Plan Review Details - Permit 05040945
Plan Review Stops For Permit 05040945
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-23 Cont ID  
Sent By jwitmer Date 2005-05-18 Time 07:15 Rev Time 0.00
Received By sgraham Date 2005-06-09 Time 07:33 Sent To  
Notes
2005-05-18 00:00:00BUILDING PLAN REVIEW
 PERMIT:05040945
 ADD: 2200 45TH STREET
 CONT: PLAN REVIEW
 TEL: (727)639-3598
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) ONCE PLANS ARE READY FOR ISSUANCE A
 NOC WILL BE REQUIRED.PROVIDE NOC
 RECORDED WITH THE CLERK OF COURT BEFORE
 A PERMIT CAN BE ISSUED.
  
 2)FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3) FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGEN-
 CY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESH-
 OLD BUILDING. THE PURPOSE OF THE SRUCTUR
 AL INSPECTION PLAN IS TO PROVIDE SPECIF-
 IC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 4) WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 5)W.P.B. AMENDMENT 105.13.4.4 ALL
 PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CON-
 TAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY WITH
 THE APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 6) NOTE, FOR ALL PLANS, REPORTS, PRODUCT
 APPROVALS, SHOP DRAWINGS REVISIONS AND
 SUBMITTALS PROVIDE (3) COPIES OF ALL
 DOCUMENTS.
  
 7) FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
 THE P.E. DID SIGN THE ENERGY FORM BUT
 WHEN SUBMITTED FOR PUBLIC RECORD:
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 8) SHEET 0.02 BUILDING DATA, TYPE II,
 NOT 1 HR PROTECTED, SEE TABLE 600 FOR
 RATING OF STRUCTURAL COMPONENTS & FOR
 EXTERIOR WALLS.
  
 9) SHEET 0.02 PLANS INDICATE THAT THE
 BUILDING IS TO BE FIRE SPRINKLERED,
 PROVIDE PLANS AND CALCULATIONS.
 903.8.1. ANY BUILDINGS WHICH IS 3
 STORIES OR MORE HEIGHT SHALL BE EQUIPPED
 WITH AN APPROVED AUTOMATIC SPRINKLER
 SYSTEM IN ACCORDANCE WITH 903.1.
  
 10) SHEET 0.03: HOTELS: R1 OCCUPANCY,
 A) 4.7.3 RAMPS 4.7.3 REQUIRE 44" IF
 PART OF A MEANS OF EGRESS.
 B) 4.8(2) FL. LAW TOP LANDING REQUIRES
 60" AT THE TOP LANDING AND 72" CLEAR RUN
 FOR THE BOTTOM LANDING.
 C) 4.8(3) / FIGURE 17, SAME AS ABOVE
 REQUIRING 44" IF PART OF A MEANS OF
 EGRESS.
  
 11) SHEET 0.04 FIGURE 28 THE 3RD FIGURE
 TO THE RIGHT, WHERE THE PLAN INDICATES
 THE W.C. IS 18", THIS IS AN ABSOLUTE NOT
 A MINIMUM.
  
 12) SHEET 0.05 4.3.3 WIDTH SEE EXCEPTION
 44" IF PART OF A MEANS OF EGRESS.
  
 13) SHEET 0.1.3 NOTE, POOL, SPA ,FENCE &
 SIGNAGE REQUIRE A SEPERATE PERMIT.
  
 14) SHEET 1.1 NOTE 14 TYPE II BUILDING
 REQUIRES FIRE RETADANT TREATED WOOD,
 BACKING, ETC, SEE 609.2.1.
  
 15) SHEET 1.7, 2.1 PLANS INDICATE USE OF
 ASPHALT/ FIBERGLASS COMPOSITE ROOF
 SHINGLES, THE PRODUCT APPROVAL WAS
 TESTED UNDER PA 110 WHICH LIMITS THE USE
 TO A HEIGHT OF 33'. SEE LIMITATIONS 3.2.
  
 16) FL BLD CODE *104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THERE SEEMS TO BE A DISCREPANCY BETWEEN
 THE STRUCTURAL AND ARCHITECTURAL PLANS.
 A2.1 DETAIL 5.5A/01 INDICATES 2"X6"
 WOOD WALLS, SECTIONS THROUGH VARIOUS
 EXTERIOR DETAILS INDICATE METAL STUD
 WALLS WITH EFIS SYSTEM WHERE AS S-1.03
 INDICATES EXTERIOR WALLS TO BE
 REINFORCED MASONARY WALLS.
  
 17) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THERE ARE DETAILS FOR STO EFIS SYSTEMS
 BUT THE PRODUCT APPROVALS SUBMITTED ARE
 FOR DRYVIT, WHICH WILL BE USED.
  
 18) THE EFIS DETAILS USED ON A2.3/ A2.4
 DO NOT INDICATE WHAT TYPE OF WALL
 SHEATHING IS TO BE USEDNOR INTERIOR
 FINISH MATERIAL NOR THICKNESS, TABLE 600
 1 HR RATED FOR NON-LOADBEARING WALLS.
  
