| 2005-05-17 00:00:00 | DENIED |
| | 1)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) USP CONNECTORS JL28 AND JL210 |
| | SPECIFIED ON 5B ARE NOT DESIGNED OR |
| | TESTED TO BE USED WITH TAPCONS FOR A |
| | MASONRY ATTACHMENT. SPECIFY APPROVED |
| | MASONRY HANGERS. |
| | |
| | 3) SUBMIT THE STATE PRODUCT APPROVAL |
| | SHEET WITH FL#1379 FOR THE METAL ROOF |
| | PANELS. |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. |
| | |
| | 4) SUBMIT THE CORRECT AND COMPLETE |
| | PRODUCT APPROVAL INFORMATION FOR THE |
| | PLASTRO/NANYA PLASTICS DOORS. SUBMIT ALL |
| | 14 PAGES OF THE TEST REPORT |
| | (# CTLA932W), WHICH INCLUDES THE TESTING |
| | FOR MISSLE IMPACT. SUBMIT THE CORRECT |
| | INSTALLATION DRAWINGS FOR THE 6'X 8' |
| | DOUBLE OUTSWING DOOR AT THE ENTRY. |
| | |
| | 5) THE OWNER LISTED ON THE PERMIT |
| | APPLICATION DOES NOT MATCH THE RECORDS |
| | OF THE COUNTY PROPERTY APPRAISER. SUBMIT |
| | A COPY OF THE RECORDED WARRANTY DEED |
| | LISTING THE NEW OWNER. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |