Plan Review Details - Permit 05040948
Plan Review Stops For Permit 05040948
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-23 Cont ID  
Sent By jwitmer Date 2005-05-23 Time 16:27 Rev Time 12.00
Received By jwitmer Date 2005-05-23 Time 16:27 Sent To  
Notes
2005-05-24 00:00:00BUILDING PLAN REVIEW
 PERMIT:05040948"STAYBRIDGE"
 ADD: 2200 45TH STREET
 CONT: PLAN REVIEW
 TEL: (727)639-3598
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) ONCE PLANS ARE READY FOR ISSUANCE A
 NOC WILL BE REQUIRED.PROVIDE NOC
 RECORDED WITH THE CLERK OF COURT BEFORE
 A PERMIT CAN BE ISSUED.
  
 2)FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3) FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGEN-
 CY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESH-
 OLD BUILDING. THE PURPOSE OF THE SRUCTUR
 AL INSPECTION PLAN IS TO PROVIDE SPECIF-
 IC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 4) WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 5)W.P.B. AMENDMENT 105.13.4.4 ALL
 PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CON-
 TAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY WITH
 THE APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 6) NOTE, FOR ALL PLANS, REPORTS, PRODUCT
 APPROVALS, SHOP DRAWINGS REVISIONS AND
 SUBMITTALS PROVIDE (3) COPIES OF ALL
 DOCUMENTS.
  
 7) FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
 THE P.E. DID SIGN THE ENERGY FORM BUT
 WHEN SUBMITTED FOR PUBLIC RECORD:
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 8) SHEET 0.02 BUILDING DATA, TYPE V,
 1 HR PROTECTED/ "SPRINKLERED". SEE TABLE
 600 FOR RATING.
  
 9) SHEET INDEX PLANS INDICATE THAT THE
 BUILDING IS TO BE FIRE SPRINKLERED,
 PROVIDE PLANS AND CALCULATIONS.
 903.8.1. ANY BUILDINGS WHICH IS 3
 STORIES OR MORE HEIGHT SHALL BE EQUIPPED
 WITH AN APPROVED AUTOMATIC SPRINKLER
 SYSTEM IN ACCORDANCE WITH 903.1.NOTE FOR
 A (4) STORY BUILDING A 13R SYSTEM CAN BE
 USED.
  
 10) SHEET A0.05:
 A) 4.8.3 RAMPS 4.8.3 REQUIRE 44" IF
 PART OF A MEANS OF EGRESS.
 B) 4.8(2) FL. LAW TOP LANDING REQUIRES
 60" AT THE TOP LANDING AND 72" CLEAR RUN
 FOR THE BOTTOM LANDING.
 C) 4.8(3) / FIGURE 17, SAME AS ABOVE
 REQUIRING 44" IF PART OF A MEANS OF
 EGRESS.
  
 11) SHEET A0.06 FIGURE 28 THE 3RD FIGURE
 TO THE RIGHT, WHERE THE PLAN INDICATES
 THE W.C. IS 18", THIS IS AN ABSOLUTE NOT
 A MINIMUM.
  
 12) SHEET A0.06 4.3.3 WIDTH SEE
 EXCEPTION 44" IF PART OF A MEANS OF
 EGRESS.
  
 13) SHEET A0.04 NOTE, POOL, SPA ,FENCE &
 SIGNAGE REQUIRE A SEPERATE PERMIT.
  
 14) SHEET A-1.06DETAIL#2PLANS INDICATE
 USE OF ASPHALT/ FIBERGLASS COMPOSITE
 ROOF SHINGLES, THE PRODUCT APPROVAL WAS
 TESTED UNDER PA 110 WHICH LIMITS THE USE
 TO A HEIGHT OF 33'. SEE LIMITATIONS 3.2.
 SEE A-10.09 DADE-COUNTY NOA LIMITATIONS
 3.1.
  
 15 FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THERE ARE DETAILS FOR STO EFIS SYSTEMS
 BUT THE PRODUCT APPROVALS SUBMITTED ARE
 FOR DRYVIT, WHICH WILL BE USED.
  
 16) THE EFIS DETAILS USED ON A6.06-
 A6.08 DO NOT INDICATE WHAT TYPE OF WALL
 SHEATHING IS TO BE USEDNOR INTERIOR
 FINISH MATERIAL NOR THICKNESS, TABLE 600
 1 HR RATED FOR NON-LOADBEARING WALLS.
 PROVIDE UL RATING.
  
