| Plan Review Stops For Permit 05041273 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2005-12-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-12-22 |
Time |
13:14 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2005-12-22 |
Time |
13:02 |
Sent To |
FIRE |
|
| Notes |
| 2005-12-22 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 05041273 | | | ADD: 424 HAMPTON RD | | | CONT: CLASSIC CONSTRUCTION | | | TEL: (561)719-5111 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVISION REVIEW | | | ACTION: DENIED | | | | | | 1) THE PERMIT THAT WAS PULLED ORIGINALLY | | | WAS WITHIN THE CONFINES OF TENANT | | | SEPERATION WALLS. THE REVISION INDICATES | | | WORK BEING COMPLETED IN THE COMMON AREA, | | | WHICH WILL OPEN NEW ISSUES. | | | FL BLD CODE 104.2.1.2 | | | ADDITIONAL INFORMATION REQUIRED: | | | | | | 1A) PROVIDE A COMPLETE FLOOR PLAN FOR | | | THIS COMPLETE FLOOR. PROVIDE THE | | | OCCUPANT LOAD FOR THIS FLOOR. THE | | | DOORWAY TO THE STAIR TOWER MAY BE | | | SWINGING IN THE WRONG DIRECTION. | | | 1012.1.2 EGRESS DOORS SHALL BE SIDE | | | SWINGING TYPE.DOORS SHALL SWING IN THE | | | DIRECTION OF EGRESS FOR THE FOLLOWING | | | 1. WHEN SERVING AN OCCUPANT LOAD OF | | | 50 OR MORE. | | | | | | 1B) PROVIDE IF THIS IS A FIRE | | | SPRINKLERED BUILDING, WHAT FIRE RATING | | | DOES THIS TRANSFORMER HAVE? IS THIS A | | | DRY OR OIL FILLED TRANSFORMER? | | | | | | 1C) IT APPEARS TO SIT ON THE FLOOR AND | | | DEPENDING ON THE SIZE AND LOCATION IT | | | MAY CONFLICT WITH :1003.2.4 OBJECTS | | | PROJECTING FROM WALLS WITH THEIR LEADING | | | EDGES BETWEEN27 AND 80 INCHES (686 | | | AND 2032 MM)ABOVE THE FINISHED FLOOR | | | SHALL PROTRUDENO MORE THAN 4 INCHES | | | (102 MM) INTO WALKS, CORRIDORS, | | | PASSAGEWAYS ORAISLES.FREE-STANDING | | | OBJECTS MOUNTED ON POSTS OR PYLONS MAY | | | OVERHANG 12INCHES (305 MM) MAXIMUM | | | FROM 27 TO 80 INCHES (686 AND 2032 MM) | | | ABOVE THE GROUND OR FINISHED FLOOR. | | | | | | 1D)11-4.4.1 GENERAL OBJECTS PROJECTING | | | FROM WALLS (FOR EXAMPLE, TELEPHONES) | | | WITH THEIR LEADING EDGES BETWEEN 27 IN. | | | AND 80 IN. (685 MM AND 2030 MM) ABOVE | | | THE FINISHED FLOOR SHALL PROTRUDE NO | | | MORE THAN 4 IN. (100 MM) INTO WALKS, | | | HALLS, CORRIDORS, PASSAGEWAYS, OR AISLES | | | (SEEFIGURE 11-8(A)).OBJECTS MOUNTED | | | WITH THEIR LEADING EDGES AT OR BELOW 27 | | | IN. (685 MM) ABOVE THE FINISHED FLOOR | | | MAY PROTRUDE ANY AMOUNT (SEEFIGURE | | | 11-8(A) AND FIGURE 11-8(B)). | | | FREE-STANDING OBJECTS MOUNTED ONPOSTS | | | OR PYLONS MAY OVERHANG 12 IN (305 MM) | | | MAXIMUM FROM 27 IN. TO 80 IN. (685 MM TO | | | 2030 MM) ABOVE THE GROUND OR FINISHED | | | FLOOR (SEE FIGURE 11-8(C) AND FIGURE | | | 11-8(D)).PROTRUDING OBJECTS SHALL NOT | | | REDUCE THE CLEAR WIDTH OF AN ACCESSIBLE | | | ROUTE OR MANEUVERING SPACE (SEE FIGURE | | | 11-8(E). | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2005-10-14 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-10-14 |
Time |
13:40 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2005-10-14 |
Time |
13:40 |
Sent To |
|
|
| Notes |
| 2005-10-08 00:00:00 | NEW SHEET A-1 AGAIN |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2005-09-30 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-09-30 |
Time |
13:08 |
Rev Time |
0.33 |
| Received By |
jwitmer |
Date |
2005-09-30 |
Time |
13:08 |
Sent To |
PC |
|
| Notes |
