Plan Review Details - Permit 05041534
Plan Review Stops For Permit 05041534
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-18 Cont ID  
Sent By adarroug Date 2005-05-18 Time 11:15 Rev Time 0.00
Received By adarroug Date 2005-05-18 Time 11:15 Sent To M
Notes
2005-05-18 00:00:00TO "PKRAUSS" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-04-25 Cont ID  
Sent By adarroug Date 2005-04-25 Time 15:47 Rev Time 0.00
Received By adarroug Date 2005-04-25 Time 15:47 Sent To M
Notes
2005-04-25 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-05-30 Cont ID  
Sent By pkrauss Date 2005-05-30 Time 16:05 Rev Time 0.30
Received By pkrauss Date 2005-05-30 Time 16:04 Sent To  
Notes
2005-05-30 00:00:00DENIED:
 COMMENT #2 BY HAROLD MOSER WAS NOT
 ADDRESSED.INDICATE LOCATION OF
 CONDENSORS AND LINE SIZE OF REFRIGERANT
 AND CONDENSATE LINES.SHOW TERMINATION
 OF THE CONDENSATE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-05-03 Cont ID  
Sent By hmoser Date 2005-05-03 Time   Rev Time 0.00
Received By hmoser Date 2005-05-03 Time 13:06 Sent To  
Notes
2005-05-03 00:00:00PLAN DENIED
 1) PLEASE SHOW GRILL SIZES ON PLAN.
 2) PLEASE SHOW LOCATION OF CONDENSORS
 AND CONDENSATE LINES.
 3) PLANS MUST HAVE A ARCHITECTS SEAL,OR
 REMOVE ARCHITECTS NAME FROM THE PLANS
 4) NEED BATHROOM EXHAUST IN BATHROOM PER
 TABLE 403.3 FBC.(M)
 PLAN REVIEW BY HAROLD MOSER 561-805-6732