 17) A-6.08 DRAWING # 2.11,INDICATE
 COMPLIANCE,?1804.6.2.7.2 FOAM PLASTIC
 INSULATION SHALL BE PERMITTED BELOW
 GRADE ON FOUNDATION WALLS IN ACCORDANCE
 WITH ONE OF THE FOLLOWING CONDITIONS:
  
 1. WHEN IN ADDITION TO THE REQUIREMENTS
 OF ?2304.1.2, AN APPROVED METHOD OF
 PROTECTING THE FOAM PLASTIC AND
 STRUCTURE FROM SUBTERRANEAN TERMITE
 DAMAGE IS PROVIDED.
 2. WITHIN TYPES I, II AND IV
 CONSTRUCTION.
 3. ON THE INTERIOR SIDE OF BASEMENT
 WALLS.
  
 18) MISSING SHEETS S-0.01, S-0.02, S0.03
 & S1.01?
  
 19) FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 20A) SHEET S0.03, THE SIMPLIFIED
 PRESSURES INDICATED IN TABLE 1606.2 CAN
 ONLY BE USED TO 30' WITH MULTIPLIERS TO
 60'. DEPENDING ON THE POSITIVE &
 NEGATIVE PRESSURES REQUIRED FOR THIS
 BUILDING THE DRYVIT EFIS SYSTEM
 MAY BE LOW IN PRESSURES.THIS BUILDING
 HAS A MEAN ROOF HEIGHT OF 51'-0.
  
 20B) THE ARCHITECT DOES NOT INDICATE HOW
 HE DESIGNED THE BUILDING (WIND)AT ALL?
  
 20C) PLEASE INDICATE ON THE ELEVATIONS
 THE POSITVE & NEGATIVE PRESSURES, FOR
 THE WINDOWS, DOORS EFIS & ROOFING,
 INTERIOR ZONES AS WELL AS END ZONES.
 1606.1.1.
  
 21A) A-5.14 THE LAUNDRY CHUTE DOESN'T
 PROVIDE WHAT TYPE OF METAL FRAMING IS TO
 BE USED FOR THE CHIMNEYABOVE THE ROOF
 LINE.
 21B) NO INFORMATION ON HURRICANE
 STRAPPING FOR FRAMED CHIMNEY.
 21C) SHEET A5.07 DETAIL# 9 INDICATES USE
 OF WOOD 2X IN THE 2 HR SHAFT, AND WOOD
 WALL ABOVE THE ROOF LINE, IF SO PROVIDE
 THE UL LISTING.
  
 22) SHEET A6.03 ELEVATOR VENTING:
 A)IS A CONTINUATION OF THE 2HR RATED
 SHAFT, TABLE 705.2.1, PROVIDE THE 2 HR
 SHAFTRATING THROUGH TOBUT NOT
 INCLUDING THE CURB MOUNTED ON THE ROOF.
  
 B) PROVIDE ANCHORING (STRAPPING) DETAILS
  
 C) INDICATE THE STRTCHER REQUIREMENTS
 IN ONE OF THE ELEVATORS DETAILS:
 ?3003.4.1 IN ALL STRUCTURES THAT ARE
 MORE THAN THREE STORIES HIGH OR IN
 WHICH THE VERTICAL DISTANCE BETWEEN
 THE BOTTOM TERMINAL LANDING AND THE
 TOP TERMINAL LANDING EXCEEDS 25 FEET
 (7.6 M) MUST BE CONSTRUCTED TO
 CONTAIN AT LEAST ONE PASSENGER
 ELEVATOR THAT IS OPERATIONAL AND WILL
 ACCOMMODATE AN AMBULANCE STRETCHER 76
 INCHES (1931 MM) LONG AND 24 INCHES
 (610 MM) WIDE IN THE HORIZONTAL
 POSITION.THIS ELEVATOR SHALL BE
 IDENTIFIED.
  
 23) PROVIDE DETAILS OF HOW THE EXHAUST
 DUCTS WILL BE VENTED TO THE ROOF. TABLE
 705.1.2 REEQUIRES 2 HR RATING FOR
 SHAFTS.
  
 24)) SHEETA-6.02 DETAIL 1 STAIR
 HANDRAILS:A) 11-4.9.4(1) HANDRAILS
 SHALL BE CONTINUOUS ALONG BOTH SIDES OF
 STAIRS. THE INSIDE HANDRAIL ON
 SWITCHBACK OR DOGLEG STAIRS SHALL ALWAYS
 BE CONTINUOUS SEE FIGURE 11-19(A) &
 FIGURE 11-19(B)).
  
