| Notes |
| 2005-09-06 00:00:00 | *** PROVISO *** | | | RETURN AIR TRANSFER DUCTS MUST BE 1 1/2 | | | TIMES LARGER THAN SUPPLY AIR. PER. 2001 | | | FBC/M 601.4 EXECPTION: 1 . | | | EX. BEDROOM 2&3 8" SUPPLY AIR DUCT, | | | RETURN AIR DUCT NEEDS TO BE 10". OFFICE | | | 6" SUPPLY AIR DUCT, RETURN AIR DUCT | | | NEEDS TO BE 10". | | | | | | RETURN AIR DUCTS ON 2ND. FLOOR AT 24X12 | | | RAG IN HALLWAY ARE DIFFICULT TO SEE ON | | | PLANS (IF TRANSFER DUCTS). | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. |
|
|
|