PRESSURE.
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 31. ARCHITECTURAL SHEETS, THERE ARE SOME
 SHEETS THAT ARE NOT SEALED, AND MOST
 SHEETS THE SEAL DOES NOT SHOW THE
 INFORMATION REQUIRED BY FAC 61G1-16.002
 AND FS 481.221 - THE TITLE BLOCK IS
 MISSING THE FOLLOWING INFORMATION:
 (2) FIRM LICENSE NUMBER
 SEE FAC 61G1-16.004 & FS 481.2055
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 9 Status P Date 2008-05-07 Cont ID  
Sent By lfranco Date 2008-05-07 Time 17:53 Rev Time 0.00
Received By lfranco Date 2008-05-07 Time 17:52 Sent To  
Notes
2008-05-07 17:55:56PLANNING AND ZONING: **** PASSED WITH THE PROVISO THAT
 THE MINOR AMENDMENT NOTED ON COMM. #2 IS APPROVED BY
 THE PLANNING AND ZONING DEPT. PRIOR TO FINAL
 CERTIFICATE OF OCCUPANCY ("CO").****
  
 NOTE: THE PASSED STATUS IS ONLY FOR THE GENERATOR
 ENCLOSURE.
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 THE FOLLOWING COMMENTS ARE TO BE ADDRESSED IN THE MINOR
 AMENDMENT AS WELL AS THE FINAL PERMIT.
  
 2. THIS PERMIT IS PART OF AN APPLICATION UNDER REVIEW
 FOR A MINOR AMENDMENT (PB1402F) TO THE COURTNEY LAKES
 RESIDENTIAL PLANNED DEVELOPMENT (RPD), HAWTHORN SUITES
 HOTEL.SIGN-OFF FROM THE PLANNING AND ZONING DEPT. FOR
 THE FINAL CO. IS CONTINGENT UPON THE APPROVAL OF THE
 MINOR AMENDMENT.THE DRAWINGS SHALL REFLECT ALL
 REVISIONS PERTAINING TO LANDSCAPING, RE-LOCATION OF THE
 COMPACT SPACES, SCREENING OF THE GENERATOR AND
 MECHANICAL EQUIPMENT ON ROOF-TOP, INCLUDING DETAILS.
 PROVIDE ALL SHEETS INCLUDING, BUT NOT LIMITED TO MSP 1
 AND 2, PD/SHEET C1, FH/SHEET C2 AND LANDSCAPING SHEETS
 (LA-1 AND LA-2) THAT ARE PART OF PERMIT NUMBER.
 05041760 - "RE-SUBMITTAL TO GO WITH ENGINEERING
 DRAWINGS" (RECEIVED ON APRIL 4, 2008) UNDER COMMENTS
 COVER FORM (THE WEITZ CO.).
 *** NOTE: ADDRESS ALL LANDSCAPING COMMENTS FROM ROBERT
 KUSSNER.
  
 3.THE BOLLARD(S) NEED TO BE RELOCATED/RECONFIGURED
 OUT OF THE PARKING SPACE LOCATED NEXT TO THE LARGE
 GENERATOR.
  
 4.LANDSCAPING PLANS - LABEL COMPACT SPACES ON
 LANDSCAPE PLANS AS NOTED ON SITE PLANS (SHEETS MSP1 AND
 MSP2).
  
 5.SHEET MSP2 OF 2 - LOCATION OF HANDICAP SYMBOL'S
 LOWER-END SHALL BE TWO (2) FEET FROM THE PARKING STRIPE
 DETAIL INSTEAD OF FOUR (4) FEET SIX (6) INCHES.
  
