Plan Review Details - Permit 05041273
Plan Review Stops For Permit 05041273
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2005-12-22 Cont ID  
Sent By jwitmer Date 2005-12-22 Time 13:14 Rev Time 0.77
Received By jwitmer Date 2005-12-22 Time 13:02 Sent To FIRE
Notes
2005-12-22 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05041273
 ADD: 424 HAMPTON RD
 CONT: CLASSIC CONSTRUCTION
 TEL: (561)719-5111
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW
 ACTION: DENIED
  
 1) THE PERMIT THAT WAS PULLED ORIGINALLY
 WAS WITHIN THE CONFINES OF TENANT
 SEPERATION WALLS. THE REVISION INDICATES
 WORK BEING COMPLETED IN THE COMMON AREA,
 WHICH WILL OPEN NEW ISSUES.
 FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED:
  
 1A) PROVIDE A COMPLETE FLOOR PLAN FOR
 THIS COMPLETE FLOOR. PROVIDE THE
 OCCUPANT LOAD FOR THIS FLOOR. THE
 DOORWAY TO THE STAIR TOWER MAY BE
 SWINGING IN THE WRONG DIRECTION.
 1012.1.2 EGRESS DOORS SHALL BE SIDE
 SWINGING TYPE.DOORS SHALL SWING IN THE
 DIRECTION OF EGRESS FOR THE FOLLOWING
 1. WHEN SERVING AN OCCUPANT LOAD OF
 50 OR MORE.
  
 1B) PROVIDE IF THIS IS A FIRE
 SPRINKLERED BUILDING, WHAT FIRE RATING
 DOES THIS TRANSFORMER HAVE? IS THIS A
 DRY OR OIL FILLED TRANSFORMER?
  
 1C) IT APPEARS TO SIT ON THE FLOOR AND
 DEPENDING ON THE SIZE AND LOCATION IT
 MAY CONFLICT WITH :1003.2.4 OBJECTS
 PROJECTING FROM WALLS WITH THEIR LEADING
 EDGES BETWEEN27 AND 80 INCHES (686
 AND 2032 MM)ABOVE THE FINISHED FLOOR
 SHALL PROTRUDENO MORE THAN 4 INCHES
 (102 MM) INTO WALKS, CORRIDORS,
 PASSAGEWAYS ORAISLES.FREE-STANDING
 OBJECTS MOUNTED ON POSTS OR PYLONS MAY
 OVERHANG 12INCHES (305 MM) MAXIMUM
 FROM 27 TO 80 INCHES (686 AND 2032 MM)
 ABOVE THE GROUND OR FINISHED FLOOR.
  
 1D)11-4.4.1 GENERAL OBJECTS PROJECTING
 FROM WALLS (FOR EXAMPLE, TELEPHONES)
 WITH THEIR LEADING EDGES BETWEEN 27 IN.
 AND 80 IN. (685 MM AND 2030 MM) ABOVE
 THE FINISHED FLOOR SHALL PROTRUDE NO
 MORE THAN 4 IN. (100 MM) INTO WALKS,
 HALLS, CORRIDORS, PASSAGEWAYS, OR AISLES
 (SEEFIGURE 11-8(A)).OBJECTS MOUNTED
 WITH THEIR LEADING EDGES AT OR BELOW 27
 IN. (685 MM) ABOVE THE FINISHED FLOOR
 MAY PROTRUDE ANY AMOUNT (SEEFIGURE
 11-8(A) AND FIGURE 11-8(B)).
 FREE-STANDING OBJECTS MOUNTED ONPOSTS
 OR PYLONS MAY OVERHANG 12 IN (305 MM)
 MAXIMUM FROM 27 IN. TO 80 IN. (685 MM TO
 2030 MM) ABOVE THE GROUND OR FINISHED
 FLOOR (SEE FIGURE 11-8(C) AND FIGURE
 11-8(D)).PROTRUDING OBJECTS SHALL NOT
 REDUCE THE CLEAR WIDTH OF AN ACCESSIBLE
 ROUTE OR MANEUVERING SPACE (SEE FIGURE
 11-8(E).
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-10-14 Cont ID  
Sent By jwitmer Date 2005-10-14 Time 13:40 Rev Time 0.55
Received By jwitmer Date 2005-10-14 Time 13:40 Sent To  
Notes
2005-10-08 00:00:00NEW SHEET A-1 AGAIN