 B) SAME SHEET DETAIL NUMBER 10:
 11-4.9.4(2) AT THE BOTTOM, THE HANDRAIL
 SHALL CONTINUE TO SLOPE FOR A DISTANCE
 OF THE WIDTH OF ONE TREAD FROM THE
 BOTTOM RISER; THE REMAINDER OF THE
 EXTENSION SHALL BE HORIZONTAL (SEE
 FIGURE 11-19(C) AND FIGURE 11-19(D)).
 HANDRAIL EXTENSIONS SHALL COMPLY WITH
 11-4.4.
  
  
  
  
 25 A-9.06 THE DOOR SCHEDULE INDICATES
 ALL STAIRWELL DOORS AS 60 MIN, TABLE
 705.1.2 REQUIRES 1 1/2 HR RATED DOORS
 FOR 2 HR RATED WALLS.
  
 26A) SHEET A-5.15/A-5.16, THERE IS A
 DISCREPANCY, ONE SHEET INDICATES A FLUE
 THE OTHER A VENTLESS SYSTEM.
 B) PROVIDE THE MANUFACTURES SPEC FOR
 THE VENTLESS FIREPLACE:SECTION 2809
 GAS APPLIANCES:GAS APPLIANCES SHALL BE
 INSTALLED AND VENTED IN ACCORDANCE WITH
 THE REQUIREMENTS OF THE FLORIDA BUILDING
 CODE, FUEL GAS.
  
 27)THE PLANS APPEARS TO HAVE ALOT OF
 DOORS ON THE FIRST FLOOR MISSING THE 18"
 CLEARENCE ON THE LATCH SIDE(PULL) OF THE
 DOOR, PLANS RED LINED.11-4.13.6
 MANEUVERING CLEARENCES AT DOORS. MINIMUM
 MANEUVERING CLEARENCES AT DOORS THAT ARE
 NOT AUTOMATIC OR POWER-ASSISTED SHALL BE
 AS SHOWN IN FIG. 25. THEFLOOR OR
 GROUND AREA WITH IN THE REQUIRED
 CLEARENCES SHALL BE CLEAR & LEVEL.
  
 28) SHEET A-2.01/ A-2.02 RESTROOM# 111 &
 112 ARE MISSING THE CLEAR FLOOR SPACE IN
 FRONT OF THE LAV, 11-4.24.5.
  
 29)SHEET A-10.11/ A-10.12 SUBMITTED A
 ROOFING REPORT FOR NON STRUCTURAL METAL
 ROOFING. THIS REPORT PRESSURE ISGOOD
 FOR ONLY 52.5 PSF. THIS ROOF WILL
 ENCOUNTER HIGHER PRESSURES THAN THIS IN
 ROOF ZONES 2 AND 3. SECOND PROBLEM THE
 ENGINEERING SHEETS THAT TIE TO THE FL
 COVERSHEET FROM C-BUCK ENGINEERING WERE
 NEVER SUBMITTED.
  
 30) SHEET A-10.13/ A-10.14 ARE FOR PGT
 HORIZONTAL SLIDERS ,THE FL COVERSHEET
 INDICATES THIS IS A NON-IMPACTWINDOW,
 SEE HIGHLIGHTED NOA# INDICATING NON-
 IMPACT RATING. THE SECOND ISSUE INDICATE
 WHICH TYPE OF GLAZING TO BE INSTALLED
 FOR PRESSURE RATINGS, MAY BE LOW VALUES.
  
 31) SHEET A-10.15/ A-10.16 SUBMITTED
 SHEETS FOR PGT FIXED GLAZING, INDICATE
 WHICH GLAZING SHALL BE USED TO SEE IF
 THE PRESSURES ARE MET.
  
 32)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) FIXED WINDOWS
 B) HORIZONTAL SLIDERS
 C) SWING DOORS- GLAZED
 D) SWING DOORS-SOLID
 E) MULLIONS
 F) LOUVERS
 G) EFIS SYSTEMS
 H) TRUSS ANCHORS
 I) ROOFING ASSEMBLIES
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 33)1707.4.3 EACH EXTERIOR DOOR ASSEMBLY
 NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 34) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 35) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 36) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED, SHEET
 S-101 INDICATES THAT THE FOUNDATION
 DESIGN IS INCOMPLETE DEPENDING ON THE
 SOILS REPORT? PLANS DO NOT PROVIDE
 INFORMATION ON CAST IN PLACE CONCRETE
 PILES, LOCATION, GROUT, ETC.
  
