Plan Review Details - Permit 05041212
Plan Review Stops For Permit 05041212
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-12-25 Cont ID  
Sent By shill Date 2005-12-25 Time 19:01 Rev Time 0.50
Received By shill Date 2005-12-25 Time 19:01 Sent To  
Notes
2005-12-25 00:00:00REVISED A4.0 DATED 12/19/05
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-09-29 Cont ID  
Sent By lmartine Date 2005-09-29 Time 18:34 Rev Time 0.00
Received By lmartine Date 2005-09-29 Time 18:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-07-23 Cont ID  
Sent By shill Date 2005-07-23 Time 23:24 Rev Time 1.00
Received By shill Date 2005-07-23 Time 23:13 Sent To  
Notes
2005-07-23 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.
  
 2.)PROVIDE PRODUCT APPROVALS FOR THE
 STOREFRONT GLASS.STATE OR LOCAL
 PRODUCT APPROVALS REQUIRED IN ADDITION
 TO THE EVALUATION OR TEST REPORT,
 FAC9B72.IF PRODUCT APPROVALS ARE NOT
 SUBMITTED PRIOR TO PERMIT ISSUANCE A
 SEPARATE PERMIT WILL BE REQUIRED.
 WWW.FLORIDABUILDING.ORG
  
 3.)SEE PREVIOUS LIST, ITEM #5.THE
 LOUNG SINKS A6 ARE TO COMPLY WITH
 FBC11-4.24.THE CABINET DOORS ARE STILL
 SHOWN ON THE DETAILS.PLEASE SEE FBC11
 FIGURE 32 AND REVISE.
  
 4.)SEE ATTACHED FS553.80(2)(B).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-16 Cont ID  
Sent By shill Date 2005-05-16 Time 10:27 Rev Time 2.00
Received By shill Date 2005-05-16 Time 10:27 Sent To  
Notes
2005-05-16 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PROVIDE MANEUVERING CLEARANCE ON
 THE PLAN FOR DOOR 102, PUSH SIDE.
  
 2.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVALS REQUIRED AS WELL AS TEST
 REPORT WITH INSTALLATION INSTRUCTIONS OR
 NOA, FAC9B72 (STOREFRONT WINDOW).
  
 3.)IMPACT PROTECTION REQUIRED
 FBC1606.1.4.IF THE STOREFRONT WINDOW
 IS NOT IMPACT, SUBMIT PRODUCT APPROVALS
 FOR SHUTTERS AND SHOW ON THE PLAN WHERE
 THEY WILL BE STORED.IF THEY ARE STORED
 VERTICALLY, PROVIDE A RACK DETAIL.
  
 4.)THE SQUARE FOOTAGE ON THE ENERGY
 CALC DOESN'T MATCH THE PLAN.
  
 5.)THE LOUNGE SINKS A6 ARE TO COMPLY
 WITH FBC11-4.24.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-01-30 Cont ID  
Sent By jleahy Date 2006-01-30 Time 14:56 Rev Time 0.45
Received By jleahy Date 2006-01-30 Time 14:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-12-08 Cont ID  
Sent By jleahy Date 2005-12-08 Time 09:24 Rev Time 0.45
Received By jleahy Date 2005-12-08 Time 09:12 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-04-26 Cont ID  
Sent By dpalmer Date 2005-04-26 Time 16:01 Rev Time 1.00
Received By dpalmer Date 2005-04-26 Time 15:33 Sent To  
Notes
2005-04-26 00:00:00***** PROVISO ******
  
  
 1)NOTE:PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125% AND LARGEST MOTOR LOADS.
 215.3,230.42 ETC.
  
 REVISE LOAD CALCS BEFORE ROUGH.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-01-11 Cont ID  
Sent By mwennerg Date 2006-01-11 Time 11:14 Rev Time 0.00
Received By mwennerg Date 2006-01-11 Time 11:14 Sent To  
Notes
2006-01-11 00:00:00REVISION DATED 11/14/05

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-05-10 Cont ID  
Sent By mwennerg Date 2005-05-10 Time 13:04 Rev Time 0.00
Received By mwennerg Date 2005-05-10 Time 10:31 Sent To  
Notes
2005-05-10 00:00:00PASSED
  
  
 1) IN THE CITY OF WEST PALM BEACH, DUCT
 SMOKE DETECTORS SHALL BE WIRED INTO THE
 FIRE ALARM PANEL TO INITIATE A GENERAL
 FIRE ALARM, NOT SUPERVISORY SIGNAL.
  