 19) SHEET S0.03, THE SIMPLIFIED
 PRESSURES INDICATED IN TABLE 1606.2 CAN
 ONLY BE USED TO 30' WITH MULTIPLIERS TO
 60'. DEPENDING ON THE POSITIVE &
 NEGATIVE PRESSURES REQUIRED FOR THIS
 BUILDING THE DRYVIT EFIS SYSTEM
 MAY BE LOW IN PRESSURES.THIS BUILDING
 HAS A MEAN ROOF HEIGHT OF 72', ASCE 7-98
 WILL BE REQUIRED FOR CALCULATING THE
 DESIGN PRESSURES FOR BUILDINGS IN EXCESS
 OF 60' IN HEIGHT.FBC 1606.1.1.S-0.01
 WIND LOADS INDICATES DESIGNED BY ASCE 7
 WHICH VERSION?
 19B) THE ARCHITECT DOES NOT INDICATE HOW
 HE DESIGNED THE BUILDING AT ALL?
  
 20) PLEASE INDICATE ON THE ELEVATIONS
 THE POSITVE & NEGATIVE PRESSURES, FOR
 THE WINDOWS, DOORS EFIS & ROOFING,
 INTERIOR ZONES AS WELL AS END ZONES.
 1606.1.1.
  
 21) A5.3 WALL SECTIONS INDICATE THE USE
 OF WOOD TRUSSES, TYPEII BLDG- SECTION
 604, STRUCTURAL MEMBERS INCLUDING
 TRUSSES, GIRDERS AND ROOFS (PLYWOOD)
 SHALL BE OF NON-COMBUSTIBLE MATERIALS
 AND ARE PROTECTED BY 1HR CONSTRUCTION
 (TABLE 600). ANNOTE PLANS FOR CODE
 COMPLIANCE.
  
 22) SHEET A5.9 LAUNDRY CHUTE, TABLE
 705.1.2 REQUIRES A 2 HR RATED SHAFT:
 A) THE SHAFT WALLS STOP AT THE FLOOR
 LINE PLANS INDICATE A 2 LAYER 2X
  
 B) THE RATED SHAFT STOPS BENEATH THE
 ROOF DECK
  
 C) ABOVE THE ROOF DECK NO SHAFT (2 HR
 RATING) IS REQUIRED.
  
 D) PLANS DO NOT INDICATE WHAT TYPE OF
 MATERIAL THE INTERNAL FRAMING OR
 SHEATHING IS COMPOSED FROM (CHIMNEY).
  
 E) INFORMATION ON HURRICANE STRAPPING
  
 23) SHEET A5.9 ELEVATOR VENTING:
 A)IS A CONTINUATION OF THE 2HR RATED
 SHAFT, TABLE 705.2.1, PROVIDE THE 2 HR
 SHAFTRATING THROUGH TO THE VENT,
 INDICATE WHICH ASSEMBLY WILL BE USED.
  
 B) 3003.6.3 THE AREA OF THE VENTS SHALL
 BE NOT LESS THAN 3 SQ FT FOR EACH
 ELEVATOR CAR, WHICHEVER IS GREATER.
 SINCE THERE IS (2) ELEVATOR CARS, A
 MINIMUM OF 6 SQ FT OF CLEAR VENT AREA IS
 REQUIRED. THE 28" VENT WILL BE ADEQUATE,
 INDICATE ON THE TERMINATION CAP THE
 CLEAR AREA HXW = X SQ FT.
  
 C) INDICATE THE STRTCHER REQUIREMENTS
 IN ONE OF THE ELEVATORS DETAILS:
 ?3003.4.1 IN ALL STRUCTURES THAT ARE
 MORE THAN THREE STORIES HIGH OR IN
 WHICH THE VERTICAL DISTANCE BETWEEN
 THE BOTTOM TERMINAL LANDING AND THE
 TOP TERMINAL LANDING EXCEEDS 25 FEET
 (7.6 M) MUST BE CONSTRUCTED TO
 CONTAIN AT LEAST ONE PASSENGER
 ELEVATOR THAT IS OPERATIONAL AND WILL
 ACCOMMODATE AN AMBULANCE STRETCHER 76
 INCHES (1931 MM) LONG AND 24 INCHES
 (610 MM) WIDE IN THE HORIZONTAL
 POSITION.THIS ELEVATOR SHALL BE
 IDENTIFIED.
  
 24) SHEET A5.9 EXHAUST DUCT DETAIL# 08
 HAS THE SAME PROBLEM AS THE LAUNDRY
 CHUTE THE SHAFT IS NOT CONTINIOUS FROM
 FLOOR TO FLOOR, THERE IS WOOD 2X'S IN
 THE SHAFT CONSTRUCTION, PROVIDE THE
 ASSEMBLY WITH THIS APPLICATION, ALSO IF
 BUILT TO FLOOR/ CEILING AND NOT
 CONTINIOUS:705.7.1 JOINTS INSTALLED
 IN OR BETWEEN FIRE RESISTANT WALLS, FIRE
 RESISTANT FLOORS OR FLOOR/ CEILING
 ASSEMBLIES AND FIRE RESISTANT ROOFS OR
 ROOF/ CEILING ASSEMBLIES SHALL BE
 PROTECTED BY AN APPROVED FIRE RESISTANT
 JOINT SYSTEM DESIGNED TO RESIST THE
 PASSAGE OF FIRE FOR A PERIOD NOT LESS
 THAN THE REQUIRED FIRE RESISTANCE RATING
 OF THE WALL, FLOOR OR FLOOR IN OR
 BETWEEN WHICH IT IS INSTALLED.
  
 25) SHEET 6.2 STAIR HANDRAILS:
 A) ?11-4.9.4(1) HANDRAILS SHALL BE
 CONTINUOUS ALONG BOTH SIDES OF STAIRS.
 THE INSIDE HANDRAIL ON SWITCHBACK OR
 DOGLEG STAIRS SHALL ALWAYS BE CONTINUOUS
 SEE FIGURE 11-19(A) & FIGURE 11-19(B)).
  