| 2005-09-21 00:00:00 | NEW SHEET A-1 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2005-08-28 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-08-28 |
Time |
12:33 |
Rev Time |
0.33 |
| Received By |
jwitmer |
Date |
2005-08-28 |
Time |
12:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2005-07-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-07-27 |
Time |
09:49 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2005-05-03 |
Time |
06:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
P |
Date |
2006-01-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-01-23 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-01-23 |
Time |
13:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
F |
Date |
2005-12-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-12-21 |
Time |
19:36 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-12-21 |
Time |
19:26 |
Sent To |
B |
|
| Notes |
| 2005-12-21 00:00:00 | **** UNSAT **** | | | | | | 1)NOTE: PLEASE SEE PLANS ARE NOW COMING | | | ON WITH THE TRANSFORMER/DISCONNECTS | | | BEING LOCATED IN WHAT APPEARS TO BE A | | | FIRE RATED EXIT CORRIDOR. | | | PLEASE SEE THE EXTEND OF THE BLDG | | | OCCUPANCY LOAD IS KNOWN FOR EXIT | | | REQUIREMENTS. | | | PLEASE SEE THIS EQUIPMENT WOULD PROMOTE | | | A MAJOR TRIPPING HAZARD LOCATED IN THIS | | | LOCATION. | | | PLEASE ALSO SEE POSSIBLE COMMENT FROM | | | BLDG REVIEW, WHEREAS PLANS SEEM TO SHOW | | | THE EGRESS DOOR FOR EXIT STAIR WAY | | | OPENING INTO THE HALL? | | | | | | 2)NOTE: PLEASE KNOW, THIS TRANSFORMER | | | MAY NOT BE MOUNTED ABOVE ANY | | | "DROP/SUSPENDED" CEILING IN HALLWAY PER | | | 450.13B | | | | | | ** PLEASE SEE BLDG REVIEW AND POSSIBLE | | | FIRE REVIEW OF EQUIPMENT INSTALLATION | | | LOCATION. | | | | | | ONCE ANY REVISION IS DONE AND REVIEWED | | | AND STAMPED BY BLDG AND FIRE, THE | | | ELECTRICAL REVISION MAY THEN BE STAMPED. | | | | | | IF THERE ARE ANY QUESTION, PLEASE DO NOT | | | HESITATE IN CONTACITNG THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2005-10-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-10-08 |
Time |
16:15 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2005-10-08 |
Time |
16:15 |
Sent To |
I |
|
| Notes |
| 2005-10-08 00:00:00 | SENT TO INCOMING, | | | NEW SHEET A-1 FOR BLDG REVIEW. | | | NEW FP SHEETS? NOT STAMPED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2005-09-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-09-21 |
Time |
19:12 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2005-09-21 |
Time |
19:12 |
Sent To |
|
|
| Notes |
| 2005-09-21 00:00:00 | *********** UNSAT 4TH REVIEW ********* | | | | | | 1)NOTE: PLEASE SEE ELECTRICAL CODE | | | COMPLIANCE COMMENTS HAVE BEEN ADDRESSED | | | BY NEW ENGINEER OF RECORD, HOWEVER | | | PLEASE SEE COMMENT BELOW. | | | | | | PLEASE SEE NE PLANS BY ENGINEER DO NOT | | | CONTAIN NEW LAYOUT FOR ELECTRICAL | | | LIGHTING/CEILING PLANS. | | | THE EXISTING LIGHTING/CEILING PLANS | | | "A-3" COULD HAVE BEEN USED FOR LIGHTING | | | LAYOUT ONLY , HOWEVER PLEASE SEE BOTH | | | SETS CONTAIN "PHOTOCOPIES" OF SIGNED AND | | | SEALED PLANS BY THE ARCHITECT??? | | | PLEASE SEE NEW SHEET A-1 AND A-3 WHICH | | | ARE NOT SIGNED, DATED AND SEALED. | | | PLEASE SEE BLDG REVIEW FOR SHEET A-1. | | | | | | PLEASE EITHER HAVE NEW ENGINEER OF | | | RECORD REVISE NEW SHEET E-1 TO INCLUDE | | | NEW ELECTRICAL LIGHTING/CEILING LAYOUT | | | OR PLEASE HAVE NEW SIGNED, DATED AND | | | SEALED PLANS FOR SHEET A-3. | | | | | | IN EITHER CASE, PLEASE REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW | | | REVISED , CORRECTED SHEETS INTO COMPLETE | | | SETS FOR REVIEW AND STAMPING. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2005-08-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-08-29 |