 37) S-2.02 SECTION B PORT COCHERE
 INDICATES THE USE OF WOOD TRUSSES AND
 WOOD SHEATHING, TYPE II BUILDING, SEE
 TABLE 600 ROOFS & ROOF /CEILING
 ASSEMBLIES FOOTNOTE "E".
  
 38) S1.04 ROOF TRUSSES:
 A) PROVIDE UPLIFT FOR THE ROOF FRAMING
 MEMBERS, DIRECTION,MAGNITUDE OF THE
 LOADS TO BE RESISTED.1606.1.1/ 1606.1.3,
 PART OF THE MAIN WIND FORCE RESISTING
 SYSTEM.
 B)1707.3.1 JOIST HANGERS, FRAMING
 ANCHORS & SIMILAR DEVICES SHALL BE TEST-
 ED IN ACCORDANCE W/ ASTM D 1761 & BE
 LABELED AND LISTED FOR THEIR LOAD CARRY-
 ING CAPACITY.
 C) 1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREASE IN ALLOWABLE STRESS
 SPECIFIED IN THE MATERIALS SECTIONS OF
 THIS CODE OR A REFRENCED STANDARD SHALL
 NOT BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23 (WOOD).
  
 39) SHEET M101-105 GENERAL NOTES
 INDICATE "PROVIDE A CONCEALED CONDENSATE
 STACK WITHIN THE OUTSIDE WALL, PROVIDE
 ADDITIONAL INFORMATION, ?705.6
 PENETRATIONS OF HORIZONTAL ASSEMBLIES.
 ALL PENETRATIONS OF A FLOOR, FLOOR
 / CEILING ASSEMBLY, OR THE CEILING
 MEMBRANE OF A ROOF/CEILING ASSEMBLY
 SHALL BE PROTECTED BY A SHAFT ENCLOSURE
 IN ACCORDANCE WITH 705.2 OR
 SHALL COMPLY WITH 705.6.1 THROUGH
 705.6.4. 705.6.1 THROUGH
 PENETRATIONS. THROUGH-PENETRATIONS OF
 FIRE RATEDHORIZONTAL ASSEMBLIES SHALL
 COMPLY WITH 705.6.1.1 OR 705.6.1.2.
  
 40) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET M-301 INDICATES THE USE OF ROOFTOP
 MAKE UP AIR AND EXHAUST UNITS, PROVIDE
 THE FRAMING AND ANCHORING DETAILS.
  
 41) SHEET A-5.06 COVERED ENTRY INDICATES
 THE USE OF STEEL TRUSSES AND TOUNGE AND
 GROOVE DECKING NO NO ADDITIONAL
 INFORMATION?
  
 42)DAVID I WALLACE & ASSOCIATES, P. A.,
 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING
 ARCHITECTURAL SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 43)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 44) ADDITIONAL FEES DUE, CALCULATED
 VALUE FOR THIS BUILDING IS :
 $6,776,174.00
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-03 Cont ID  
Sent By dpalmer Date 2005-05-03 Time 08:14 Rev Time 6.00
Received By dpalmer Date 2005-04-27 Time 14:42 Sent To  
Notes
2005-05-03 00:00:00*********** UNSAT *************
  
 ** REVIEW FOR STAYBRIDGE SUITES ***
 THIS IS UBMITTED FOR PLAN REVIEW ONLY
 AND NOT SUBMITTED FOR PERMIT.
 PLEASE SEE THIS WAS SUBMITTED UDNER THE
 SAME ADDRESS AS THE "FAIRFILED INN
 SUITES".
  
 1)NOTE: PLEASE SEE 240.4C
 WHERE THE OVERCURRENT DEVICE IS RATED
 OVER 800 AMPERES, THE AMPACITY OF THE
 CONDUCTORS IT PROTECTS SHALL BE EQUAL TO
 OR GREATER THAN THE RATING OF THE
 OVERCURRENT DEVICE DEFINED IN 240.6.
 PLEASE SEE CONDUCTORS SHOWN ARE ONLY
 RATED FOR 2100A'S.
 310.15,110.14C1
  
 2)NOTE: PLEASE IDENTIFY FOOTER STEEL AS
 PART OF THE GROUNDING ELECTRODE SYSTEM
 AS REQUIRED UNDER 250.50.
  
 3)NOTE: PLEASEMSB MAY HAVE AN
 ADDITIONAL "SHUNT TRIP" , HOWEVER THE
 MCB MUST STILL MEET 230.76,230.79.
 PLEASE NOTE ON PLANS/RISER/PANEL
 SCHEDULE.
  
