Plan Review Details - Permit 05040985
Plan Review Stops For Permit 05040985
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-06-20 Cont ID  
Sent By alange Date 2005-06-20 Time 08:00 Rev Time 1.25
Received By alange Date 2005-06-20 Time 07:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-09 Cont ID  
Sent By alange Date 2005-05-09 Time 13:40 Rev Time 1.00
Received By alange Date 2005-05-09 Time 13:11 Sent To  
Notes
2005-05-09 00:00:00DENIED
  
 1.FBC1804.1.3 THE BOTTOM OF
 FOUNDATIONS SHALL EXTEND NO LESS THAN 12
 INCHES (305 MM) BELOW FINISH GRADE.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
 NOTE: SCOPE OF WORK ON NOC DOES NOT
 REFLECT A ROOM ADDITION. RECORD A NEW
 NOC WITH CORRECTED SCOPE OF WORK.
  
 4.WINDOW "C" NOT ON SCHEDULE SUBMIT
 SIZE AND TYPE OF WINDOW.
  
 5.USP STRAP DTC NOT LISTED IN UPS
 CATALOGE.
  
 6.SUBMIT PRODUCT APPROVALS WITH
 QUALITY ASSURANCE FOR STRAPS AND
 TIE-DOWNS, EXTERIOR BATHROOM DOOR AND
 IMPACT PROTECTION.
 ALL PRODUCT APPROVALS SUBMITTED REQUIRE
 THE FOLLOWING TO BE ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 7. ROOF SHEATHING SHALL COMPLY WITH
 FBC 2306.1 WITH WPB AMMENDMENTS.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-06-15 Cont ID  
Sent By dpalmer Date 2005-06-15 Time 07:36 Rev Time 0.70
Received By dpalmer Date 2005-06-14 Time 19:25 Sent To B
Notes
2005-06-15 00:00:00********** NOTES REDLINED **********
  
 1) PLEASE SEE CIRCUITING OF SD'S. PLEASE
 SEE 2002 NEC 210.12, THESE ARE ALSO
 REQUIRED TO BE ARC FAULT PROTECTED.
  
 2)NOTE: PLEASE SEE PLANS SHOWS THREE
 PANELS, HOWEVER ONLY TWO PANEL SCHEDULES
 AND TWO PANELS ARE SHOWN ON RISER
 DIAGRAM. ALL SHOWN AS EXISTING. THIS IS
 TO BE VERIFIED IN FIELD.
2005-06-14 00:00:00IN FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-04-21 Cont ID  
Sent By dpalmer Date 2005-04-21 Time 15:31 Rev Time 0.50
Received By dpalmer Date 2005-04-21 Time 15:31 Sent To P
Notes
2005-04-21 00:00:00*********** UNSAT **********
  
  
 1)NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
 PLEASE SEE THESE ARE SHOWN AS 15A,
 PLEASE ALSO SEE NO WIRE SIZES ARE SHOWN
 ON PANEL SCHEDULE.
  
 2 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 PLEASE SEE 210.12 2002 NEC.
  
 3)NOTE: PLEASE SEE MISSING RECEPT(S) PER
 210.52 FOR WALL SPACE IN BEDRM. IF
 EXSITING PLEASE LABEL.
  
 4)NOTE: PLEASE CLARIFY NEW OR EXISTING
 SD'S REQUIRED INSIDE AND OUT SIDE
 BEDROOM. NFPA-72 8-1.4.1.6.2
  
 5)NOTE: PLEASE SEE MISSING GFI RECEPT
 W/IN 3' OF SINK/LAV EDGE.
 210.52
  
 6)NOTE: PLEASE SEE PLANS ARE SHOWING
 PANEL, SUB PANELS ETC, HOWEVER THERE IS
 NO INDICATION IF THESE ARE EXISTING. ?
 PLEASE INCLUDE A COMPLETE RISER DIAGRAM
 310.16,240.4,250.50,110.9 ETC.
  
 7)NOTE: PLEASE SEE PANEL AND MCB IS
 SHOWN AS 210A'S? PLEASE SEE 240.6, 210A
 OCP IS NOT A COMMON OCP SIZE.
 PLEASE ADJUST.
  
 8)NOTE: PLEASE VERIFY NEW OR EXISTING
 EGRESS LIGHTING REQUIRED IN BEDRM.
 210.70,LS 101 5-8
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE SET OF OLD/VOIDED
 SHEETS FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-09-13 Cont ID  
Sent By adarroug Date 2005-09-13 Time 13:45 Rev Time 0.00
Received By adarroug Date 2005-09-13 Time 13:45 Sent To B
Notes
2005-09-13 00:00:00TO "KCONRAD" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-03 Cont ID  
Sent By shill Date 2005-06-03 Time 16:04 Rev Time 0.00
Received By shill Date 2005-06-03 Time 16:04 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-28 Cont ID  
Sent By adarroug Date 2005-04-28 Time 12:59 Rev Time 0.00
Received By adarroug Date 2005-04-28 Time 12:59 Sent To B
Notes
2005-04-28 00:00:00TO "B-RESIDENTIAL" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-09 Cont ID  
Sent By alange Date 2005-05-09 Time 14:00 Rev Time 0.00
Received By alange Date 2005-04-18 Time 15:43 Sent To  
Notes
2005-04-18 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-10-11 Cont ID  
Sent By pkrauss Date 2005-10-11 Time 13:33 Rev Time 0.30
Received By pkrauss Date 2005-10-11 Time 13:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-04-28 Cont ID  
Sent By pkrauss Date 2005-04-28 Time 07:47 Rev Time 0.25
Received By pkrauss Date 2005-04-28 Time 07:36 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-04-25 Cont ID  
Sent By jleech Date 2005-04-25 Time 13:28 Rev Time 0.50
Received By jleech Date 2005-04-25 Time 13:28 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-04-28 Cont ID  
Sent By mmclean Date 2005-04-28 Time 10:56 Rev Time 0.00
Received By mmclean Date 2005-04-28 Time 10:56 Sent To I
Notes
***NONE***