 B) SAME SHEET DETAIL NUMBER 5:
 11-4.9.4(3) THE CLEAR SPACE BETWEEN
 HANDRAILS AND WALL SHALL BE 1-1/2 INCHES
 (38 MM).
  
 C) SAME SHEET DETAIL NUMBER 10:
 11-4.9.4(2) AT THE BOTTOM, THE HANDRAIL
 SHALL CONTINUE TO SLOPE FOR A DISTANCE
 OF THE WIDTH OF ONE TREAD FROM THE
 BOTTOM RISER; THE REMAINDER OF THE
 EXTENSION SHALL BE HORIZONTAL (SEE
 FIGURE 11-19(C) AND FIGURE 11-19(D)).
 HANDRAIL EXTENSIONS SHALL COMPLY WITH
 11-4.4.
  
 26) A-9.06 DOOR SCHEDULE DOORS TO THE
 STAIR TOWERS TO BE 60 MIN TABLE 705.1.2
 REQUIRESA 1 1/2 HR RATED DOOR.
  
 27) SHEET A5.15/A5.16
 A) DISCREPANCY, A5.15 DETAIL 1 INDICATES
 A FLUE WHILE THE NEXT PAGE INDICATES A
 VENTLESS FIRE PLACE.
  
 B) PROVIDE THE MANUFACTURES SPEC FOR
 THE VENTLESS FIREPLACE:SECTION 2809
 GAS APPLIANCES:GAS APPLIANCES SHALL BE
 INSTALLED AND VENTED IN ACCORDANCE WITH
 THE REQUIREMENTS OF THE FLORIDA BUILDING
 CODE, FUEL GAS.
  
  
  
 27) A-201/ A-202, THERE ARE NUMEROUS
 DOORS THAT DO NOT HAVE THE REQUIRED18"
 CLEAR ON THE PULL LATCH SIDE.
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 28) SHEET A-2,01 RESTROOMS 112, DOORS
 SWING INTO THE REQUIRED CLEAR FLOORSPACE
 FOR FIXTURES, 11-4.19.3.
  
  
  
  
  
 31) SHEET A-10.06/A-10.07/ A-10.08
 ADDITIONAL INFORMATION IS REQUIRED,
 SUBMITTED IS A FLORIDA COVER SHEET
 LISTING FL 3627, WHICH TIES TO PRODUCT
 EVALUATION REPORTS FROM FRANK L BENNARDO
 A MIAMI-DADE REPORT WAS SUBMITTED. THERE
 IS A DIFFERENT FL# (FL#379) FOR THE
 MIAMI-DADE REPORT. PROVIDE THE CORRECT
 FLORIDA COVERSHEET WITH THE ASSOCIATED
 REPORT.
  
 32) SHEET A-10.11/ A-10.12 SUBMITTED A
 ROOFING REPORT FOR NON STRUCTURAL METAL
 ROOFING. THIS REPORT PRESSURE ISGOOD
 FOR ONLY 52.5 PSF. THIS ROOF WILL
 ENCOUNTER HIGHER PRESSURES THAN THIS IN
 ROOF ZONES 2 AND 3. SECOND PROBLEM THE
 ENGINEERING SHEETS THAT TIE TO THE FL
 COVERSHEET FROM C-BUCK ENGINEERING WERE
 NEVER SUBMITTED.
  
 33) SHEET A-10.13/ A-10.14 ARE FOR PGT
 HORIZONTAL SLIDERS ,THE FL COVERSHEET
 INDICATES THIS IS A NON-IMPACTWINDOW,
 SEE HIGHLIGHTED NOA# INDICATING NON-
 IMPACT RATING. THE SECOND ISSUE INDICATE
  
 WHICH TYPE OF GLAZING TO BE INSTALLED
 FOR PRESSURE RATINGS, MAY BE LOW VALUES.
  
 34) SHEET A-10.15/ A-10.16 SUBMITTED
 SHEETS FOR PGT FIXED GLAZING, INDICATE
 WHICH GLAZING SHALL BE USED TO SEE IF
 THE PRESSURES ARE MET.
  
 35)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) FIXED WINDOWS
 B) HORIZONTAL SLIDERS
 C) EXTERIOR GLAZED HORIZONTAL SLIDING
 DOORS
 D) SWING DOORS- GLAZED
 E) SWING DOORS-SOLID
 F) MULLIONS
 G) LOUVERS
 H) EFIS SYSTEMS
 I) TRUSS ANCHORS
 J) ROOFING ASSEMBLIES
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 36)1707.4.3 EACH EXTERIOR DOOR ASSEMBLY
 NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 37) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 38) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 39) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED, SHEET
 S-101 INDICATES THAT THE FOUNDATION
 DESIGN IS INCOMPLETE DEPENDING ON THE
 SOILS REPORT? PLANS DO NOT PROVIDE
 INFORMATION ON CAST IN PLACE CONCRETE
 PILES, LOCATION, GROUT, ETC.
  
 40) S-2.02 SECTION B PORT COCHERE
 INDICATES THE USE OF WOOD TRUSSES AND
 WOOD SHEATHING, TYPE II BUILDING, SEE
 TABLE 600 ROOFS & ROOF /CEILING
 ASSEMBLIES FOOTNOTE "E".
  