 4)NOTE: PLEASE SEE FEEDERS SHOWN ON
 RISER DIAGRAM FOR PANEL "M". THIS NOTES
 FEEDER SCHEDULE #28. PLEASE SEE OCP FROM
 MSB IS 600A'S AND FEEDER IS ONLY RATED
 FOR 380A'S.
 310.16,240.4
  
 5)NOTE: PLEASE SEE GROUND FLR ELECTRICAL
 ROOM DOORS. PLEASE SEE REQUIRED
 "OUT-SWING" FOR DOORS PER 110.26. PLEASE
 ALSO NOTE ON PLANS FOR PANIC HARDWARE
 REQUIRED ETC.
  
 6)NOTE: PLEASE CLARIFY ARC FAULT
 PROTECTION PER 210.12 2002 NEC.
 PLEASE SEE INDIVIDUAL UNITS ARE NOT
 LABELED FOR CIRCUITING, IT IS UNCLEAR
 WHEATHER ARC FAULT PROTECTION IS
 PROVIDED FOR ALL RECEPTS, LTS ETC.
  
 7)NOTE: PLEASE PROVIDE CIRCUITING ON
 UNIT LAYOUTS AND COORELATE WITH THE
 PANEL SCHEDULES SUBMITTED.
 CIRCUITING SHOWN ON POWER PLANS DO NOT
 ISOLATE.
  
 8)NOTE: PLEASE SEE 2002 NEC FOR GFI
 PROTECTION OF RECEPTS IN KITCHENS.
 PLEASE SEE KITCHEN AREA IN BREAKRM, AND
 KITCHEN AREA FOR BUFFET AREA.
 210.8B3
  
 9)NOTE: PLEASE SEE 210.60, ALL RECEPTS
 IN "GUEST RMS" AND SUITES ARE TO MEET
 210.52. PLEASE SEE THERE ARE SOME
 EXCEPTIONS PERMITTED, HOWEVER THERE
 APPEARS TO BE SOME MISSING.
 PLEASE SEE 2' OF WALL SPACES WOULD BE
 REQUIRED UNDER 210.52, PLEASE SEE
 PENINSULAR IN KITCHENS ALSO PER 210.52C3
  
 10)NOTE: PLEASE PROVIDE WIND LOADING FOR
 SITE LIGHTING POLES.
 THIS WILL BE REQUIRED AT THIS TIME AND
 REVIEWED BY BLDG PLAN REVIEW TO MEET FBC
 140MPH.
  
 11)NOTE: PLEASE CLARIFY WHERE ELEVATOR
 MACHINE RM LIGHTING CAN BE LOCATED.
 PLEASE SEE 620.23,24 FOR MIN REQUIRED
 BRANCH CIRCUITS. ELEV CLOSET RECEPT
 BRANCH CIRCUIT WAS LOCATED.
  
 12)NOTE: PLEASE SEE PANEL "P" MENTIONS
 "IN ELECTRICAL ROOM" BUT THIS PANEL
 COULD NOT BE LOCATED ON PLANS IN ANY OF
 THE ELECTRICAL ROOMS SHOWN. PLEASE
 CLARIFY??
 215.5
  
 13)NOTE: PLEASE BE SURE TO SEE ANY
 POSSIBLE COMMENTS FROM OTHER REVIEWER(S)
 WHICH MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 14)NOTE: PLEASE BE SURE TO REMOVE ANY
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
2005-05-02 00:00:00NOTES TO FOLLOW.5/2/05
2005-04-27 00:00:001 ROLL IN ELEC FOR REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2005-06-03 Cont ID  
Sent By mamini Date 2005-06-03 Time 10:25 Rev Time 0.55
Received By mamini Date 2005-06-03 Time 10:25 Sent To  
Notes
2005-06-03 00:00:00FAILED:
  
 1. PLEASE SUBMIT CIVIL PLANS FOR OUR
 REVIEW AND APPROVAL.NOTE THAT STORM
 WATER CALCULATIONS FOR ENTIRE SITE AND
 POLLUTION PREVENTION PLANS SHOULD BE
 INCLUDED IN THIS SUBMITTAL.
 2. PLEASE SUBMIT CIVIL PLANS TO THE
 PUBLIC UTILITIES AND ENGINEERING FOR
 THEIR APPROVAL OF THE CONNECTIONS TO THE
 CITY' SERVICES, ATT; MANNY GONZALEZ,
 494-1085. NOTE THAT CIVIL PLANS MUST BE
 APPROVED BY THEM PRIOR TO GETTING PERMIT
 FROM THE CONSTRUCTION SERVICES DEPT.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-06-02 Cont ID  
Sent By mwennerg Date 2005-06-02 Time 15:22 Rev Time 0.00
Received By mwennerg Date 2005-06-02 Time 15:22 Sent To  
Notes
2005-06-02 00:00:00****FAILED****
  
 1) LOCKING CAPS ARE REQUIRED ON THE FIRE
 DEPARTMENT CONNECTION.
  
