Plan Review Details - Permit 05041364
Plan Review Stops For Permit 05041364
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2006-06-24 Cont ID  
Sent By mjacobs Date 2006-06-24 Time 08:36 Rev Time 0.00
Received By mjacobs Date 2006-06-24 Time 08:27 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2006-06-16 Cont ID  
Sent By mjacobs Date 2006-06-16 Time 10:31 Rev Time 0.00
Received By mjacobs Date 2006-06-16 Time 06:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2006-05-01 Cont ID  
Sent By mjacobs Date 2006-05-01 Time 16:39 Rev Time 0.00
Received By mjacobs Date 2006-05-01 Time 12:06 Sent To PC
Notes
2006-05-01 00:00:001) FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 2) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3) PLANS WHICH WERE BROUGHT IN UNDER THE
 2001 FBC CANNOT BE CHANGE TO 2004 CODE
 DURING THE REVIEW PROCESS. SEE SHEET 2
 OF 6. WHICH REFERS TO THE 2004 CODE.SO
 PLEASE CHANGE INFORMATION TO REFLECT THE
 2001 CODE.
  
 4) THE PRODUCT APPROVAL FOR THE MODIFIED
 ROOF INDICATES A WOOD INSULATED SYSTEM
 HOWEVER, THE INFORMATION ON THE DRAWINGS
 ABOUT THE ROOF (SHEET 2), DOES NOT
 INDICATE ANY INSULATION. THE PRODUCT
 APPROVAL HAS TO MATCH WHAT IS ON THE
 DRAWINGS. READ THE APPROVED ASSEMBLY TO
 BE SURE THAT IS THE TYPE WHICH WILL BE
 INSTALLED.
  
 5 ) 713.13(2) F.S.THE NOTICE OF
 COMMENCEMENT MUST BE RE-RECORDED BECAUSE
 THE DESCRIBED IMPROVEMENT OR
 CONSTRUCTION DID NOT COMMENCE WITHIN 90
 DAYS OF RECORDING.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-01-27 Cont ID  
Sent By mjacobs Date 2006-01-27 Time 09:02 Rev Time 2.00
Received By mjacobs Date 2006-01-26 Time 14:10 Sent To PC
Notes
2006-01-26 00:00:001) PLEASE SEE NOTES FROM PREVIOUS REVIEW
 WHICH WERE NOT ADDRESSED.
  
 2) SOME OF THE PRODUCT APPROVALS ARE
 MISSING THE NOA REPORTS.NOTE: THE
 PRODUCT APPROVALS ARE INCOMPLETE IF THE
 INSTALLATION INSTRUCTIONS ARE MISSING
 FROM THE REPORTS. ALSO SOME PRODUCT WERE
 NOT APPROVED WHEN THEY WERE SUBMITTED,SO
 CHECK THE WEB-SITE FOR THE APPROVED
 SHEETS.EG FL42-R2 WHICH WAS STILL
 PENDING AT THE TIME OF SUBMITTAL.
 HOWEVER, THIS PRODUCT HAS SINCE BEEN
 APPROVED WHICH MEANS THAT THE APPROVED
 SHEETS SHOULD REPLACE THOSE PENDING
 SHEETS. CHECK ALL PRODUCT APPROVALS AND
 MAKE SURE THEY HAVE APPROVED AND UPDATED
 SHEETS,ALSO THE INSTALLATION REPORTS.
  
 3) CHOOSE THE SYSTEM FROM THE PRODUCT
 APPROVAL FOR THE MODIFIED ROOF. SEE
 PAGES 6-32 AND INDICATE WHICH SYSTEM
 WILL BE INSTALLED.
  
 4) AGAIN SEE NOTES FROM PREVIOUS REVIEW.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-12-20 Cont ID  
Sent By mjacobs Date 2005-12-20 Time 08:50 Rev Time 2.50
Received By mjacobs Date 2005-12-20 Time 06:09 Sent To PC
Notes
2005-12-20 00:00:00 
 1) IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE
 ISSUED.PLEASE CALL (561) 233-5025 FOR
 MORE INFORMATION.
  
 2) FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
 PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 2001 FLORIDA ENERGY
 EFFICIENTCY CODE FOR BUILDING CONSTRUC-
 TION.
  
 3) 471.023 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING
 ENGINEERING SERVICES, SHALL INCLUDE THE
 CERTIFICATE OF AUTHORIZATION NUMBER.
 ADD THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
 4) FBC 1203.1 EVERY HABITABLE ROOM OF
 BUILDINGS HEREAFTER ERECTED SHALL HAVE
 ONE OR MORE WINDOWS, UNLESS OTHERWISE
 SPECIFICALLY PROVIDED HEREIN, TO AFFORD
 ADEQUATE LIGHT AND VENTILATION. SEE
 BEDROOM NEXT TO NEW OFFICE.PG 1 OF 6.
  