 41) S1.04 ROOF TRUSSES:
 A)TYPE II BUILDING ROOF- NONCOMBUSTIBLE
 STRUCTURAL ELEMENTS TRUSSES & WOOD DECK.
 B) PROVIDE UPLIFT FOR THE ROOF FRAMING
 MEMBERS, DIRECTION,MAGNITUDE OF THE
 LOADS TO BE RESISTED.1606.1.1/ 1606.1.3,
 PART OF THE MAIN WIND FORCE RESISTING
 SYSTEM.
 C)1707.3.1 JOIST HANGERS, FRAMING
 ANCHORS & SIMILAR DEVICES SHALL BE TEST-
 ED IN ACCORDANCE W/ ASTM D 1761 & BE
 LABELED AND LISTED FOR THEIR LOAD CARRY-
 ING CAPACITY.
 D) 1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREASE IN ALLOWABLE STRESS
 SPECIFIED IN THE MATERIALS SECTIONS OF
 THIS CODE OR A REFRENCED STANDARD SHALL
 NOT BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23 (WOOD).
  
 42) SHEET A-5.2 SECTION 02, BUILDING
 SECTION B-B:
  
 A) DEMONSTRATE COMPLIANCE WITH:
 2305.2.2 3. OTHER BUILDINGS.IN
 FLOOR/CEILING ASSEMBLIES SO THAT
 HORIZONTAL AREAS DO NOT EXCEED 1,000 SQ
 FT (92.9 M^2).
 2305.2.3(3) WHERE APPROVED SPRINKLERS
 ARE PROVIDED, DRAFTSTOPPING SHALL BE
 REQUIRED FOR AREAS OVER 9,000 SQ FT (836
 M^2).
  
 B)SEE NOTE FOR VENTILATION AND DRAFT
 STOPPING "LOCAL CODE REQUIREMENTS",
 104.2.1 W.P.B. ADMINISTRATIVE CODE
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES.
 SUCH INFORMATION SHALL BE SPECIFIC AND
 THE TECHNICAL CODES "SHALL NOT BE CITED
 AS A WHOLE OR IN PART, NOR THE TERM
 "LEGAL" OR ITS RQUIVALENT BE USED AS A
 SUBSTITUTE FOR SPECIFIC INFORMATION".
  
 C)(WOOD)?2309.7.1 FOR GABLED AND HIPPED
 ROOFS, VENTILATION SHALL BE PROVIDED TO
 FURNISH CROSS VENTILATION OF EACH
 SEPARATE ATTIC SPACE WITH WEATHER
 PROTECTED VENTS.ALL VENTS SHALL BE
 SCREENED TO PROTECT THE INTERIOR FROM
 INTRUSION OF BIRDS.THE RATIO OF
 TOTAL NET FREE VENTILATING AREA TO THE
 AREA OF THE CEILING SHALL BE NOT LESS
 THAN 1/150.
  
 43) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET A-5.3 INDICATES THE USE OF GABLE
 TRUSSES WITH A LOWER ROOF AND HIGHER
 SECTION OF TRUSS CREATING A WALL SECTION
 BETWEEN THE TO ROOF SYSTEMS. PROVIDE A
 SECTION INDICATING THE ROOF BRACING OF
 WALL.
  
 44) SHEET M101-107 GENERAL NOTES
 INDICATE "PROVIDE A CONCEALED CONDENSATE
 STACK WITHIN THE OUTSIDE WALL, PROVIDE
 ADDITIONAL INFORMATION, ?705.6
 PENETRATIONS OF HORIZONTAL ASSEMBLIES.
 ALL PENETRATIONS OF A FLOOR, FLOOR
 / CEILING ASSEMBLY, OR THE CEILING
 MEMBRANE OF A ROOF/CEILING ASSEMBLY
 SHALL BE PROTECTED BY A SHAFT ENCLOSURE
 IN ACCORDANCE WITH ?705.2 OR
 SHALL COMPLY WITH ?705.6.1 THROUGH
 ?705.6.4.?705.6.1 THROUGH
 PENETRATIONS. THROUGH-PENETRATIONS OF
 FIRE RATEDHORIZONTAL ASSEMBLIES SHALL
 COMPLY WITH ?705.6.1.1 OR ?705.6.1.2.
  
 45) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET M-201 INDICATES THE USE OF ROOFTOP
 MAKE UP AIR AND EXHAUST UNITS, PROVIDE
 THE FRAMING AND ANCHORING DETAILS.
  
 46) SHEET A-5.5A SECTION# 9, INDICATES
 THE USSE OF 5/8" TYPE"X" GYPSUM SOFFIT
 BOARD FINISH. PROVIDE REPORT FOR THIS TO
 BE AN ACCEPTABLE APPLICATION FOR THIS
 PRODUCT (PRODUCT APPROVAL). ES REPORTS
 INDICATE THIS ISTO BE USED FOR
 CEILINGS IN CARPORTS WHAT FINISH
 APPLICATION IS TO BE USED?
  
 47)DAVID I WALLACE & ASSOCIATES, P. A.,
 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING
 ARCHITECTURAL SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 48)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 49) ADDITIONAL FEES DUE, CALCULATED
 VALUE FOR THIS BUILDING IS :
 $6,195,792.00.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-04-28 Cont ID  
Sent By dpalmer Date 2005-04-28 Time 15:23 Rev Time 8.00
Received By dpalmer Date 2005-04-27 Time 14:44 Sent To  
Notes
2005-05-02 00:00:00*** ALL ELECTRICAL ROOMS PER 110.26,
 DOOR SWINGS, PANIC HARDWARE ETC.
2005-04-28 00:00:00*********** UNSAT ***********
  
 FAIRFIELD INN 6- STORY
 PLANS SUBMITTED FOR "PLAN REVIEW" ONLY
 AND NOT SUBMITTED FOR PERMIT.
  