 2) LIFE SAFETY SHALL COMPLY WITH NFPA
 101, 2003 EDITION.
  
 3) ALL CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 4) SEPARATE SHOP DRAWING AND PERMITS ARE
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS.
  
 5) NEW FIRE ALARM SYSTEMS SHALL BE
 MONITORED FOR UL CERTIFIED CENTRAL
 STATION SERVICE.
  
 6) TEMPORARY STANDPIPES ARE REQUIRED
 WHEN THE BUILDING REACHES 3 STORIES OR
 30 FEET IN HEIGHT.
  
 7) FIRE DEPARTMENT CONNECTIONS MUST
 REMAIN ACCESSIBLE, AND BE LOCATED NO
 FURTHER THAN 150' FROM THE CLOSEST FIRE
 HYDRANT.
  
 8) PLEASE INDICATE THE OCCUPANT LOAD FOR
 THE POOL AND DECK AREAS.
  
 9) PLEASE PROVIDE THE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR ALL HANDRAILS
 AND GUARDRAILS.
  
 10) PLEASE PROVIDE MORE DETAILS IN
 REGARDS TO THE CARD READERS, AND WHAT
 ISSUES IF ANY WILL THEY RAISE IN
 EXITING.
  
 11) 2A-10B,C FIRE EXTINGUISHERS SHALL BE
 PLACED TO SATISFY THE 75' TRAVEL
 DISTANCE REQUIREMENT.
  
 12) TACTILE SIGNAGE IS REQUIRED AT ALL
 EXIT DOORS.
  
 13) IT APPEARS THAT ADDITIONAL EXIT
 SIGNS WILL BE NEEDED TO SATISFY THE 100'
 TRAVEL REQUIREMENT BETWEEN SIGNS.
  
 14) AN ADDRESS NUMBER IS REQUIRED TO BE
 INSTALLED ON THE BUILDING, A MINIMUM OF
 6" IN HEIGHT AND CONTRASTING TO THE
 BACKGROUND.
  
 15) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION OF THE WALLS AND
 CEILINGS.
  
 16) LOCAL REQUIREMENTS REQUIRE THE DUCT
 SMOKE DETECTORS TO BE WIRED INTO THE
 FIRE ALARM SYSTEM TO CAUSE A GENERAL
 FIRE ALARM, AND NOT A SUPERVISORY
 SIGNAL.
  
 17) A CHAIN AND LOCK IN ADDITION TO
 ELECTRONIC SUPERVISION WILL BE REQUIRED
 ON THE DOUBLE CHECK DETECTOR ASSEMBLY.
  
 18) PLEASE ILLUSTRATE STRETCHER
 ACCESSIBILITY IN ELEVATORS.
  
 19) PLEASE SHOW THE LOCATIONS OF LIVING
 UNIT SINGLE STATION SMOKE DETECTORS.
  
 20) ARE THE ELEVATOR LOBBIES ABOVE THE
 FLOOR OF EXIT DISCHARGE FIRE RATED?
  
 21) A KNOX BOX WILL BE REQUIRED.
  
 22) PLEASE SHOW EXISTING AND NEW FIRE
 HYDRANT LOCATIONS.
  
 23) NO FIRE PROTECTION OF LIFE SAFETY
 DRAWINGS WERE SUBMITTED.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2951 OR 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-07 Cont ID  
Sent By shill Date 2005-06-07 Time 13:37 Rev Time 0.00
Received By shill Date 2005-06-07 Time 13:37 Sent To Z
Notes
2005-06-07 00:00:00PERMIT APPLICATION SENT TO ZONING BOX
 PLANS ON SHELF
 EMAILED SHIRLEY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-13 Cont ID  
Sent By mmclean Date 2005-06-13 Time 08:54 Rev Time 0.00
Received By mmclean Date 2005-04-18 Time 14:13 Sent To  
Notes
2005-04-18 00:00:00TO "COMM" BD#42/PLANS ON "COMM" RACK