 5) 2001 FL BLD CODE, 1005.4:
 PROVIDE EMERGENCY EGRESS WINDOWS IN
 SLEEPING ROOMS WITH A MINIMUM NET CLEAR
 OPENING HEIGTH OF 24" AND NET CLEAR
 OPENING WIDTH OF 20" AND A NET CLEAR
 OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR
 OPENINGS ARE PERMITTED TO HAVE A NET
 CLEAR OPENING OF 5.0 SQ. FT. SILL HEIGTH
 SHALL NOT BE MORE THAN 44 " ABOVE THE
 FINISH FLOOR.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL (561) 805-6726
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-08-17 Cont ID  
Sent By mjacobs Date 2005-08-17 Time 09:51 Rev Time 1.75
Received By mjacobs Date 2005-08-17 Time 06:53 Sent To PC
Notes
2005-08-17 00:00:001) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2) SUBMIT EXISTING FLOOR PLAN SHOWING
 EGRESS OPENINGS NEXT TO NEW
 CONSTRUCTION. ALSO PLEASE SHOW ACCESS
 FROM EXISTING STRUCTURE TO NEEW ENCLOSE
 AREA.
  
 3) PLEASE LOOK CLOSELY AT PAGE 1 OF 6 OF
 THE TWO SETS OF PLANS AND SEE THAT ONE
 OF THE DRAWINGS IS DIFFERENT FROM THE
 OTHER. THE PLANS SHOULD BE IDENTICAL FOR
 RECORDING PURPOSES.
  
 4) ONE OF THE PRODUCT APPROVAL ISFOR A
 8' DOOR. WHERE WILL THIS DOOR BE USED?
 PLEASE INDICATE ON THE PLANS THE SIZE
 AND LOCATION OF EACH DOOR.
  
 5) WHERE WILL THE AWNING WINDOW BE
 INSTALLED? PLEASE INDICATE ON PLANS.
  
 6) EACH PRODUCT APPROVAL NEEDS A STATE
 COVER SHEET OR LOCAL PRODUCT APPROVAL. I
 PUT A FEW COVER SHEETS IN THE PACKAGE
 PLEASE MAKE SURE THAT EACH PRODUCT
 APPROVAL HAS IT'S OWN COVER SHEET WHEN
 RESUBMITTING.
  
 7) FBC 13-103.1.2BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHITECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
  
 BUILDING PLAN REVIEW
 MYRON JACOBS
 TEL: (561)805-6726
 FAX: (561)659-8026
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-17 Cont ID  
Sent By mjacobs Date 2005-05-17 Time 09:01 Rev Time 2.50
Received By mjacobs Date 2005-05-17 Time 06:45 Sent To PC
Notes
2005-05-17 00:00:005/17/05
  
 1) 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2) IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 3) FBC 13-103.1.2BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHITECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 4) SUBMIT EXISTING FLOOR PLAN SHOWING
 EGRESS OPENINGS NEXT TO NEW
 CONSTRUCTION. ALSO PLEASE SHOW ACCESS
 FROM EXISTING STRUCTURE TO NEW ENCLOSE
 AREA.
  
 5) THE TITLE BLOCK IS MISSING FROM SHEET
 6 OF 6.
  
 6) PRODUCT APPROVALS ARE MISSING TEST
 REPORTS. ALSO PLEASE SELECT THE PRODUCT
 TO BE USED WITHEACH REPORT. YOU NEED
 MORE THAN THE COVER SHEET.
 PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 BUILDING PLAN REVIEW
 MYRON JACOBS
 TEL: (561)805-6726
 FAX: (561)659-8026
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-06-16 Cont ID  
Sent By btrobaug Date 2006-06-16 Time 09:44 Rev Time 0.50
Received By btrobaug Date 2006-06-16 Time 09:43 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-04-27 Cont ID  
Sent By btrobaug Date 2006-04-27 Time 14:27 Rev Time 0.33
Received By btrobaug Date 2006-04-27 Time 14:20 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-01-23 Cont ID  
Sent By btrobaug Date 2006-01-23 Time 15:06 Rev Time 0.50
Received By btrobaug Date 2006-01-23 Time 14:17 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-12-16 Cont ID  
Sent By btrobaug Date 2005-12-16 Time 07:37 Rev Time 0.50
Received By btrobaug Date 2005-12-16 Time 07:27 Sent To B
Notes
2005-12-16 00:00:00 
 THE ENGINEER MUST COMPLY WITH 471 FS AND
 61G15-23.002 FAC. TITLE BLOCKS AND
 CERTIFICATE OF AUTHORIZATION REQUIRED,
 ALL SHEETS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-08-16 Cont ID  
Sent By btrobaug Date 2005-08-16 Time 12:29 Rev Time 0.33
Received By btrobaug Date 2005-08-16 Time 12:21 Sent To B
Notes
2005-08-16 00:00:00 
  
 THE DESIGNER MUST PRINT NAME AND SIGN
 PLANS THEY ARE RESPONSIBLE FOR.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 AS NOTED ON LAST REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-11 Cont ID  
Sent By btrobaug Date 2005-05-10 Time 18:21 Rev Time 0.50
Received By btrobaug Date 2005-05-11 Time 06:44 Sent To B
Notes
2005-05-11 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE HAND DRAWN CHANGES ON THE PLAN
 ARE NOT ACCEPTABLE FOR RETENTION OR JOB
 SITE REVIEWED PLAN PER 104.2.1.3 FBC.
  