Time |
11:34 |
Rev Time |
|
| Received By |
dpalmer |
Date |
2005-08-29 |
Time |
11:33 |
Sent To |
|
|
| Notes |
| 2005-08-29 00:00:00 | ********* UNSAT 3RDREVIEW ********** | | | | | | PLEASE SEE NOTES FROM PREVIOUS REVIEWS | | | AND NEW COMMENTS DUE TO COMPLETE NEW | | | ELECTRICAL RISER SUBMITTED. | | | | | | 1)NOTE: PLEASE SEE RISER NOW INDICATES | | | AND NEW TRANSFOMER AND 277/480V SYSTEM | | | BEING SHOWN. | | | PLEASE SEE FS 471.003, WHICH REQUIRES | | | NEW WORK FOR 277/480V TO BE SIGNED AND | | | SEALED BY AN ENGINEER/PE. | | | | | | 2)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR(S) FOR TRANSFORMER. | | | 250.110, SIZED PER 250.122 | | | PLEASE ALSO SEE 250.30, 250.66 FOR | | | SIZING OF GROUNDING FOR TRANSFORMER. | | | | | | 3)NOTE: PLEASE SEE 210.8B3, 2002 NEC | | | REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT | | | RECEPTACLES IN NONDWELLING-TYPE KITCHENS | | | TO BE GFCI PROTECTED. THIS REQUIREMENT | | | APPLIES TO EACH AND EVERY 15- AND | | | 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE, | | | WHETHER OR NOT THE RECEPTACLE SERVES | | | COUNTERTOP APPLIANCES. | | | | | | 4)NOTE: PLEASE SUBMIT LOAD CALCUALTIONS | | | FOR NOW ADDING NEW LOADS TO EXISTING | | | MAIN DIST SYSTEM. | | | 220 | | | | | | 5)NOTE: PLEASE SEE FS 553.80(2)(B) | | | ATTACHED WITH RESPECT TO DESIGN | | | PROFESSIONAL AND REPEAT COMMENTS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2005-07-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-07-15 |
Time |
19:12 |
Rev Time |
0.60 |
| Received By |
dpalmer |
Date |
2005-07-15 |
Time |
18:53 |
Sent To |
|
|
| Notes |
| 2005-07-15 00:00:00 | ************ UNSAT ************* | | | | | | | | | PLEASE SEE A NEW ELECTRICAL RISER FOR | | | NEW SERVICE IS NOW BEING SUBMITTED. | | | | | | 1)NOTE: PLEASE SUBMIT/SHOW AIC RATING | | | FOR NEW MAIN. IT IS NOTED THAT AIC | | | RATING IS INDICATED FOR SUB PANEL. | | | 110.9,215.5 | | | | | | 2)NOTE: PLEASE INDICATE SIZE OF EXISTING | | | METER. PREVIOUS SERVICE RISER INDICATED | | | 100A'S? NEW MAIN IS 200A'S. | | | 215.5 | | | | | | 3)NOTE: PLEASE SEE NOW AN EQUIPMENT | | | GROUNDING CONDUCTOR IS SHOWN FROM METER | | | TO MAIN/FIRST MEANS OF DISCONNECT. | | | PLEASE SEE 250.6,250.24, EQUIPMENT | | | GROUNDING CONDUCTORS ARE ONLY INSTALLED | | | AFTER THE FIRST MEANS OF DISCONNECT. | | | | | | 4)NOTE: PLEASE SEE 2002 NEC 210.8B3 | | | WHICH REQUIRES ALL 15- AND 20-AMPERE, | | | 125-VOLT RECEPTACLES IN NONDWELLING-TYPE | | | KITCHENS TO BE GFCI PROTECTED. THIS | | | REQUIREMENT APPLIES TO EACH AND EVERY | | | 15- AND 20-AMPERE, 125-VOLT KITCHEN | | | RECEPTACLE, WHETHER OR NOT THE | | | RECEPTACLE SERVES COUNTERTOP APPLIANCES. | | | | | | 5)NOTE: PLEASE SEE ADDRESS ON PLANS | | | INDICATE 420 HAMPTON, HOWEVER PERMIT | | | APPLICATION SHOWS 424 AND OUR SYSTEM | | | SHOWS 424, PLEASE CORRELATE. | | | | | | | | | PLEASE SEE PLANS ARE COMING ABCK FOR | | | PLUMBING NOTES, PLEASE MAKE THE ABOVE | | | CHANGES/CORRECTIONS AT THIS TIME. | | | | | | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | ONE COPY OF OLD/VOIDED SHEETS SHALL BE | | | SUBMITTED FOR REFERENCE ONLY. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-04-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-04-26 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2005-05-03 |