  
 1)NOTE: PLEASE SEE ALL BACKGROUNDS FOR
 ELECTRICAL PLANS ARE VERY FAINT AND
 UNABLE TO VIEW CORRECTLY.
 PLEASE ALSO SEE ALL PLANS TO BE
 SUBMITTED ARE REQUIRED TO BE A MIN OF
 1/8" SCALE.
 104.2.1
  
 2)NOTE: PLEASE SHOW LOCATION OF ALL
 ELECTRICAL PANELS, DISCONNECTS ETC ON
 PLANS. UNABLE TO LOCATE ANY ON PLANS.
 PLEASE ALSO SHOW PANELS ETC IN
 ELECTRICAL RMS AS REQUIRED.
 PLEASE INCLUDE PROPOSED FIRE PUMP RM
 ETC.
 110.26,215.5
  
 3)NOTE: PLEASE SEE FAC 61G1-16.004 AND
 FS 481.219 FOR MISSING REQUIRED
 INFORMATION ON/IN TITLE BLOCKS.
 THIS IS REQUIRED FOR ALL TRADES AND FOR
 ALL SHEETS WHEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 4)NOTE: PLEASE SEE ELECTRICAL NOTES
 MENTIONS "PLANS TO COMPLY WITH:"??
 PLEASE COMPLETE NOTE AND PLEASE SEE WE
 ARE CURRENTLY UNDER THE 2002 NEC.
 215.5
  
 5)NOTE: PLEASE SEE 2002 NEC FOR GFI
 PROTECTION REQUIRED FOR "ALL" RECEPTS IN
 KITCHENS.210.8B3
 PLEASE ALSO SEE RECEPTS LOCATED IN BREAK
 RM AND CLOSE PROXIMITY TO SINKS. 6'
 210.8
  
 6)NOTE:PLEASE INCLUDE ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULES
 SUBMITTED.
 PLEASE SEE ROOM TYPICAL DETAILS ALSO.
  
 7)NOTE: PLEASE SEE SOME ROOMS APPEAR TO
 SHOW MORE THAN ONE SINGLE POLE SWITCH
 CONTROLLING THE SAME DEVICE. THESE
 SHOULD BE 3-WAYS?
  
 8)NOTE: PLEASE SEE DETAIL ON E4.1.1E
 REFERS TO #7 ON E4.4F, HOWEVER THIS
 DEATIL FOR CIRCLED NOT SHOWN.??
  
 9)NOTE: PLEASE SOME BATHRMS DO NOT
 INDICATES RECETPS AS GFI?
 210.8A3
  
 10)NOTE: PLEASE SEE CIRCUITING LABELD ON
 MSB. PLEASE CORRELATE CIRCUITS # WITH
 PLANS.
 215.5
  
 11)NOTE:PLEASE SEE NOTE #1 , PLEASE
 SHOW ELEVATOR EQUIPMENT RMS. PLEASE SEE
 620.23,620.24 FOR MIN CIRCUITING
 REQUIRED.
 CIRCUITS SHOWN ON PANEL SCHEDULE 6C, BUT
 UNCLEAR IF THESE ARE FOR "CARS" OR
 MACHINE RM?
  
 12)NOTE: PLEASE SHOW ALL CONTINUOUS
 LOADS AT 125% ON EACH PANEL ALSO.THIS
 MAY BE A NOTE, IF INDEED THESE LOADS ARE
 ALREADY FIGURED AT 125%.
 IT IS NOTED THAT MAIN SERVICE CONTAINS
 THE 125% ALREADY.
 215.3,230.42 ETC.
  
 13)NOTE: PLEASE CORRELATE ALL CONDUCTOR
 SIZES SHOWN ON EQUIPMENT SCHEDULE WITH
 PANEL SCHEDULES FOR EACH.
 215.5
 PLEASE SEE MIN AWG FOR OCP AND KW LOADS.
 310.16,240.4
  
 14)NOTE: PLEASE SEE EQUIPMENT SCHEDULE
 MENTIONS REFERENCE TO NOTE #7 ON E1.00,
 YET NO E-1.00 COULD BE LOCATED IN SETS??
 215.5
  
 14)NOTE: PLEASE VERIFY FEEDERS INDICATED
 FOR 200A PANELS, 2A -6A.
 SHOWN AS 500MCM?
 THIS IS ONLY A NOTE:
  
 15)NOTE: PLEASE SEE FIRE PUMP IS SHOWN
 BEING FED FROM MSB. PLEASE SEE 695.3,
 THIS "ISNOT" PERMITTED.
 PLEASE ALSO SEE FIRE PUMP IS SHOWN WITH
 A ADDITIONAL FEED FROM FPL THROUGH AN
 ATS??
 PLEASE SEE NO SIZE OF FIRE PUMP IS
 SHOWN?
 PLEASE SEE NO MAIN SHOWN FOR THIS?
 PLEASE SEE NO INFORMATION SUBMITTED FOR
 FIRE PUMP?
 PLEASE SEE THIS IS PHYISCALLY
 IMPOSSIBLE.
 PLEASE SUBMIT ALL INFORMATION FOR FIRE
 PUMP, ATS, GENERATOR ETC.
 PLEASE SUBMIT MANUFACTURE SPEC SHEETS
 FOR ALL EQUIPMENT.
 PLEASE INCLUDE PRIME MOVER FOR
 GENERATOR.
 PLEASE SEE MISSING DISCONNECTING MEANS
 PER 225.31-225.36.
 PLEASE SEE MISSING EQUIPMENT GROUNDING
 FOR FEEDS TO FIRE PUMP.
 250.110,250.122
 PLEASE SEE MISSING INFORMATION FOR
 LOCKED ROTOR PER 695.4B1
 PLEASE SHOW ALL LOCATIONS OF ALL
 EQUIPMENT ON ELECTRICAL PLANS.
  