 2) NEW FIRE ALARM SYSTEMS SUPERVISING A
 SPRINKLER SYSTEM SHALL BE UL CERTIFIED
 FOR CENTRAL STATION SERVICE.
  
 3) SEPARATE SHOP DRAWING AND PERMITS ARE
 REQUIRED FOR FIRE ALARM AND FIRE
 SPRINKLER REMODELS.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910 OR 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-01-13 Cont ID  
Sent By adarroug Date 2006-01-13 Time 16:39 Rev Time 0.00
Received By adarroug Date 2006-01-13 Time 16:39 Sent To M
Notes
2006-01-13 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-12-22 Cont ID  
Sent By adarroug Date 2005-12-22 Time 15:20 Rev Time 0.00
Received By adarroug Date 2005-12-22 Time 15:19 Sent To  
Notes
2005-12-22 00:00:00TO "BOB"#7

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-12-10 Cont ID  
Sent By adarroug Date 2005-12-10 Time 10:57 Rev Time 0.00
Received By adarroug Date 2005-12-10 Time 10:57 Sent To  
Notes
2006-01-11 00:00:00TO "COMM" BD#15
2005-12-10 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-12-08 Cont ID  
Sent By jleahy Date 2005-12-08 Time 09:11 Rev Time 0.00
Received By jleahy Date 2005-12-08 Time 09:11 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-19 Cont ID  
Sent By adarroug Date 2005-09-19 Time 14:49 Rev Time 0.00
Received By adarroug Date 2005-09-19 Time 14:48 Sent To  
Notes
2005-09-21 00:00:00TO "COMM" BD#3
2005-09-19 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-08 Cont ID  
Sent By adarroug Date 2005-07-08 Time 14:46 Rev Time 0.00
Received By adarroug Date 2005-07-08 Time 14:46 Sent To  
Notes
2005-07-18 00:00:00TO "COMM" BD#16
2005-07-08 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-09 Cont ID  
Sent By kstevens Date 2005-06-09 Time 08:18 Rev Time 0.00
Received By kstevens Date 2005-04-25 Time 08:42 Sent To  
Notes
2005-04-25 00:00:00TO "COMM" BD#45

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-01-31 Cont ID  
Sent By hmoser Date 2006-01-31 Time 14:33 Rev Time 0.00
Received By hmoser Date 2006-01-31 Time 14:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-01-23 Cont ID  
Sent By pkrauss Date 2006-01-23 Time 16:23 Rev Time 0.00
Received By pkrauss Date 2006-01-23 Time 16:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-12-22 Cont ID  
Sent By tgordon Date 2005-12-22 Time 16:26 Rev Time 0.20
Received By tgordon Date 2005-12-22 Time 16:26 Sent To  
Notes
2005-12-22 00:00:00MECH. REV. SUBMITTAL TO GO FROM SQUARE
 DUCT TO ROUND.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-09-22 Cont ID  
Sent By pkrauss Date 2005-09-22 Time 14:35 Rev Time 0.10
Received By pkrauss Date 2005-09-22 Time 14:35 Sent To  
Notes
2005-09-22 00:00:00APPROVED PER PER HAROLD MOSER 6-4-05

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-06-04 Cont ID  
Sent By hmoser Date 2005-06-04 Time 10:38 Rev Time 0.00
Received By hmoser Date 2005-06-04 Time 09:58 Sent To  
Notes
2005-06-04 00:00:00REFER TO SECTION 601.4 EXCEPTION # 3
 HABITABLE ROOMS ONLEY SHALL BE REQUIRED
 TO HAVE BALANCED RETURN AIR.BATHROOM OR
 RESTROOMS ARE AN EXCEPTION.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-01-25 Cont ID  
Sent By pschmitz Date 2006-01-25 Time 10:42 Rev Time 0.00
Received By pschmitz Date 2006-01-25 Time 10:42 Sent To  
Notes
2006-01-25 00:00:00RE-SUB

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-09-27 Cont ID  
Sent By pschmitz Date 2005-09-27 Time 11:49 Rev Time 0.00
Received By pschmitz Date 2005-09-27 Time 11:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-08-08 Cont ID  
Sent By kstevens Date 2005-08-08 Time 09:20 Rev Time 1.00
Received By kstevens Date 2005-08-08 Time 09:20 Sent To  
Notes
2005-08-08 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
  
