Plan Review Details - Permit 05041137
Plan Review Stops For Permit 05041137
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-05-16 Cont ID  
Sent By lsmith Date 2005-05-16 Time 15:29 Rev Time 0.25
Received By lsmith Date 2005-05-16 Time 15:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-04 Cont ID  
Sent By lsmith Date 2005-05-04 Time 14:28 Rev Time 0.50
Received By lsmith Date 2005-05-04 Time 14:28 Sent To  
Notes
2005-05-04 00:00:00BUILDING PLAN REVIEW: FAILED
  
 1. SUBMIT DETAIL FOR SLAB FOR GENERATOR.
 SHOW ANCHORING DETAIL, THICKNESS OF
 SLAB.
  
 2. SHOW LOCATION OF PROPANE TANK.
  
 3. SEE NOTES FROM OTHER REVIEWERS
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-04-22 Cont ID  
Sent By btrobaug Date 2005-04-22 Time 11:03 Rev Time 0.50
Received By btrobaug Date 2005-04-22 Time 10:28 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-21 Cont ID  
Sent By adarroug Date 2005-04-21 Time 16:34 Rev Time 0.00
Received By adarroug Date 2005-04-21 Time 16:34 Sent To E
Notes
2005-04-21 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-04-15 Cont ID  
Sent By adarroug Date 2005-04-15 Time 15:51 Rev Time 0.00
Received By adarroug Date 2005-04-15 Time 15:51 Sent To Z
Notes
2005-04-15 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-05-16 Cont ID  
Sent By pkrauss Date 2005-05-16 Time 16:02 Rev Time 0.30
Received By pkrauss Date 2005-05-16 Time 16:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-04-28 Cont ID  
Sent By pkrauss Date 2005-04-28 Time 08:22 Rev Time 0.35
Received By pkrauss Date 2005-04-28 Time 08:02 Sent To B
Notes
2005-04-28 00:00:00DENIED:
 PROVIDE DISTANCE FROM PROPERTY LINES
 BUILDINGAND FRESH AIR INTAKE, DOOR,
 AND WINDOW.
  
 PLAN INDICATES A NEW 1,100 GALLON
 PROPANE TANK.INDICATE LOCATION OF THE
 NEW TANK.ADDITIONAL PERMIT REQUIRED
 FOR THE PROPANE TANK AND PIPING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-04-25 Cont ID  
Sent By jleech Date 2005-04-25 Time 11:14 Rev Time 0.50
Received By jleech Date 2005-04-25 Time 11:14 Sent To M
Notes
2005-04-25 00:00:00LP GAS PERMIT #
 05031548 HAS BEEN APPROVED

Review Stop Z ZONING
Rev No 2 Status P Date 2005-05-16 Cont ID  
Sent By mmclean Date 2005-05-16 Time 15:19 Rev Time 0.00
Received By mmclean Date 2005-05-16 Time 15:19 Sent To B
Notes
2005-05-16 00:00:00GENERATOR IS 3FT WIDE 6FT LONG.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-04-20 Cont ID  
Sent By mmclean Date 2005-04-20 Time 11:57 Rev Time 0.00
Received By mmclean Date 2005-04-20 Time 11:57 Sent To I
Notes
2005-04-20 00:00:00DENIED,
 1. NEED TO PROVIDE THE SETBACK FOR THE
 GENERATOR. (NEED TO KNOW THE DISTANCE
 BETWEEN THE STRUCTURE AND GENERATOR AND
 DISTANCE FROM GENERATOR TO PROPERTY
 LINE).
  
 NOTE: GENERATOR CAN ONLY ENCROACH ONLY
 4FT INTO ANY SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720