Plan Review Details - Permit 05041551
Plan Review Stops For Permit 05041551
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-17 Cont ID  
Sent By alange Date 2005-05-17 Time 14:18 Rev Time 2.00
Received By alange Date 2005-05-17 Time 12:43 Sent To  
Notes
2005-05-17 00:00:00DENIED
  
 1.SUBMIT PRODUCT APPROVALS WITH
 QUALITY ASSURANCE FOR EXTERIOR DOOR "E"
 AND STORE FRONT "D".ALL PRODUCT
 APPROVALS SUBMITTED REQUIRE THE
 FOLLOWING TO BE ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-05-03 Cont ID  
Sent By dpalmer Date 2005-05-03 Time 15:54 Rev Time 0.50
Received By dpalmer Date 2005-05-03 Time 15:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-05-05 Cont ID  
Sent By mwennerg Date 2005-05-05 Time 15:36 Rev Time 0.00
Received By mwennerg Date 2005-05-05 Time 15:32 Sent To  
Notes
2005-05-05 00:00:001) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR THE FIRE ALARM AND FIRE
 SPRINKLER REMODELS.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910 OR 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2005-05-02 Time 16:18 Sent To  
Notes
2005-05-02 00:00:00TO "COMM" BD#6

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-06-01 Cont ID  
Sent By hmoser Date 2005-06-01 Time 18:54 Rev Time 0.00
Received By hmoser Date 2005-06-01 Time 18:16 Sent To  
Notes
2005-06-01 00:00:00PLAN DENIED
 1) REFER TO SECTION 601.4 BALANCED
 RETURN AIR FBC(M)
 2) PLAN SHOWS ROUND DUCT.NOTES ON PAGE
 M-2 CALL FOR 1 1/2 DUCT BOARD
 3) MECHANICAL PLANS ON PAGE M-1 SAY OPEN
 STRUCTURE.PAGE A.2.0 SHOW A CEILING.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-06-01 Cont ID  
Sent By kstevens Date 2005-06-01 Time 15:55 Rev Time 1.00
Received By kstevens Date 2005-06-01 Time 15:55 Sent To  
Notes
2005-06-01 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1. SHT A-1.1 CLEAR FLOOR SPACE FOR
 COFFEE AREA SINK SHALL EXTEND A MAXIMUM
 OF 19" UNDERNEATH THE COUNTER. SECTION
 11-4.24.5. THE SINK SHALL BE CENTERED ON
 THE 30" WIDTH OF THE CLEAR FLOOR SPACE.
 SEE FIG. 32.
 2. SHT A-3.0 SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. HEIGHTS & CLEARANCES 11-4.19.2
 B. EXPOSED PIPES & SURFACES 11-4.19.4
 C. FAUCETS 11-4.19.5
 3. SHT P-1 DOMESTIC WATER ISOMETRIC, THE
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT IN THE CEILING AS SHOWN. PDI-WH 201
 AND MANUF. INSTALL. INSTRUCTIONS.
 4. A DRINKING FOUNTAIN IS REQUIRED PER
 TABLE 403.1. IF A DRINKING FOUNTAIN IS
 PROVIDED IN THE COMMON AREA, PLEASE
 INDICATE THE LOCATION ON THE PLANS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]