 A. FROM PREVIOUS REVIEW: COMMENT NUMBER
 TO REFLECT NUMBER FROM FIRST REVIEW:
 3. CABINET DOORS ARE STILL SHOWN ON THE
 THE DETAILS 1/A-6, D/A-6 & H/A-6. THE
 CABINET DOORS ARE NOT ALLOWED IN THE
 CLEAR FLOOR SPACE FOR THE SINKS.
 4. SHT A5.0 WALL TO BE NONABSORBENT PER
 SECTION 1204.2. RESPONSE NOTED, BUT
 REQUIREMENT TO USE WATER PROOF EPOXY
 PAINT SHALL BE CALLED OUT IN THE FINISH
 LEGEND OR FINISH NOTES. SECTION 104.2.1.
 5. SHT A6.0 DETAIL #1 TO REFLECT FIG. 31
 CHAPTER 11. INDICATE ALL MEASUREMENTS AS
 SHOWN IN FIG. 31. (SEE DETAIL 13/A9.0) -
 RESPONSE NOTED, BUT LAYOUT STILL DOES
 NOT COMPLY. 27" MEASUREMENT FOR
 CLEARANCE SHOWN ABOVE THE SINK.
 **NEW COMMENT** SINK DEPTH TO BE 6-1/2"
 MAXIMUM. PLEASE INDICATE ON DETAIL.
 11-4.24.4
  
 NEW COMMENT:
 1B. SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS 533.80(2)(B).
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-06-09 Cont ID  
Sent By kstevens Date 2005-06-09 Time 08:18 Rev Time 2.00
Received By kstevens Date 2005-06-08 Time 17:06 Sent To  
Notes
2005-06-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
  
 1. SHT A1.0 IN THE INSTALLATION OR
 REMOVAL OF ANY PART OF THE DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 SECTION 704.5 - ALL DEMO'D PIPING SHALL
 BE INSPECTED PRIOR TO COVERING.
 2. SHT A3.0 MINIMUM FACILITIES TABLE
 403.1. 3 DRINKING FOUNTAINS ARE REQUIRED
 BUT ONLY 2 ARE SHOWN.
 3. SHT A3.0 SHOW CLEAR FLOOR SAPCE FOR
 ALL ACCESSIBLE FIXTURES IN THE TOILET
 ROOMS AND LOUNGES. PER SECTIONS 11-4.16,
 11-4.19, 11-4.22, & 11-4.24. THE CLEAR
 FLOOR SPACE FOR THE LOUNGE SINKS SHALL
 BE FORWARD APPROACH AND EXTEND A MAXIMUM
 OF 19" UNDERNEATH THE SINK. CABINET
 DOORS ARE NOT APPROVED AS THEY WILL BE
 IN THE CLEAR FLOOR SPACE OF THE FIXTURE.
 OPENING UNDER THE SINK SHALL BE MINIMUM
 OF 30" AND SHALL BE INDICATED ON PLANS.
 4. SHT A5.0 WALL TO BE NON-ABSORBENT PER
 SECTION 1204.2. INDICATE HOW PAINTED GWB
 WILL COMPLY WITH THIS REQUIREMENT. ROOMS
 119A, 120, 187, & 188.
 5. SHT A6.0 DETAIL #1 TO REFLECT FIG 31
 CHAPTER 11. TOE CLEARANCE 6" MAX, PLANS
 TO 1'0". (SEE DETAIL 13/A9.0).
 6. SHT P0.1 DOMESTIC WATER ISOMETRIC,
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT IN THE CEILING AS SHOWN. PDI-WH 201
 - SANT. ISOMETRIC INDICATES ROOM 186,
 BUT NEEDS TO BE FOR ROOM 188. PLEASE
 CORRECT. SECTION 104.2.1.
 7. SHT P2.1 ANY PORTION OF THE DRAINAGE
 SYSTEM INSTALLED UNDERGROUND SHALL BE
 NOT LESS THAN 2" IN DIAMETER. THE
 CONDENSATE LINES INDICATE 3/4", 1-1/4" &
 1-1/2" UNDERGROUND PIPING. SECTION 710.3
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]