Time |
06:57 |
Sent To |
|
|
| Notes |
| 2005-04-26 00:00:00 | ************ UNSAT ************ | | | | | | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH THE SUBMITTED | | | PANEL SCHEDULE. | | | 215.5 | | | | | | 2)NOTE: PLEASE SEE PLANS SHOW TWO | | | PANELS, PLEASE VERIFY IF ANY CIRCUITING | | | TO OUT OF SECOND PANEL SHOWN? IF SO, | | | PLEASE SUBMIT PANEL SCHEDULE AND | | | CORRELATE. | | | 215.5 | | | | | | 3)NOTE: PLEASE SHOW LOAD CALCULATIONS, | | | PLEASE SHOW PER | | | 220.3,220.10,220.11,220.13 ETC. | | | PLEASE ALSO SHOW ALL CONTINOUS LOADS | | | AT 125% PER 215.3,230.42 | | | | | | 4)NOTE: PLEASE SEE 424.3B FOR MIN OCP | | | FOR AHU. PLEASE SEE UNTI IS SHWON WITH | | | 10KW HEAT, 40 OCP AND #8 AWG. | | | 240.4,310.16 ETC. | | | | | | 5)NOTE: PLEASE SEE SERVICE IS SHOWN AS | | | EXISTING, HOWEVER SERVICE AS SHOWN DOES | | | NOT MEET CODE COMPLIANCE FOR SEC'S OR | | | FEEDERS. | | | PLEASE SEE #4 SHOWN FOR 200A'S. | | | PLEASE SEE 310.16, 240.4B | | | | | | 6)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR FROM MAIN TO PANEL. | | | 250.110,250.122,250.24 ETC. | | | | | | 7)NOTE: PLEASE SEE 700.12E FOR | | | CIRCUITING OF EM/EXT LTS. | | | | | | PLEASE SEE OTHER POSSIBLE COMMENTS FROM | | | OTHER REVIEWER(S) WHICH MAY HAVE AN | | | AFFECT ON ELECTRICAL PLANS. | | | | | | PLEASE REMOVE AN AND ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO COMPLETE SETS FOR REVIEW AND | | | STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
6 |
Status |
F |
Date |
2005-12-22 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-12-22 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-12-22 |
Time |
15:52 |
Sent To |
|
|
| Notes |
| 2005-12-22 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE SEE OTHER REVIEW COMMENTS | | | REGARDING SCOPE OF WORK IRREGULARITY. | | | | | | 2) PLEASE NOTE THAT TRANSFORMER AND | | | ASSOCIATED EQUIPMENT APPEARS TO OBSTRUCT | | | REQUIRED MEANS OF EGRESS. | | | | | | 3) PLEASE INDICATE TOTAL OCCUPANT LOAD | | | FOR FLOOR THAT MAY HAVE DIRECT IMPACT ON | | | DOOR SWING AT EXISTING EXIT STAIRS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2005-10-11 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-10-11 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-10-11 |
Time |
13:15 |
Sent To |
|
|
| Notes |
| 2005-10-11 00:00:00 | PLANS APPROVED AND STAMPED ON 8/30/05 | | | | | | FP SHEETS STAMPED ON 10/11/05 REF: | | | SEPARATE SHOP DRAWINGS AND PERMIT | | | REQUIRED FOR FIRE SPRINKLER REMODEL. | | 2005-10-08 00:00:00 | NEW FP SHEETS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2005-09-26 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2005-09-26 |
Time |
12:06 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2005-09-26 |
Time |
12:06 |
Sent To |
|
|
| Notes |
| 2005-09-26 00:00:00 | 1. SEPERATE PLANS AND PERMITS REQUIRED | | | FOR FIRE SPRINKLER SYSTEM REMODEL. | | | | | | 2. ENSURE THAT SUFFICIENT EMERGENCY | | | LIGHTING IS AVAILABLE FOR THE SPACE. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | | | | 804-4709 PHONE | | | 804-4774 FAX |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2005-08-30 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-08-30 |