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-09-30 Cont ID  
Sent By jwitmer Date 2005-09-30 Time 13:08 Rev Time 0.33
Received By jwitmer Date 2005-09-30 Time 13:08 Sent To PC
Notes
2005-09-21 00:00:00NEW SHEET A-1

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-08-28 Cont ID  
Sent By jwitmer Date 2005-08-28 Time 12:33 Rev Time 0.33
Received By jwitmer Date 2005-08-28 Time 12:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-07-27 Cont ID  
Sent By jwitmer Date 2005-07-27 Time 09:49 Rev Time 0.55
Received By jwitmer Date 2005-05-03 Time 06:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2006-01-23 Cont ID  
Sent By dpalmer Date 2006-01-23 Time 14:22 Rev Time 0.00
Received By dpalmer Date 2006-01-23 Time 13:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2005-12-21 Cont ID  
Sent By dpalmer Date 2005-12-21 Time 19:36 Rev Time 0.00
Received By dpalmer Date 2005-12-21 Time 19:26 Sent To B
Notes
2005-12-21 00:00:00**** UNSAT ****
  
 1)NOTE: PLEASE SEE PLANS ARE NOW COMING
 ON WITH THE TRANSFORMER/DISCONNECTS
 BEING LOCATED IN WHAT APPEARS TO BE A
 FIRE RATED EXIT CORRIDOR.
 PLEASE SEE THE EXTEND OF THE BLDG
 OCCUPANCY LOAD IS KNOWN FOR EXIT
 REQUIREMENTS.
 PLEASE SEE THIS EQUIPMENT WOULD PROMOTE
 A MAJOR TRIPPING HAZARD LOCATED IN THIS
 LOCATION.
 PLEASE ALSO SEE POSSIBLE COMMENT FROM
 BLDG REVIEW, WHEREAS PLANS SEEM TO SHOW
 THE EGRESS DOOR FOR EXIT STAIR WAY
 OPENING INTO THE HALL?
  
 2)NOTE: PLEASE KNOW, THIS TRANSFORMER
 MAY NOT BE MOUNTED ABOVE ANY
 "DROP/SUSPENDED" CEILING IN HALLWAY PER
 450.13B
  
 ** PLEASE SEE BLDG REVIEW AND POSSIBLE
 FIRE REVIEW OF EQUIPMENT INSTALLATION
 LOCATION.
  
 ONCE ANY REVISION IS DONE AND REVIEWED
 AND STAMPED BY BLDG AND FIRE, THE
 ELECTRICAL REVISION MAY THEN BE STAMPED.
  
 IF THERE ARE ANY QUESTION, PLEASE DO NOT
 HESITATE IN CONTACITNG THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-10-08 Cont ID  
Sent By dpalmer Date 2005-10-08 Time 16:15 Rev Time 0.33
Received By dpalmer Date 2005-10-08 Time 16:15 Sent To I
Notes
2005-10-08 00:00:00SENT TO INCOMING,
 NEW SHEET A-1 FOR BLDG REVIEW.
 NEW FP SHEETS? NOT STAMPED.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-09-21 Cont ID  
Sent By dpalmer Date 2005-09-21 Time 19:12 Rev Time 0.50
Received By dpalmer Date 2005-09-21 Time 19:12 Sent To  
Notes
2005-09-21 00:00:00*********** UNSAT 4TH REVIEW *********
  
 1)NOTE: PLEASE SEE ELECTRICAL CODE
 COMPLIANCE COMMENTS HAVE BEEN ADDRESSED
 BY NEW ENGINEER OF RECORD, HOWEVER
 PLEASE SEE COMMENT BELOW.
  