 6.PROVIDE AN ENLARGED DETAIL OF THE HOTEL SITE PLAN
 AREA FOR THE DIMENSIONS, ETC. TO BE LEGIBLE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE
 NUMBER BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
  
 TEL: (561) 822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 8 Status P Date 2008-04-07 Cont ID  
Sent By lfranco Date 2008-04-07 Time 18:12 Rev Time 0.00
Received By lfranco Date 2008-04-07 Time 18:11 Sent To  
Notes
2008-04-07 19:05:44PLANNING AND ZONING: **** PASSED WITH THE PROVISO THAT
 THE MINOR AMENDMENT NOTED ON COMM. #2 IS APPROVED BY
 THE PLANNING AND ZONING DEPT. PRIOR TO FINAL
 CERTIFICATE OF OCCUPANCY ("CO").****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. THIS PERMIT IS PART OF AN APPLICATION UNDER REVIEW
 FOR A MINOR AMENDMENT (PB1402F) TO THE COURTNEY LAKES
 RESIDENTIAL PLANNED DEVELOPMENT (RPD), HAWTHORN SUITES
 HOTEL.SIGN-OFF FROM THE PLANNING AND ZONING DEPT. FOR
 THE FINAL CO. IS CONTINGENT UPON THE APPROVAL OF THE
 MINOR AMENDMENT.THE DRAWINGS SHALL REFLECT ALL
 REVISIONS PERTAINING TO LANDSCAPING, RE-LOCATION OF THE
 COMPACT SPACES, SCREENING OF THE GENERATOR AND
 MECHANICAL EQUIPMENT ON ROOF-TOP, INCLUDING DETAILS.
 PROVIDE ALL SHEETS INCLUDING, BUT NOT LIMITED TO MSP 1
 AND 2, PD/SHEET C1, FH/SHEET C2 AND LANDSCAPING SHEETS
 (LA-1 AND LA-2) THAT ARE PART OF PERMIT NUMBER.
 05041760 - "RE-SUBMITTAL TO GO WITH ENGINEERING
 DRAWINGS" (RECEIVED ON APRIL 4, 2008) UNDER COMMENTS
 COVER FORM (THE WEITZ CO.).
 *** NOTE: ADDRESS ALL LANDSCAPING COMMENTS FROM ROBERT
 KUSSNER.
  
 3.THE BOLLARD(S) NEED TO BE RELOCATED/RECONFIGURED
 OUT OF THE PARKING SPACE LOCATED NEXT TO THE LARGE
 GENERATOR.
  
 4.LANDSCAPING PLANS - LABEL COMPACT SPACES ON
 LANDSCAPE PLANS AS NOTED ON SITE PLANS (SHEETS MSP1 AND
 MSP2).
  
 5.SHEET MSP2 OF 2 - LOCATION OF HANDICAP SYMBOL'S
 LOWER-END SHALL BE TWO (2) FEET FROM THE PARKING STRIPE
 DETAIL INSTEAD OF FOUR (4) FEET SIX (6) INCHES.
  
 6.PROVIDE AN ENLARGED DETAIL OF THE HOTEL SITE PLAN
 AREA FOR THE DIMENSIONS, ETC. TO BE LEGIBLE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE
 NUMBER BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
  
 TEL: (561) 822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 7 Status P Date 2006-08-04 Cont ID  
Sent By lfranco Date 2006-08-04 Time 16:57 Rev Time 0.00
Received By lfranco Date 2006-08-04 Time 16:57 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 6 Status F Date 2006-07-25 Cont ID  
Sent By lfranco Date 2006-07-25 Time 19:18 Rev Time 0.00
Received By lfranco Date 2006-07-25 Time 18:52 Sent To I
Notes
2006-07-25 00:00:00PLANNING AND ZONING: FAILED
  
 1. PROVIDE ALL RESPONSES TO COMMENTS IN
 WRITING.
  
 2. PLANS NEED TO HAVE ORIGINAL SIGNED
 AND SEALED STAMP (I.E. SITE PLAN,
 LANDSCAPE PLANS, AND OTHER PERTINENT
 PLANS)
  
 3.PURSUANT TO 94-444- DUMPSTER SHOWN
 ON SITE PLAN DOES NOT COMPLY WITH
 DIMENSIONAL REQUIREMENTS AND
 SPECIFICATION.SEE FIGURE XIV-3.I
 HAVE INCLUDED A DETAIL COPY FOR YOUR
 USE.THE DUMPSTER SHOWN ON SITE PLAN
 SHOWS TO BE A WIDTH OF ONLY 12 FEET.
  