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-05-15 Cont ID  
Sent By hmoser Date 2005-05-15 Time   Rev Time 0.00
Received By hmoser Date 2005-05-15 Time 12:52 Sent To  
Notes
2005-05-15 00:00:00PLAN DENIED
 1) PLEASE SHOW RETURN AIR LOCATION
 ANDDUCT SIZES.
 2)PLEASE INDICATE FRESH AIR ON PLANS.
 3) PLEASE SUPPLY MANUFACTURE
 INSTALLATION INSTRUCTIONS ON VPAC UNITS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-06-03 Cont ID  
Sent By kstevens Date 2005-06-03 Time 08:00 Rev Time 10.25
Received By kstevens Date 2005-06-02 Time 18:52 Sent To  
Notes
2005-06-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL CODE
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. PLANS SHALL BE ROUTED TO DBPR HOTEL &
 RESTURANT DIVISION FOR REVIEW PRIOR TO
 RESUBMITTING TO THE CITY WPB FOR REVIEW.
 SUBMIT A MINIMUM OF 3 SETS OF PLANS
 STAMPED BY DBPR WITH THE TWO PAGE "WORK
 SHEETS" ATTACHED TO EACH SET. SECTION
 101.4.7.
 2. INDICATE IF FOOD WILL BE PREPARED ON
 SITE OR IF ALL FOOD WILL BE PREPACKAGED
 FOOD FOR COMSUMPTION. TO DETERMINE IF A
 GREASE INTERCEPTOR IS REQUIRED CONTACT
 RODNEY COMPO, ENVIRONMENTAL COMPLIANCE.
 (561) 473-4074, FAX (561) 659-7458, OR
 E-MAIL [email protected]. PLEASE SUBMIT HIS
 DETERMINATION WITH PLANS.
 3. SHT A-0.04 SEPARATE POOL PERMIT
 REQUIRED. SECTION 104.1.1.
 4. SHT A0.06 TUB & SHOWER DETAIL, SHOW
 MEASURMENTS FOR CONTROLS. SECTIONS
 11-4.20.5 & 11-4.21.5.
 5. SHTS A-2.01 & A-2.02 TOILET ROOMS.
 SHOW CLEAR FLOOR SPACE FOR EACH
 ACCESSIBLE FIXTURE. SHOW TURNING AREA IN
 EACH TOILET ROOM, NOT REQUIRED IN STALL.
 SECTION 11-4.22.3
 6. SHTS A-2.01 & A-2.02 SUBMIT
 CALCULATIONS FOR MINIMUM FACILITIES PER
 TABLES 1103.1 & 403.1 FOR ALL COMMON
 AREAS. SHOW THE SQUARE FOOTAGE OF EACH
 COMMON AREA ON THE FLOOR PLAN.
 7. SHT A-2.02 SINK IN EMPLOYEE BREAK
 ROOM SHALL COMPLY WITH SECTION 11-4.24
 AND ALL SUBSECTIONS. (FORWARD APPROACH
 IS REQUIRED MAXIMUM 19" UNDERNEATH THE
 SINK. SINK SHALL BE CENTERED ON THE 30"
 WIDTH OF THE CLEAR FLOOR SPACE).
 8. PER TABLE 403.1 A SERVICE SINK IS
 REQUIRED.
 9. SHTS A-2.10 & A-2.11 SEE COMMENT #5
 CONCERNING REQUIRED TURNING AREA.
 10. ALL RAIN WATER DOWNSPOUTS AND
 CONDENSATE SHALL DRAIN A MINIMUM OF 1FT
 FROM THE STRUCTURAL WALL. SECTION
 1503.4.4.
 11. SHT A-8.04 DETAIL #11 SHOW THE
 FOLLOWING TO SHOW COMPLIANCE: FOR THE
 W/C:
 A. HEIGHT 11-4.16.3
 B. GRAB BARS 11-4.16.4
 C. FLUSH CONTROLS 11-4.16.5
 LAV:
 A. HEIGHT & CLEARANCES 11-4.19.2
 B. EXPOSED PIPES & SURFACES 11-4.19.4
 C. FAUCETS 11-4.19.5
 DETAIL #10 SAME AS FOR DETAIL #11 PLUS
 URINAL:
 A. HEIGHT 11-4.18.2
 B. FLUSH CONTROLS 11-4.18.4
 DETAIL #5 SAME AS #11 EXCEPT FOR SECTION
 11-4.19.4 EXPOSED PIPES & SURFACES.
 12. SHT P-2.01 GENERAL NOTES:
 #2 GOVERNING CODE IS FBC-2001 NOT 2002
 OBC OR 2002 OHIO PLUMBING CODE. PLEASE
 CORRECT.