 16)NOTE: PLEASE CORRELATE GROUNDING
 ELECTRODE CONDUCTOR SIZES ON PLANS.
 PLEASE SEE ONE LOCATION SHOWS 4/0 AND
 THE OTHER 3/0?
 250.66
  
 17)NOTE: PLEASE VERIFY SEC'S SHOWN.
 THIS IS ONLY A NOTE AND NO CODE
 VIOLATION EXIST FOR SEC'S.
  
 18)NOTE: PLEASE SEE PANEL "L" IS SHOWN
 ON RISER TO BE FED FROM MSB, HOWEVER MSB
 SCHEDULE DOES NOT INDICATE THIS ?
 PLEASE CORRELATE.215.5
  
 19)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 PERTAINING TO FIRE ALARM PLANS REQUIRED.
  
 20)NOTE: PLEASE SEE OTHER POSSIBLE
 COMMENTS FROM OTHER REVIEWER(S) WHICH
 MAY HAVE AN AFFECT ON ELECTRICAL PLANS.
  
 PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW SHEETS INTO
 THREE COMPLETED SETS FOR REVIEW AND
 STAMPING.
  
 *** PLEASE SEE DUE TO THE AMOUNT OF
 MISSING INFORMATION ON PLANS, A COMPLETE
 REVIEWFOR CODE COMPLIANCE CAN NOT BE
 DONE AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
 *** PLEASE SEE DUE TO THE AMOUNT OF
 MISSING INFORMATION ON PLANS, A COMPLETE
 REVIEWFOR CODE COMPLIANCE CAN NOT BE
 DONE AT THIS TIME.
2005-04-27 00:00:001 ROLL IN FOR ELECTRICAL REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2005-06-03 Cont ID  
Sent By mamini Date 2005-06-03 Time 08:19 Rev Time 0.50
Received By mamini Date 2005-06-03 Time 08:19 Sent To  
Notes
2005-06-03 00:00:00FAILED:
  
 1. PLEASE SUBMIT CIVIL PLANS FOR OUR
 REVIEW AND APPROVAL.NOTE THAT STORM
 WATER CALCULATIONS FOR ENTIRE SITE AND
 POLLUTION PREVENTION PLANS SHOULD BE
 INCLUDED IN THIS SUBMITTAL.
 2. PLEASE SUBMIT CIVIL PLANS TO THE
 PUBLIC UTILITIES AND ENGINEERING FOR
 THEIR APPROVAL OF THE CONNECTIONS TO THE
 CITY' SERVICES, ATT; MANNY GONZALEZ,
 494-1085. NOTE THAT CIVIL PLANS MUST BE
 APPROVED BY THEM PRIOR TO GETTING PERMIT
 FROM THE CONSTRUCTION SERVICES DEPT.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-05-25 Cont ID  
Sent By mwennerg Date 2005-05-25 Time 10:56 Rev Time 0.00
Received By mwennerg Date 2005-05-25 Time 10:56 Sent To  
Notes
2005-05-25 00:00:00****FAILED****
  
 1) LOCKING CAPS ARE REQUIRED ON THE FIRE
 DEPARTMENT CONNECTION.
  
 2) LIFE SAFETY SHALL COMPLY WITH NFPA
 101, 2003 EDITION.
  
 3) ALL CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 4) SEPARATE SHOP DRAWING AND PERMITS ARE
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS.
  
 5) NEW FIRE ALARM SYSTEMS SHALL BE
 MONITORED FOR UL CERTIFIED CENTRAL
 STATION SERVICE.
  
 6) TEMPORARY STANDPIPES ARE REQUIRED
 WHEN THE BUILDING REACHES 3 STORIES OR
 30 FEET IN HEIGHT.
  
 7) FIRE DEPARTMENT CONNECTIONS MUST
 REMAIN ACCESSIBLE, AND BE LOCATED NO
 FURTHER THAN 150' FROM THE CLOSEST FIRE
 HYDRANT.
  
 8) PLEASE INDICATE THE OCCUPANT LOAD FOR
 THE POOL AND DECK AREAS.
  
 9) PLEASE PROVIDE THE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR ALL HANDRAILS
 AND GUARDRAILS.
  
 10) PLEASE PROVIDE MORE DETAILS IN
 REGARDS TO THE CARD READERS, AND WHAT
 ISSUES IF ANY WILL THEY RAISE IN
 EXITING.
  
 11) 2A-10B,C FIRE EXTINGUISHERS SHALL BE
 PLACED TO SATISFY THE 75' TRAVEL
 DISTANCE REQUIREMENT.
  
 12) TACTILE SIGNAGE IS REQUIRED AT ALL
 EXIT DOORS.
  
 13) IT APPEARS THAT ADDITIONAL EXIT
 SIGNS WILL BE NEEDED TO SATISFY THE 100'
 TRAVEL REQUIREMENT BETWEEN SIGNS.
  
 14) AN ADDRESS NUMBER IS REQUIRED TO BE
 INSTALLED ON THE BUILDING, A MINIMUM OF
 6" IN HEIGHT AND CONTRASTING TO THE
 BACKGROUND.
  