 4.IN ADDITION, YOUR DUMPSTER DETAIL ON
 MSP PLANS, SHEET 2 OF 2 INCLUDES A
 RECYCLE BIN, THIS IS NOT SHOWN ON THE
 SITE PLAN. REVISE TO CORRELATE ON BOTH
 DETAILS SHEET, SITE PLAN, LANDSCAPE PLAN
 AND ALL OTHER PERTINENT DOCUMENTATION.
 REDUCTION IN LANDSCAPE STRIP WILL NOT BE
 ALLOWED TO ACCOMODATE RECYCLE BIN IF
 CALCULATIONS FOR LANDSCAPING WERE
 INCLUDED IN THIS AREA. THERE ARE 2
 DUMPSTER DETAILS SHOWN. ONE HAS A
 RECYCLE BIN OF 5'-8" THE OTHER 8'-10" IN
 WIDTH.PLEASE CLARIFY, AS ONLY ONE
 DUMPSTER AREA IS SHOWN ON SITE PLAN.
  
 5.PURSUANT TO SECTION 94-485 -STALL
 PAINTING DETAIL ON MSP PLANS, SHEET 2 OF
 2 DOES NOT COMPLY.A COPY OF THE
 STRIPPING DETAIL IS ATTACHED FOR
 REFERENCE. THE INTERIOR WIDTH NEED TO BE
 12" AND THE WHITE LINES ON THE OUTER
 AREA NEED TO BE 4".PLEASE REFERENCE ON
 NOTES THAT THE PARKING DETAILS WILL
 COMPLY WITH CITY OF WEST PALM BEACH CODE
 REQUIREMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 LINDA MIA FRANCO @ (561) 822-1435.
  
 THANK YOU.

Review Stop Z ZONING
Rev No 5 Status F Date 2006-07-20 Cont ID  
Sent By lfranco Date 2006-07-20 Time 19:28 Rev Time 0.00
Received By lfranco Date 2006-07-20 Time 19:28 Sent To I
Notes
2006-07-20 00:00:00PLANNING AND ZONING:
 FAILED ON 7-20-06-NO SITE PLAN WAS
 SUBMITTED.
  
 FAILED ON 5-17-06
  
 COMMENTS FROM 4-4-06 ARE STILL
 OUTSTANDING.
  
 1. THE SITE PLANS ON ALL SUBMITTED
 DOCUMENTATION NEED TO MATCH THE MINOR
 AMENDMENT CASE PB1402C APPROVED
 (4-03-06) SITE PLANS. (I.E. ALL THE
 ELECTRICAL PLANS, MILLER LEGG PLANS USED
 THE OLD, NON CONFORMING SITE PLAN AS
 THEIR FOOTPRINT).
  
  
 2.A COPY OF THE ORIGINAL APPROVED
 PLANS HAS BEEN SUBMITTED FROM THE
 PLANNING DEPARTMENT INTO YOUR PACKET,
 FOR YOUR USE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 LINDA MIA FRANCO @ (561) 822-1435.
  
 THANK YOU,
  
 LINDA MIA FRANCO

Review Stop Z ZONING
Rev No 4 Status F Date 2006-05-18 Cont ID  
Sent By lfranco Date 2006-05-18 Time 19:07 Rev Time 0.00
Received By lfranco Date 2006-05-18 Time 19:07 Sent To I
Notes
2006-05-18 00:00:00PLANNING AND ZONING: FAILED ON 5-17-06
  
 COMMENTS FROM 4-4-06 ARE STILL
 OUTSTANDING.
  