 2} A RECEPTACLE MUST BE ADDED TO THE
 REAR OF THE BUILDING (IF NONE EXIST)PER
 210.52(E).
  
 3} THE ENGINEER MUST ATTACH A TITLE
 BLOCK TO THE PLANS PER 61G15-23.002.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-06-15 Cont ID  
Sent By adarroug Date 2006-06-15 Time 10:06 Rev Time 0.00
Received By adarroug Date 2006-06-15 Time 10:06 Sent To B
Notes
2006-06-15 00:00:00TO "LMARTINEZ' DESK

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-04-27 Cont ID  
Sent By adarroug Date 2006-04-27 Time 10:23 Rev Time 0.00
Received By adarroug Date 2006-04-27 Time 10:23 Sent To E
Notes
2006-04-27 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-04-17 Cont ID  
Sent By adarroug Date 2006-04-17 Time 11:41 Rev Time 0.00
Received By adarroug Date 2006-04-17 Time 11:41 Sent To Z
Notes
2006-04-17 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-01-22 Cont ID  
Sent By adarroug Date 2006-01-22 Time 12:07 Rev Time 0.00
Received By adarroug Date 2006-01-22 Time 12:07 Sent To E
Notes
2006-01-22 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-12-10 Cont ID  
Sent By adarroug Date 2005-12-10 Time 10:08 Rev Time 0.00
Received By adarroug Date 2005-12-10 Time 10:08 Sent To E
Notes
2005-12-10 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-11-23 Cont ID  
Sent By adarroug Date 2005-11-23 Time 08:22 Rev Time 0.00
Received By adarroug Date 2005-11-23 Time 08:22 Sent To Z
Notes
2005-11-23 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-08-16 Cont ID  
Sent By mmclean Date 2005-08-19 Time 15:27 Rev Time 0.00
Received By adarroug Date 2005-08-16 Time 09:33 Sent To E
Notes
2005-08-16 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-08-09 Cont ID  
Sent By adarroug Date 2005-08-09 Time 10:14 Rev Time 0.00
Received By adarroug Date 2005-08-09 Time 10:14 Sent To Z
Notes
2005-08-09 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-05-10 Cont ID  
Sent By adarroug Date 2005-05-10 Time 14:41 Rev Time 0.00
Received By adarroug Date 2005-05-10 Time 14:41 Sent To E
Notes
2005-05-10 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-03 Cont ID  
Sent By adarroug Date 2005-05-03 Time 11:15 Rev Time 0.00
Received By adarroug Date 2005-05-03 Time 11:15 Sent To B
Notes
2005-05-03 00:00:00TO "MISC" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-04-20 Cont ID  
Sent By adarroug Date 2005-04-20 Time 16:32 Rev Time 0.00
Received By adarroug Date 2005-04-20 Time 16:31 Sent To Z
Notes
2005-04-20 00:00:00TO "Z" BOX

Review Stop Z ZONING
Rev No 4 Status N Date 2006-04-26 Cont ID  
Sent By mmclean Date 2006-04-26 Time 07:34 Rev Time 0.00
Received By mmclean Date 2006-04-26 Time 07:34 Sent To I
Notes
2006-04-26 00:00:00NO CHANGES TO LAST APPROVED REVIEW
 12/7/05

Review Stop Z ZONING
Rev No 3 Status P Date 2005-12-07 Cont ID  
Sent By mmclean Date 2005-12-07 Time 16:39 Rev Time 0.00
Received By mmclean Date 2005-12-07 Time 16:39 Sent To I
Notes
2005-12-07 00:00:00ADDITION MEETS THE FRONT & SIDE SETBACK
 AND INTERIOR ACCESS TO MAIN STRUCTURE.

Review Stop Z ZONING
Rev No 2 Status F Date 2005-08-19 Cont ID  
Sent By mmclean Date 2005-08-15 Time 12:10 Rev Time 0.00
Received By mmclean Date 2005-08-15 Time 12:10 Sent To I
Notes
2005-08-15 00:00:00DENIED,
 1. MUST HAVE ACCESS FROM THE MAIN TO
 ADDITION (LIBRARY) AND EXISTING
 RESIDENCE.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2005-04-29 Cont ID  
Sent By mmclean Date 2005-04-29 Time 10:54 Rev Time 0.00
Received By mmclean Date 2005-04-28 Time 17:10 Sent To I
Notes
2005-04-29 00:00:00DENIED,
 1. MUST HAVE INTERIOR ACCESS FROM THE
 ADDITION TO MAIN STRUCTURE AND MAIN
 STRUCTURE TO ADDITION.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
2005-04-28 00:00:00NEED A PLANNER OPINION REGARDING THE
 ADDITION AND INTERIOR ENTRANCE.