 15) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION OF THE WALLS AND
 CEILINGS.
  
 16) LOCAL REQUIREMENTS REQUIRE THE DUCT
 SMOKE DETECTORS TO BE WIRED INTO THE
 FIRE ALARM SYSTEM TO CAUSE A GENERAL
 FIRE ALARM, AND NOT A SUPERVISORY
 SIGNAL.
  
 17) A CHAIN AND LOCK IN ADDITION TO
 ELECTRONIC SUPERVISION WILL BE REQUIRED
 ON THE DOUBLE CHECK DETECTOR ASSEMBLY.
  
 18) PLEASE ILLUSTRATE STRETCHER
 ACCESSIBILITY IN ELEVATORS.
  
 19) PLEASE SHOW THE LOCATIONS OF LIVING
 UNIT SINGLE STATION SMOKE DETECTORS.
  
 20) ARE THE ELEVATOR LOBBIES ABOVE THE
 FLOOR OF EXIT DISCHARGE FIRE RATED?
  
 21) A KNOX BOX WILL BE REQUIRED.
  
 22) PLEASE SHOW EXISTING AND NEW FIRE
 HYDRANT LOCATIONS.
  
 23) NO FIRE PROTECTION OF LIFE SAFETY
 DRAWINGS WERE SUBMITTED.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2951 OR 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-11-15 Cont ID  
Sent By adarroug Date 2005-11-15 Time 08:50 Rev Time 0.00
Received By adarroug Date 2005-11-15 Time 08:50 Sent To  
Notes
2005-11-15 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-07 Cont ID  
Sent By shill Date 2005-06-07 Time 13:38 Rev Time 0.00
Received By shill Date 2005-06-07 Time 13:38 Sent To Z
Notes
2005-06-07 00:00:00APPLICATION SENT TO ZONING BOX
 PLANS ON SHELF
 EMAILED S GRAHAM

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-13 Cont ID  
Sent By mmclean Date 2005-06-13 Time 08:54 Rev Time 0.00
Received By mmclean Date 2005-04-18 Time 14:12 Sent To  
Notes
2005-04-18 00:00:00TO "COMM" BD#42/PLANS ON "COMM" RACK