 1. THE SITE PLANS ON ALL SUBMITTED
 DOCUMENTATION NEED TO MATCH THE MINOR
 AMENDMENT CASE PB1402C APPROVED
 (4-03-06) SITE PLANS. (I.E. ALL THE
 ELECTRICAL PLANS, MILLER LEGG PLANS USED
 THE OLD, NON CONFORMING SITE PLAN AS
 THEIR FOOTPRINT).
  
  
 2.A COPY OF THE ORIGINAL APPROVED
 PLANS HAS BEEN SUBMITTED FROM THE
 PLANNING DEPARTMENT INTO YOUR PACKET,
 FOR YOUR USE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 LINDA MIA FRANCO @ (561) 822-1435.
  
 THANK YOU,
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 CITY OF WEST PALM BEACH

Review Stop Z ZONING
Rev No 3 Status F Date 2006-04-05 Cont ID  
Sent By lfranco Date 2006-04-04 Time 16:37 Rev Time 0.00
Received By lfranco Date 2006-04-04 Time 16:37 Sent To I
Notes
2006-04-05 00:00:00PLANNING AND ZONING: FAILED
  
 1. THE SITE PLANS ON ALL SUBMITTED
 DOCUMENTATION NEED TO MATCH THE MINOR
 AMENDMENT CASE PB1402C APPROVED
 (4-03-06) SITE PLANS. (I.E. ALL THE
 ELECTRICAL PLANS, MILLER LEGG PLANS USED
 THE OLD, NON CONFORMING SITE PLAN AS
 THEIR FOOTPRINT).
  
  
 2.A COPY OF THE ORIGINAL APPROVED
 PLANS HAS BEEN SUBMITTED FROM THE
 PLANNING DEPARTMENT INTO YOUR PACKET,
 FOR YOUR USE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 LINDA MIA FRANCO @ (561) 822-1435.
  
 THANK YOU,
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 CITY OF WEST PALM BEACH

Review Stop Z ZONING
Rev No 2 Status F Date 2006-01-06 Cont ID  
Sent By lfranco Date 2006-01-05 Time 18:27 Rev Time 0.00
Received By lfranco Date 2006-01-05 Time 16:38 Sent To  
Notes
2006-01-05 00:00:00FAILED:
  
 ZONING COMMENTS:
  
 1.PROVIDE RESPONSES TO COMMENTS IN
 WRITING AND INDICATE THE REVISIONS ON
 SITE PLAN.
  
 2.PURSUANT TO SECTION 94-485(O)PAGE
 CD 94:272 OF THE CODE,THE PROPOSED
 "COMPACT" SMALL CAR SPACE DOES NOT
 COMPLY WITH CODE REQUIREMENTS.FOR
 EXAMPLE:
 A. THE PROPOSED COMPACT SPACES, EXCEED
 THE 30 PERCENT ALLOWED;AND,
 B.SMALL AND STANDARD PARKING SPACES
 SHALL BE DISTRIBUTED EQUALLY THROUGHOUT
 A PARKING LOT, AND THE CITY ENGINEER
 SHALL REVIEW THE DESIGN OF ALL PROPOSED
 PARKING FACILITIES TO ENSURE THAT THE
 INTENT OF THIS SECTION IS SATISFIED.
 CONTACT THE CITY ENGINEER TO COORDINATE
 AND PROVIDE A LETTER FROM THEM STATING
 THAT THIS REQUIREMENT HAS BEEN
 SATISFIED.
  
 3.PURSUANT TO SECTION 94-485(O)PAGE
 CD 94:273 OF THE CODE, THE AMOUNT OF
 DISABLED PARKING SPACES PROPOSED DOES
 NOT COMPLY.THERE ARE FIVE (5) REQUIRED
 PARKING SPACES THAT NEED TO BE PROVIDED.
 IN ADDITION, THE LOCATION OF THE SPACES
 SHALL BE LOCATED SO THAT USERS ARE NOT
 COMPELLED TO WALK OR OTHERWISE MOVE
 BEHIND PARKED VEHICLES.WHY ARE THESE
 SPACES LOCATED ACROSS DRIVE AISLES
 INSTEAD OF CLOSE PROXIMITY TO THE
 BUILDING ACCESS? REVISE ACCORDINGLY.
  