Time |
09:34 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-08-30 |
Time |
09:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2005-07-21 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-07-21 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-07-21 |
Time |
11:18 |
Sent To |
|
|
| Notes |
| 2005-07-21 00:00:00 | ******APPROVED****** | | | | | | | | | 1) FIRE SPRINKLER DRAWINGS HAVE BEEN | | | SUBMITTED UNDER THIS PERMIT APPLICATION. | | | PLEASE NOTE THAT SEPARATE SHOP DRAWINGS | | | AND PERMITS ARE REQUIRED FOR THE FIRE | | | SPRINKLER AND FIRE ALARM SYSTEMS. | | | | | | 2) 2A-10 B,C RATED FIRE EXTINGUISHERS | | | ARE REQUIRED AND SHALL BE MOUNTED NOT TO | | | EXCEED 75' TRAVEL DISTANCE. | | | | | | | | | MIKE WENNERGREN, CAPTAIN | | | WPBFR(561) 805-6722 OR 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-05-04 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-05-04 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-05-04 |
Time |
14:44 |
Sent To |
|
|
| Notes |
| 2005-05-04 00:00:00 | 1) ALL CONSTRUCTION, ALTERATION AND | | | DEMOLITION TO COMPLY WITH NFPA 241. | | | | | | 2) DRAWINGS DO NOT SHOW ANY ILLUMINATED | | | EXIT SIGNS OR EMERGENCY LIGHTING. | | | | | | 3) SEPARATE SHOP DRAWINGS ARE REQUIRED | | | FOR FIRE ALARM AND FIRE SPRINKLER | | | REMODEL IF APPLICABLE. | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 835-2910 OR 805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2006-01-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-01-17 |
Time |
17:52 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-01-17 |
Time |
17:52 |
Sent To |
E |
|
| Notes |
| 2006-01-17 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2005-12-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-12-14 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-12-14 |
Time |
09:36 |
Sent To |
E |
|
| Notes |
| 2005-12-14 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2005-12-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-12-10 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-12-10 |
Time |
11:02 |
Sent To |
M |
|
| Notes |
| 2005-12-10 00:00:00 | TO "M" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-10-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-10-06 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-10-06 |
Time |
14:03 |
Sent To |
E |
|
| Notes |
| 2005-10-06 00:00:00 | TO "BOB"#9 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-09-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-20 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-20 |
Time |
09:06 |
Sent To |
|
|
| Notes |
| 2005-09-20 00:00:00 | TO "BOB"#5 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-08-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-23 |
Time |
19:03 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-23 |
Time |
19:03 |
Sent To |
|
|
| Notes |
| 2005-08-23 00:00:00 | TO "BOB"#2 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-07-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-15 |
Time |
10:38 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-15 |
Time |
10:38 |
Sent To |
|
|
| Notes |
| 2005-07-15 00:00:00 | TO "BOB" BD#8 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
P |
Date |
2005-08-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-06-10 |
