| 2005-05-03 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. - PIPE SIZING OUT OF THE |
| | PRV THRU THE TEE FOR CHAR GRILLE IS |
| | SHOWN AS 1" BUT SHALL BE 1-1/4" PER |
| | TABLE 402(2) |
| | 2. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). - GAS CLACULATIONS SHOW |
| | DIFFERENT BTU RATINGS FOR CHAR GRILLE |
| | AND GRIDDLE THAN IS SHOWN ON THE |
| | ISOMETRIC. PLEASE CORRELATE CALCULATIONS |
| | & ISOMETRIC. SECTION 104.2.1. |
| | 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | 4. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. - SHOW THE |
| | UNION ON THE ISOMETRIC. SECTION 104.2.1. |
| | 5. GAS PERMIT SHALL NOT BE ISSUED UNTIL |
| | ARCHITECTURAL PLANS SHOWING THE FLOOR |
| | PLAN WITH ALL SEATING, SQUARE FOOTAGE OF |
| | INTERIOR, EXISTING TOILET ROOM |
| | FACILITIES ECT. INDICATE IF ALL KITCHEN |
| | FACILITIES ARE EXISTING OR NEW. THESE |
| | PLANS SHALL BE ROUTED TO DBPR DEPT. OF |
| | BUSINESS REGULATION HOTEL & RESTURANT |
| | DIVISION. TWO SETS OF PLANS SHALL BE |
| | STAMPED BY DBPR PLAN REVIEW AND HAVE THE |
| | TWO PAGE "WORK SHEETS" ATTACHED. SECTION |
| | 101.4.7. |
| | 6) CERTIFICATE OF AUTHORIZATION IS |
| | REQUIRED FOR METRO DESIGN REFERENCED IN |
| | THE TITLE BLOCK. FAC61G15-23.002(2) AND |
| | FS 471.025. |
| | |