 PLEASE SEE NE PLANS BY ENGINEER DO NOT
 CONTAIN NEW LAYOUT FOR ELECTRICAL
 LIGHTING/CEILING PLANS.
 THE EXISTING LIGHTING/CEILING PLANS
 "A-3" COULD HAVE BEEN USED FOR LIGHTING
 LAYOUT ONLY , HOWEVER PLEASE SEE BOTH
 SETS CONTAIN "PHOTOCOPIES" OF SIGNED AND
 SEALED PLANS BY THE ARCHITECT???
 PLEASE SEE NEW SHEET A-1 AND A-3 WHICH
 ARE NOT SIGNED, DATED AND SEALED.
 PLEASE SEE BLDG REVIEW FOR SHEET A-1.
  
 PLEASE EITHER HAVE NEW ENGINEER OF
 RECORD REVISE NEW SHEET E-1 TO INCLUDE
 NEW ELECTRICAL LIGHTING/CEILING LAYOUT
 OR PLEASE HAVE NEW SIGNED, DATED AND
 SEALED PLANS FOR SHEET A-3.
  
 IN EITHER CASE, PLEASE REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED , CORRECTED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-08-29 Cont ID  
Sent By dpalmer Date 2005-08-29 Time 11:34 Rev Time  
Received By dpalmer Date 2005-08-29 Time 11:33 Sent To  
Notes
2005-08-29 00:00:00********* UNSAT 3RDREVIEW **********
  
 PLEASE SEE NOTES FROM PREVIOUS REVIEWS
 AND NEW COMMENTS DUE TO COMPLETE NEW
 ELECTRICAL RISER SUBMITTED.
  
 1)NOTE: PLEASE SEE RISER NOW INDICATES
 AND NEW TRANSFOMER AND 277/480V SYSTEM
 BEING SHOWN.
 PLEASE SEE FS 471.003, WHICH REQUIRES
 NEW WORK FOR 277/480V TO BE SIGNED AND
 SEALED BY AN ENGINEER/PE.
  
 2)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR(S) FOR TRANSFORMER.
 250.110, SIZED PER 250.122
 PLEASE ALSO SEE 250.30, 250.66 FOR
 SIZING OF GROUNDING FOR TRANSFORMER.
  
 3)NOTE: PLEASE SEE 210.8B3, 2002 NEC
 REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT
 RECEPTACLES IN NONDWELLING-TYPE KITCHENS
 TO BE GFCI PROTECTED. THIS REQUIREMENT
 APPLIES TO EACH AND EVERY 15- AND
 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE,
 WHETHER OR NOT THE RECEPTACLE SERVES
 COUNTERTOP APPLIANCES.
  
 4)NOTE: PLEASE SUBMIT LOAD CALCUALTIONS
 FOR NOW ADDING NEW LOADS TO EXISTING
 MAIN DIST SYSTEM.
 220
  
 5)NOTE: PLEASE SEE FS 553.80(2)(B)
 ATTACHED WITH RESPECT TO DESIGN
 PROFESSIONAL AND REPEAT COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-07-15 Cont ID  
Sent By dpalmer Date 2005-07-15 Time 19:12 Rev Time 0.60
Received By dpalmer Date 2005-07-15 Time 18:53 Sent To  
Notes
2005-07-15 00:00:00************ UNSAT *************
  
  
 PLEASE SEE A NEW ELECTRICAL RISER FOR
 NEW SERVICE IS NOW BEING SUBMITTED.
  