Time |
09:59 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-08-30 |
Time |
09:33 |
Sent To |
|
|
| Notes |
| 2005-04-25 00:00:00 | TO "COMM" BD#36 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2005-07-16 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2005-07-16 |
Time |
09:25 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2005-07-16 |
Time |
09:21 |
Sent To |
|
|
| Notes |
| 2005-07-16 00:00:00 | NO PLANS HM. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2005-06-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-06-10 |
Time |
09:49 |
Rev Time |
0.20 |
| Received By |
pkrauss |
Date |
2005-06-10 |
Time |
09:49 |
Sent To |
|
|
| Notes |
| 2005-06-10 00:00:00 | NO MECHANICAL PLANS OR CONTRACTOR | | | INDICATED WITH PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2005-09-30 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-09-30 |
Time |
07:49 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2005-09-30 |
Time |
07:49 |
Sent To |
|
|
| Notes |
| 2005-09-30 00:00:00 | PROVISO; | | | NO GARBAGE DISPOSAL TO BE INSTALLED | | | UNDER BREAK SINK. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2005-08-27 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2005-08-27 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2005-08-27 |
Time |
08:40 |
Sent To |
|
|
| Notes |
| 2005-08-27 00:00:00 | PLUMBING PLAN REVIEW EXAMINER, FBC 2001 | | | PAUL SCHMITZ561-805-6692 | | | [email protected] | | | FBC 2001 | | | | | | 1.THIS THE THIRD REVIEW FOR BREAK ROOM | | | SINK, FS 553.80(2)(B) | | | DESIGN PROFESSIONAL DOUCMENTS | | | SEE ATTACHEDNOTICE.FOR ADDITIONAL FEE. | | | | | | 2. SHT. C-1 BREAK ROOM SINK. | | | GARBAGE DISPOSAL IS IN THE REQUIRED KNEE | | | SPACE CLEARANCES,NOT APPROVED. | | | END OF COMMENTS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2005-07-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-07-15 |
Time |
18:40 |
Rev Time |
0.35 |
| Received By |
kstevens |
Date |
2005-07-15 |
Time |
18:40 |
Sent To |
|
|
| Notes |
| 2005-07-15 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | | | | A. SHT C1 DETAIL FOR THE KITCHEN SINK IS | | | NOT APPROVED FOR COMMERCIAL ACCESSIBLE | | | SINKS. THE FOLLOWING INFORMATION SHALL | | | BE SHOWN ON THE DETAIL: | | | A. 11-4.24.2 HEIGHT (SHOWN AS 36") | | | B. 11-4.24.3 KNEE CLEARANCE - SHOW A | | | FRONTAL ELEVATION INDICATING COMPLIANCE | | | AS WELL AS A SIDE ELEVATION. | | | C. 11-4.24.4 SINK DEPTH | | | D. 11-4.24.7 FAUCETS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-06-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-06-04 |
Time |
10:49 |
Rev Time |
0.38 |
| Received By |
kstevens |
Date |
2005-06-04 |
Time |
10:49 |
Sent To |
|
|
| Notes |
| 2005-06-04 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | 1. SUBMIT A SANITARY RISER DIAGRAM SHOW | | | ALL PIPE SIZES, VENTING, AND POINTS OF | | | CONNECTION AND TERMINATION. SECTION | | | 104.3.1.1. | | | 2. SUBMIT A WATER RISER DIAGRAM SHOWING | | | ALL PIPE SIZES, VALVES AND WATER HAMMER | | | ARRESTORS (WHERE REQUIRED BY SECTION | | | 604.9). | | | 3. SUBMIT A DETIAL SHOWING COMPLIANCE | | | WITH SECTION 11-4.24 AND ALL | | | SUBSECTIONS. CLEAR FLOOR SPACE SHALL BE | | | FORWARD APPROACH AND EXTEND A MAXIMUM OF | | | 19" UNDERNEATH THE SINK. | | | 4. A DRINKING FOUNTAIN IS REQUIRED PER | | | TABLE 403.1 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|
|