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2005-05-14 Time   Rev Time 0.00
Received By hmoser Date 2005-05-16 Time 07:21 Sent To  
Notes
2005-05-14 00:00:00PLAN DENIED
 1) BATHROOM EXHAUST MUST BE INSTALLED IN
 A 2HR.SHAFT.PER SECTION 607.4 FLOOR
 PENETRATION FBC(M)
 2) PAGE M1.01 AIRHANDLER #3 NEEDS FAN
 SHUTDOWN.SECTION 606 FBC(M)
 3) ALL METERALS IN RETURN AIR PLENUM
 MUST BE NONCOMBUSTIBLE SECTION 602.2.1
 FBC(M)
 4) PLEASE SHOW FRESH AIR DUCT FOR
 AIRHANDLERS 1 THROUGH 6 ON PLANS.
 5) PLEASE SHOW LOCATION AND DUCT SIZE
 FOR RETURN AIR ON AIRHANDLERS 1,2,3,6
 6) IF EXHAUST FANS AER LOCATED ON ROOF
 PLAESE REFER TO SECTION 306.6 FBC(M)
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-06-04 Cont ID  
Sent By kstevens Date 2005-06-04 Time 08:33 Rev Time 6.33
Received By kstevens Date 2005-06-04 Time 08:33 Sent To  
Notes
2005-06-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL CODE
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. PLANS SHALL BE ROUTED TO DBPR HOTEL &
 RESTURANT DIVISION FOR REVIEW PRIOR TO
 RESUBMITTING TO THE CITY WPB FOR REVIEW.
 SUBMIT A MINIMUM OF 3 SETS OF PLANS
 STAMPED BY DBPR WITH THE TWO PAGE "WORK
 SHEETS" ATTACHED TO EACH SET. SECTION
 101.4.7.
 2. INDICATE IF FOOD WILL BE PREPARED ON
 SITE OR IF ALL FOOD WILL BE PREPACKAGED
 FOOD FOR COMSUMPTION. TO DETERMINE IF A
 GREASE INTERCEPTOR IS REQUIRED CONTACT
 RODNEY COMPO, ENVIRONMENTAL COMPLIANCE.
 (561) 473-4074, FAX (561) 659-7458, OR
 E-MAIL [email protected]. PLEASE SUBMIT HIS
 DETERMINATION WITH PLANS.
 3. SHT 0.1.3 SEPARATE POOL PERMIT
 REQUIRED. SECTION 104.1.1.
 4. SHT 3.1 TOILET ROOMS. SHOW CLEAR
 FLOOR SPACE FOR EACH ACCESSIBLE FIXTURE.
 SHOW TURNING AREA IN EACH TOILET ROOM. .
 SECTION 11-4.22.3
 5. SHTS A-2.01 & A-2.02 SUBMIT
 CALCULATIONS FOR MINIMUM FACILITIES PER
 TABLES 1103.1 & 403.1 FOR ALL COMMON
 AREAS. SHOW THE SQUARE FOOTAGE OF EACH
 COMMON AREA ON THE FLOOR PLAN.
 6. SHT 3.1 SINK IN EMPLOYEE BREAK ROOM
 #156 SHALL COMPLY WITH SECTION 11-4.24
 AND ALL SUBSECTIONS. (FORWARD APPROACH
 IS REQUIRED MAXIMUM 19" UNDERNEATH THE
 SINK. SINK SHALL BE CENTERED ON THE 30"
 WIDTH OF THE CLEAR FLOOR SPACE).
 7. SHT P1.01 INDICATE THE USE OF FD1 IN
 VENDING ROOM 154. IF USED FOR INDIRECT
 WASTE, A FLOOR SINK OR HUB DRAIN IS
 REQUIRED. SECTIONS 802.3 & 802.3.2.
 8. SHT P1.01 BUILDING DRAIN LINE DOES
 NOT REFLECT PIPING SHOWN ON SHT P-5.01.
 PIPING ON SHT P-5.01 SHOWS THE LAUNDRY
 ROOM CONNECTING UPSTREAM OF RISER S/3
 CONNECTION TO BUILDING DRAIN. CORRELATE
 PLANS. SECTION 104.2.1.
 9. SHT P2.01 WATER HEATER SCHEMATIC:
 A. T&P LINE SHALL BE PIPED TO AN
 APPROVED INDIRECT WASTE RECEPTOR. FLOOR
 SINK OR HUB DRAIN REQUIRED. FLOOR DRAINS
 ARE NOT APPROVED WASTE RECEPTORS.
 SECTIONS 802.3 & 802.3.2.
 B. SCHEMATIC SHOWS 2-1/2" STUB OUTS FOR
 FUTURE WATER SOFTENER (HOT ONLY), BUT IT
 APPEARS TO BE ON THE COLD WATER SIDE OF
 THE HEATERS. PLEASE CLARIFY. SECTION
 104.2.1.
 C. DIELECTRIC UNIONS NOT APPROVED FOR
 WATER DISTRIBUTION SYSTEM. DIELECTRIC
 COUPLINGS SHOULD BE USED.
 10. SHT P-201 GENERAL PLUMBING NOTES:
 #12 REVISIONS WILL BE REQUIRED FOR ALL
 CHANGES TO A SIGNED/SEALED/DATED SET OF
 PLANS.
 #27 AIR CHAMBERS ARE NOT APPROVED PER
 SECTION 604.9. DELETE FROM REFERENCE.
 #29 CONDENSATE SHALL BE PIPED
 SEPARATELY FROM THE BUILDING AND
 CONNECTED TO STORM, A CATCH BASIN OR TO
 DRYWELL OR PLANTED AREA.
 11. SUBMIT A BUILDING DRAIN SANITARY
 ISOMETRIC SHOWING ALL PIPE SIZES, DFU'S
 AS THEY ACCUMULATE IN THE SYSTEM, AND
 SHOW RISER LOCATIONS WITH RISER
 DESIGNATION NUMBERS. SECTIONS 104.2.1 &
 104.3.1.1.
 12) SHT P-3.01 ALL SANT. RISER DIAGRAMS,
 (EXCEPT S/16), DO NOT REFLECT THE FLOOR
 PLAN, NOR DO THEY MEET CODE REQUIREMENTS
 A. RISER S/15 EW1 NOT SHOWN ON RISER.
 B. RISERS SHALL REFLECT THE SANT.
 LAYOUT ON SHTS P-4.01 & P-4.02.
 C. A VENT STACK SHALL BE REQUIRED FOR
 EVERY DRAINAGE STACK THAT IS FIVE BRANCH
 INTERVALS OR MORE. SECTION 903.2.
 D. EVERY VENT STACK SHALL CONNECT TO
 THE BASE OF THE DRAINAGE STACK. THE VENT
 STACK SHALL CONNECT AT OR BELOW THE
 LOWEST HORIZONTAL BRANCH. SECTION 903.4.
 13. SUBMIT A WATER RISER DIAGRAM IN
 ISOMETRIC FORM FOR THE LAUNDRYAND ALL
 COMMON AREAS SHOWING ALL PIPE SIZES,
 VALVES, AND WATER HAMMER ARRESTORS,
 (WHERE REQUIRED BY SECTION 604.9).
 14. SUBMIT A WATER RISER DIAGRAM IN
 ISOMETRIC FORM FOR THE WATER
 DISTRIBUTION SYSTEM SHOWING THE LOCATION
 OF THE WATER ENTERING THE BUILDING, ALL
 PIPING NOT SHOWN ON RISERS, ALL PIPE
 SIZES, WATER HAMMER ARRESTORS, LOCATION
 OF WATER RISERS CONNECTING TO
 DISTRIBUTION LINE WITH RISER DESIGNATION
 NUMBERS ECT. SECTIONS 104.2.1 AND
 104.3.1.1.
 15. SUBMIT A CONDENSATE RISER DIAGRAM
 SHOWING ALL PIPE SIZES, MATERIAL, AND
 TERMINATION POINT. SECTIONS 104.2.1. &
 104.3.1.1.
 16. THE FOLLOWING INFORMATION IS
 REQUIRED FOR A GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 F. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 I. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 J. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 17. AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THE BUILDING. SECTION
 608.13.2.
 18. BACKFLOW PROTECTION IS REQUIRED FOR
 POOL WATER SUPPLY. THIS CAN BE INDICATED
 ON THE POOL PLANS WHEN SUBMITTED.
 19. ALL INFORMATION REQUIRED BY FAC
 61G1-16.004 & FS 481.219 TO BE IN THE
 TITLE BLOCK OF THE ARCHITECT.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2005-06-08 Time   Rev Time  
Received By   Date 2005-06-08 Time   Sent To  
Notes
2005-06-10 00:00:00REVIEWED BY SHIRLEY GRAHAM, ASSOCIATE
 PLANNER 822-1435