 1)NOTE: PLEASE SUBMIT/SHOW AIC RATING
 FOR NEW MAIN. IT IS NOTED THAT AIC
 RATING IS INDICATED FOR SUB PANEL.
 110.9,215.5
  
 2)NOTE: PLEASE INDICATE SIZE OF EXISTING
 METER. PREVIOUS SERVICE RISER INDICATED
 100A'S? NEW MAIN IS 200A'S.
 215.5
  
 3)NOTE: PLEASE SEE NOW AN EQUIPMENT
 GROUNDING CONDUCTOR IS SHOWN FROM METER
 TO MAIN/FIRST MEANS OF DISCONNECT.
 PLEASE SEE 250.6,250.24, EQUIPMENT
 GROUNDING CONDUCTORS ARE ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISCONNECT.
  
 4)NOTE: PLEASE SEE 2002 NEC 210.8B3
 WHICH REQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
 5)NOTE: PLEASE SEE ADDRESS ON PLANS
 INDICATE 420 HAMPTON, HOWEVER PERMIT
 APPLICATION SHOWS 424 AND OUR SYSTEM
 SHOWS 424, PLEASE CORRELATE.
  
  
 PLEASE SEE PLANS ARE COMING ABCK FOR
 PLUMBING NOTES, PLEASE MAKE THE ABOVE
 CHANGES/CORRECTIONS AT THIS TIME.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE COPY OF OLD/VOIDED SHEETS SHALL BE
 SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-04-26 Cont ID  
Sent By dpalmer Date 2005-04-26 Time 13:14 Rev Time 0.00
Received By jwitmer Date 2005-05-03 Time 06:57 Sent To  
Notes
2005-04-26 00:00:00************ UNSAT ************
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE.
 215.5
  
 2)NOTE: PLEASE SEE PLANS SHOW TWO
 PANELS, PLEASE VERIFY IF ANY CIRCUITING
 TO OUT OF SECOND PANEL SHOWN? IF SO,
 PLEASE SUBMIT PANEL SCHEDULE AND
 CORRELATE.
 215.5
  
 3)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
  
 4)NOTE: PLEASE SEE 424.3B FOR MIN OCP
 FOR AHU. PLEASE SEE UNTI IS SHWON WITH
 10KW HEAT, 40 OCP AND #8 AWG.
 240.4,310.16 ETC.
  
 5)NOTE: PLEASE SEE SERVICE IS SHOWN AS
 EXISTING, HOWEVER SERVICE AS SHOWN DOES
 NOT MEET CODE COMPLIANCE FOR SEC'S OR
 FEEDERS.
 PLEASE SEE #4 SHOWN FOR 200A'S.
 PLEASE SEE 310.16, 240.4B
  
 6)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO PANEL.
 250.110,250.122,250.24 ETC.
  
 7)NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF EM/EXT LTS.
  
 PLEASE SEE OTHER POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 PLEASE REMOVE AN AND ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status F Date 2005-12-22 Cont ID  
Sent By mwennerg Date 2005-12-22 Time 15:52 Rev Time 0.00
Received By mwennerg Date 2005-12-22 Time 15:52 Sent To  
Notes
2005-12-22 00:00:00******DENIED******
  
 1) PLEASE SEE OTHER REVIEW COMMENTS
 REGARDING SCOPE OF WORK IRREGULARITY.
  
 2) PLEASE NOTE THAT TRANSFORMER AND
 ASSOCIATED EQUIPMENT APPEARS TO OBSTRUCT
 REQUIRED MEANS OF EGRESS.
  
 3) PLEASE INDICATE TOTAL OCCUPANT LOAD
 FOR FLOOR THAT MAY HAVE DIRECT IMPACT ON
 DOOR SWING AT EXISTING EXIT STAIRS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2005-10-11 Cont ID  
Sent By mwennerg Date 2005-10-11 Time 13:15 Rev Time 0.00
Received By mwennerg Date 2005-10-11 Time 13:15 Sent To  
Notes
2005-10-11 00:00:00PLANS APPROVED AND STAMPED ON 8/30/05
  
 FP SHEETS STAMPED ON 10/11/05 REF:
 SEPARATE SHOP DRAWINGS AND PERMIT
 REQUIRED FOR FIRE SPRINKLER REMODEL.
2005-10-08 00:00:00NEW FP SHEETS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2005-09-26 Cont ID  
Sent By mcarsill Date 2005-09-26 Time 12:06 Rev Time 0.00
Received By mcarsill Date 2005-09-26 Time 12:06 Sent To  
Notes
2005-09-26 00:00:001. SEPERATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEM REMODEL.
  
