| Plan Review Stops For Permit 05041142 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2005-06-10 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-06-10 |
Time |
09:12 |
Rev Time |
1.00 |
| Received By |
alange |
Date |
2005-06-10 |
Time |
09:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-05-11 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-05-11 |
Time |
09:50 |
Rev Time |
0.75 |
| Received By |
alange |
Date |
2005-05-11 |
Time |
09:40 |
Sent To |
I |
|
| Notes |
| 2005-05-11 00:00:00 | DENIED | | | | | | 1.FBC 1804.1.3 MINIMUM FOOTING SHALL | | | EXTEND 12" BELOW GRADE.PLEASE SHOW ON | | | DETAIL. | | | | | | 2.PLEASE SIGN OWNER/AGENT ON ENERGY | | | CALCS. | | | | | | 3.FBC 2309.6 SHOW SIZE AND LOCATION OF | | | ATTIC ACCESS. | | | | | | 4.PRODUCT APPROVAL WITH QUALITY | | | ASSURANCE FOR PGT SERIES 70 DOOR IS OK | | | BUT THE STATE APPROVAL SUBMITTED IS NOT | | | FOR THAT DOOR.PLEASE REVISE. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | \ | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2005-06-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-06-07 |
Time |
09:09 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-06-07 |
Time |
08:54 |
Sent To |
M |
|
| Notes |
| 2005-06-07 00:00:00 | NEW AHU REPLACING EXISTING. NO NEW A/C | | | LOAD. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-04-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-04-21 |
Time |
17:21 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2005-04-21 |
Time |
17:19 |
Sent To |
M |
|
| Notes |
| 2005-04-21 00:00:00 | ********** UNSAT ********** | | | | | | 1)NOTE: PLEASE PROVIDE LOAD CALCULATIONS | | | FOR EXISTING PANEL/SERVICE PER 220.31B | | | | | | 2) NOTE: PLEASE SEE MISSING RECEPT REQ'D | | | FOR A/C EQUIPMENT. 210.63 | | | | | | 3)NOTE: PLEASE SEE MISSING LIGHTING | | | REQUIRED FOR AHU. 210.70 | | | | | | 4)NOTE: PLEASE SEE MISSING A/C DISC'S | | | PER 440.11. | | | | | | 5)NOTE: PLEASE SEE MISSING RECEPTS PER | | | 210.52 | | | | | | 6)NOTE: PLEASE SEE MISSING MEANS OF | | | EGRESS CONTROL FOR LIGHTING. PLEASE SEE | | | CONTROL FOR ENTERING NEW LIVING FROM | | | EXIST OFFICE(3-WAY SW?). PLEASE ALSO SEE | | | EGRESS CONTROL AND FIXTURE REQUIRED FOR | | | EGRESS FROM NEW LIVING RM AREA TO | | | OUTSIDE. | | | BOTH PER 210.70 | | | | | | 7)NOTE: PLEASE SEE MISSING REQUIRED | | | LICENSE INFORMATION ON TITLE BLOCKS PER | | | FAC 61G1-16.004 AND FS 481.219 | | | PLEASE SEE THIS COMMENTS IS REQUIRED FOR | | | ALL SHEETS AND FOR ALL TRADES WHEATHER | | | OR NOT COMMENT IS MADE BY OTHER | | | REVIEWER(S). | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | ONE SET OF OLD SHEETS SHOULD BE | | | SUBMITTED FOR REFERENCE ONLY. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-05-31 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-05-31 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-05-31 |
Time |
14:06 |
Sent To |
E |
|
| Notes |
| 2005-05-31 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-05-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-05-11 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-05-11 |
Time |
09:54 |
Sent To |
Z |
|
| Notes |
| 2005-05-11 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-05-12 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-05-12 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-04-18 |
Time |
09:24 |
Sent To |
|
|
| Notes |
| 2005-04-18 00:00:00 | TO "E" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2005-09-01 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-09-01 |
Time |
10:58 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2005-09-01 |
Time |
10:57 |
Sent To |
|
|
| Notes |
| 2005-09-01 00:00:00 | REVISION/CHANGE FLEX DUCT TO SQUARE |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2005-06-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-06-07 |
Time |
20:37 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2005-06-07 |
Time |
20:25 |
Sent To |
B |
|
| Notes |
| 2005-06-07 00:00:00 | PLEASE NOTE, PLAN DOES NOT INDICATE | | | SUPPLY OR RETURN AIR FROM THE OFFICE | | | AREA. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2005-04-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-04-22 |
Time |
13:21 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2005-04-22 |
Time |
13:21 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2005-04-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-04-22 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2005-04-22 |
Time |
13:23 |
Sent To |
|
|
| Notes |
| 2005-04-22 00:00:00 | NO PLUMBING WORK OR CONTRACTOR INDICATED | | | WITH BUILDING PERMIT APPLICATION |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2005-05-12 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-05-12 |
Time |
13:59 |
Rev Time |
0.35 |
| Received By |
mmclean |
Date |
2005-05-12 |
Time |
13:59 |
Sent To |
|
|
| Notes |
| 2005-06-07 00:00:00 | PLEASE NOTE, PLAN DOES NOT INDICATE | | | SUPPLY OR RETURN AIR INTO THE OFFICE | | | AREA. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT, PATTY KRAUSS AT (561)805-6719. |
|
|