Plan Review Details - Permit 05041551
| Plan Review Stops For Permit 05041551 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-05-17 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-05-17 |
Time |
14:18 |
Rev Time |
2.00 |
| Received By |
alange |
Date |
2005-05-17 |
Time |
12:43 |
Sent To |
|
|
| Notes |
| 2005-05-17 00:00:00 | DENIED | | | | | | 1.SUBMIT PRODUCT APPROVALS WITH | | | QUALITY ASSURANCE FOR EXTERIOR DOOR "E" | | | AND STORE FRONT "D".ALL PRODUCT | | | APPROVALS SUBMITTED REQUIRE THE | | | FOLLOWING TO BE ATTACHED. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | ANY QUESTIONS CALL ME. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2005-05-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-05-03 |
Time |
15:54 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2005-05-03 |
Time |
15:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2005-05-05 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-05-05 |
Time |
15:36 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-05-05 |
Time |
15:32 |
Sent To |
|
|
| Notes |
| 2005-05-05 00:00:00 | 1) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR THE FIRE ALARM AND FIRE | | | SPRINKLER REMODELS. | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 835-2910 OR 805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-05-02 |
Time |
16:18 |
Sent To |
|
|
| Notes |
| 2005-05-02 00:00:00 | TO "COMM" BD#6 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-06-01 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2005-06-01 |
Time |
18:54 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2005-06-01 |
Time |
18:16 |
Sent To |
|
|
| Notes |
| 2005-06-01 00:00:00 | PLAN DENIED | | | 1) REFER TO SECTION 601.4 BALANCED | | | RETURN AIR FBC(M) | | | 2) PLAN SHOWS ROUND DUCT.NOTES ON PAGE | | | M-2 CALL FOR 1 1/2 DUCT BOARD | | | 3) MECHANICAL PLANS ON PAGE M-1 SAY OPEN | | | STRUCTURE.PAGE A.2.0 SHOW A CEILING. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-06-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-06-01 |
Time |
15:55 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2005-06-01 |
Time |
15:55 |
Sent To |
|
|
| Notes |
| 2005-06-01 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1. SHT A-1.1 CLEAR FLOOR SPACE FOR | | | COFFEE AREA SINK SHALL EXTEND A MAXIMUM | | | OF 19" UNDERNEATH THE COUNTER. SECTION | | | 11-4.24.5. THE SINK SHALL BE CENTERED ON | | | THE 30" WIDTH OF THE CLEAR FLOOR SPACE. | | | SEE FIG. 32. | | | 2. SHT A-3.0 SHOW COMPLIANCE WITH THE | | | FOLLOWING: | | | A. HEIGHTS & CLEARANCES 11-4.19.2 | | | B. EXPOSED PIPES & SURFACES 11-4.19.4 | | | C. FAUCETS 11-4.19.5 | | | 3. SHT P-1 DOMESTIC WATER ISOMETRIC, THE | | | WATER HAMMER ARRESTORS SHALL BE LOCATED | | | NEAR THE FIXTURE IN AN "EFFECTIVE RANGE" | | | NOT IN THE CEILING AS SHOWN. PDI-WH 201 | | | AND MANUF. INSTALL. INSTRUCTIONS. | | | 4. A DRINKING FOUNTAIN IS REQUIRED PER | | | TABLE 403.1. IF A DRINKING FOUNTAIN IS | | | PROVIDED IN THE COMMON AREA, PLEASE | | | INDICATE THE LOCATION ON THE PLANS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
|