 2. ENSURE THAT SUFFICIENT EMERGENCY
 LIGHTING IS AVAILABLE FOR THE SPACE.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
  
 804-4709 PHONE
 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-08-30 Cont ID  
Sent By mwennerg Date 2005-08-30 Time 09:34 Rev Time 0.00
Received By mwennerg Date 2005-08-30 Time 09:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-07-21 Cont ID  
Sent By mwennerg Date 2005-07-21 Time 11:18 Rev Time 0.00
Received By mwennerg Date 2005-07-21 Time 11:18 Sent To  
Notes
2005-07-21 00:00:00******APPROVED******
  
  
 1) FIRE SPRINKLER DRAWINGS HAVE BEEN
 SUBMITTED UNDER THIS PERMIT APPLICATION.
 PLEASE NOTE THAT SEPARATE SHOP DRAWINGS
 AND PERMITS ARE REQUIRED FOR THE FIRE
 SPRINKLER AND FIRE ALARM SYSTEMS.
  
 2) 2A-10 B,C RATED FIRE EXTINGUISHERS
 ARE REQUIRED AND SHALL BE MOUNTED NOT TO
 EXCEED 75' TRAVEL DISTANCE.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 805-6722 OR 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-05-04 Cont ID  
Sent By mwennerg Date 2005-05-04 Time 14:44 Rev Time 0.00
Received By mwennerg Date 2005-05-04 Time 14:44 Sent To  
Notes
2005-05-04 00:00:001) ALL CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 2) DRAWINGS DO NOT SHOW ANY ILLUMINATED
 EXIT SIGNS OR EMERGENCY LIGHTING.
  
 3) SEPARATE SHOP DRAWINGS ARE REQUIRED
 FOR FIRE ALARM AND FIRE SPRINKLER
 REMODEL IF APPLICABLE.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910 OR 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-01-17 Cont ID  
Sent By adarroug Date 2006-01-17 Time 17:52 Rev Time 0.00
Received By adarroug Date 2006-01-17 Time 17:52 Sent To E
Notes
2006-01-17 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-12-14 Cont ID  
Sent By adarroug Date 2005-12-14 Time 09:37 Rev Time 0.00
Received By adarroug Date 2005-12-14 Time 09:36 Sent To E
Notes
2005-12-14 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-12-10 Cont ID  
Sent By adarroug Date 2005-12-10 Time 11:02 Rev Time 0.00
Received By adarroug Date 2005-12-10 Time 11:02 Sent To M
Notes
2005-12-10 00:00:00TO "M" BOX

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-10-06 Cont ID  
Sent By adarroug Date 2005-10-06 Time 14:03 Rev Time 0.00
Received By adarroug Date 2005-10-06 Time 14:03 Sent To E
Notes
2005-10-06 00:00:00TO "BOB"#9

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-09-20 Cont ID  
Sent By adarroug Date 2005-09-20 Time 09:06 Rev Time 0.00
Received By adarroug Date 2005-09-20 Time 09:06 Sent To  
Notes
2005-09-20 00:00:00TO "BOB"#5

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-23 Cont ID  
Sent By adarroug Date 2005-08-23 Time 19:03 Rev Time 0.00
Received By adarroug Date 2005-08-23 Time 19:03 Sent To  
Notes
2005-08-23 00:00:00TO "BOB"#2

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-15 Cont ID  
Sent By adarroug Date 2005-07-15 Time 10:38 Rev Time 0.00
Received By adarroug Date 2005-07-15 Time 10:38 Sent To  
Notes
2005-07-15 00:00:00TO "BOB" BD#8