 #12 REVISIONS WILL BE REQUIRED FOR ALL
 CHANGES TO A SIGNED/SEALED/DATED SET OF
 PLANS.
 #27 AIR CHAMBERS ARE NOT APPROVED PER
 SECTION 604.9. DELETE FROM REFERENCE.
 #29 CONDENSATE SHALL BE PIPED
 SEPARATELY FROM THE BUILDING AND
 CONNECTED TO STORM, A CATCH BASIN OR TO
 DRYWELL/PLANTED AREA.
 13. SHT P-2.01 PIPING SCHEMATIC AT WATER
 HEATERS:
 A. 160 DEGREE TO AIR HANDLERS, SHOWS
 WATER GOING TO THE AIR HANDLERS, BUT NO
 RETURN. PLEASE CLARIFY SECTION 104.2.1.
 - A CHECK OF THE MECHANICAL PLANS DOES
 NOT SHOW 160 DEGREE WATER PIPED TO THE
 AIR HANDLERS. PLEASE SUBMIT A DETAIL AND
 MORE INFORMATION ON THIS SYSTEM. SECTION
 104.2.1.
 B. T&P DRAINAGE SHALL DRAIN TO A FLOOR
 SINK OR HUB DRAIN. FLOOR DRAINS ARE NOT
 APPROVED INDIRECT WASTE RECEPTORS.
 SECTIONS 802.3 & 802.3.2.
 C. DIELECTRIC UNIONS ARE NOT APPROVED
 FOR WATER PIPING USAGE. DIELECTRIC
 COUPLINGS SHALL BE USED.
 D. 2-1/2" STUB OUTS W/BY-PASS FOR
 FUTURE SOFTENER (HOT WATER ONLY) APPEARS
 TO BE ON THE COLD WATER INLET PIPING.
 PLEASE CLARIFY. SECTION 104.2.1.
 14. SHTS P-3.01, P-3.02, & P-3.03 SANT.
 RISER DIAGRAMS, TUBS AND SHOWERS REQUIRE
 A TRAP. SECTION 1002.1. - RISER DIAGRAMS
 DO NOT REFLECT THE FLOOR PLANS. PLEASE
 SUBMIT RISER DIAGRAMS IN AN ISOMETRIC
 FORM THAT REFLECT THE FLOOR PLAN, AND
 MEET CODE REQUIREMENTS. SHOW ALL PIPE
 SIZES, VENTS AND DFU FOR EACH RISER.
 SECTION 104.2.1.
 15. SUBMIT A BUILDING DRAIN SANITARY
 ISOMETRIC SHOWING ALL PIPE SIZES, DFU'S
 AS THEY ACCUMULATE IN THE SYSTEM, AND
 SHOW RISER LOCATIONS WITH RISER
 DESIGNATION NUMBERS. SECTIONS 104.2.1 &
 104.3.1.1.
 16. SHTS P3.04, P-3.05, & P-3.06 WATER
 RISER DIAGRAMS, FULL OPEN VALVES ARE
 REQUIRED ON THE BASE OF EVERY WATER
 RISER PIPE. SECTION 606.1(3).
 17. SUBMIT A WATER RISER DIAGRAM IN
 ISOMETRIC FORM FOR THE LAUNDRYAND ALL
 COMMON AREAS SHOWING ALL PIPE SIZES,
 VALVES, AND WATER HAMMER ARRESTORS,
 (WHERE REQUIRED BY SECTION 604.9).
 18. SUBMIT A WATER RISER DIAGRAM IN
 ISOMETRIC FORM FOR THE WATER
 DISTRIBUTION SYSTEM SHOWING THE LOCATION
 OF THE WATER ENTERING THE BUILDING, ALL
 PIPING NOT SHOWN ON RISERS, ALL PIPE
 SIZES, WATER HAMMER ARRESTORS, LOCATION
 OF WATER RISERS CONNECTING TO
 DISTRIBUTION LINE WITH RISER DESIGNATION
 NUMBERS ECT. SECTIONS 104.2.1 AND
 104.3.1.1.
 19. SUBMIT A CONDENSATE RISER DIAGRAM
 SHOWING ALL PIPE SIZES, MATERIAL, AND
 TERMINATION POINT. SECTIONS 104.2.1. &
 104.3.1.1.
 20. THE FOLLOWING INFORMATION IS
 REQUIRED FOR A GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 F. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 I. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 J. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2005-06-13 Cont ID  
Sent By mmclean Date 2005-06-13 Time 08:54 Rev Time 0.00
Received By mmclean Date 2005-06-13 Time 08:54 Sent To  
Notes
***NONE***