 4.THE TYPICAL PARKING DETAIL DOES NOT
 COMPLY WITH THE STALL PAINTING DETAIL IN
 SECTION 94-485 (PAGE CD94:272).THE
 BOTTOM STRIPPING DETAIL NEEDS TO BE
 SQUARED-OFF.IN ADDITION, THERE NEEDS
 TO BE TWO (2)FEET CLEARANCE FOR VEHICLE
 OVERHANG, REFER TO DETAIL IN SECTION
 94-443 (PAGE CD94:253).
  
 5. PURSUANT TO SECTION 94-486(O) PAGE
 CD 94:274 OF THE CODE,THE SITE PLAN
 DOES NOT SHOW OR ALLOCATE THE REQUIRED
 BICYCLE PARKING SPACES.
  
 6.PURSUANT TO SECTION 94-443(E)PAGE CD
 94:254 OF THE CODE, AT LEAST 30 PERCENT
 OF THE LINEAR FEET AROUND THE EXTERIOR
 OF ALL COMMERCIAL STRUCTURES SHALL BE
 PLANTED WITH TREES, SHRUBS OR HEDGES;
 THE PROPOSED SITE PLAN DOES NOT COMPLY
 WITH THE REQUIRED FOUNDATION PLANTING.
  
 7.PROVIDE CALCULATIONS OF OPEN SPACE
 AND LANDSCAPE PERCENTAGE FOR THIS
 (HOTEL) SITE.
  
 8.PROVIDE THE SITE DATA ON PLANS (I.E.
 BUILDING COVERAGE, SETBACKS, PARKING
 REQUIREMENTS, DENSITY CALCULATIONS.
 SITE PLAN NEEDS TO MATCH THE APPROVED
 SITE PLAN OF RECORD.
  
 9. IDENTIFY THE SQUARE FOOTAGE OF THE
 DINING AREAS, KITCHENS, BARS, LOUNGES
 AND MEETING ROOMS. PROVIDE INFORMATION
 ON SITE DATA TABLE.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-06-15 Cont ID  
Sent By jlong Date 2005-06-15 Time 09:34 Rev Time 0.00
Received By jlong Date 2005-06-15 Time 09:34 Sent To  
Notes
2005-06-15 00:00:001. A MINOR PLANNED DEVELOPMENT AMENDMENT
 IS REQUIRED TO APPROVE THE ALTERATION
 AND RELOCATION OF PARKING, DUMPSTER,
 POOL AND LANDSCAPING.
  
 2. A COPY OF THE RECORDED PLAT WITH THE
 FOLLOWING CONDITIONS IS REQUIRED:
 A. TRACT C, LAKE, AND TRACT D, ROAD,
 MUST REMAIN IN COMMON OWNERSHIP OF THE
 OWNERS OF TRACT A, COURTNEY LAKES, AND
 TRACT B, HOTEL.
 B. PERPETUAL EASEMENTS FOR INGRESS,
 EGRESS, DRAINAGE AND COMMON AREA
 MAINTENANCE MUST EXIST BETWEEN ALL
 PARCELS.
 C. A PUBLIC ACCESS EASEMENT FOR THE LAKE
 PATH IS REQUIRED.
  
 3. A SITE DATA SHEET IS REQUIRED, THE
 SHEET MUST IDENTIFY THE SQUARE FOOTAGE
 OF THE DINING AREAS, KITCHENS, BARS,
 LOUNGES AND MEETING ROOMS.
  
 4. NONE OF THE HOTEL'S AMENITIES MAY BE
 ADVERTISED TO THE PUBLIC.
  
 5.CAN NOT PLACE A TRANSFORMER IN A
 REQUIRED LANDSCAPE ISLAND.
  
 6. MAY NOT HAVE MORE THAN 10 PARKING
 SPACES IN ONE ROW.