Review Stop I INCOMING/PROCESSING
Rev No 1 Status P Date 2005-08-30 Cont ID  
Sent By shill Date 2005-06-10 Time 09:59 Rev Time 0.00
Received By mwennerg Date 2005-08-30 Time 09:33 Sent To  
Notes
2005-04-25 00:00:00TO "COMM" BD#36

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2005-07-16 Cont ID  
Sent By hmoser Date 2005-07-16 Time 09:25 Rev Time 0.00
Received By hmoser Date 2005-07-16 Time 09:21 Sent To  
Notes
2005-07-16 00:00:00NO PLANS HM.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-06-10 Cont ID  
Sent By pkrauss Date 2005-06-10 Time 09:49 Rev Time 0.20
Received By pkrauss Date 2005-06-10 Time 09:49 Sent To  
Notes
2005-06-10 00:00:00NO MECHANICAL PLANS OR CONTRACTOR
 INDICATED WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-09-30 Cont ID  
Sent By jleech Date 2005-09-30 Time 07:49 Rev Time 0.50
Received By jleech Date 2005-09-30 Time 07:49 Sent To  
Notes
2005-09-30 00:00:00PROVISO;
 NO GARBAGE DISPOSAL TO BE INSTALLED
 UNDER BREAK SINK.

Review Stop P PLUMBING
Rev No 3 Status F Date 2005-08-27 Cont ID  
Sent By pschmitz Date 2005-08-27 Time 08:40 Rev Time 0.00
Received By pschmitz Date 2005-08-27 Time 08:40 Sent To  
Notes
2005-08-27 00:00:00PLUMBING PLAN REVIEW EXAMINER, FBC 2001
 PAUL SCHMITZ561-805-6692
 [email protected]
 FBC 2001
  
 1.THIS THE THIRD REVIEW FOR BREAK ROOM
 SINK, FS 553.80(2)(B)
 DESIGN PROFESSIONAL DOUCMENTS
 SEE ATTACHEDNOTICE.FOR ADDITIONAL FEE.
  
 2. SHT. C-1 BREAK ROOM SINK.
 GARBAGE DISPOSAL IS IN THE REQUIRED KNEE
 SPACE CLEARANCES,NOT APPROVED.
 END OF COMMENTS

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-07-15 Cont ID  
Sent By kstevens Date 2005-07-15 Time 18:40 Rev Time 0.35
Received By kstevens Date 2005-07-15 Time 18:40 Sent To  
Notes
2005-07-15 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
  
 A. SHT C1 DETAIL FOR THE KITCHEN SINK IS
 NOT APPROVED FOR COMMERCIAL ACCESSIBLE
 SINKS. THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON THE DETAIL:
 A. 11-4.24.2 HEIGHT (SHOWN AS 36")
 B. 11-4.24.3 KNEE CLEARANCE - SHOW A
 FRONTAL ELEVATION INDICATING COMPLIANCE
 AS WELL AS A SIDE ELEVATION.
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.7 FAUCETS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-06-04 Cont ID  
Sent By kstevens Date 2005-06-04 Time 10:49 Rev Time 0.38
Received By kstevens Date 2005-06-04 Time 10:49 Sent To  
Notes
2005-06-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1. SUBMIT A SANITARY RISER DIAGRAM SHOW
 ALL PIPE SIZES, VENTING, AND POINTS OF
 CONNECTION AND TERMINATION. SECTION
 104.3.1.1.
 2. SUBMIT A WATER RISER DIAGRAM SHOWING
 ALL PIPE SIZES, VALVES AND WATER HAMMER
 ARRESTORS (WHERE REQUIRED BY SECTION
 604.9).
 3. SUBMIT A DETIAL SHOWING COMPLIANCE
 WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. CLEAR FLOOR SPACE SHALL BE
 FORWARD APPROACH AND EXTEND A MAXIMUM OF
 19" UNDERNEATH THE SINK.
 4. A DRINKING FOUNTAIN IS REQUIRED PER
 TABLE 403.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  