Plan Review Details - Permit 05040874
Plan Review Stops For Permit 05040874
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-06-28 Cont ID  
Sent By rmcdouga Date 2005-06-28 Time 15:37 Rev Time 0.00
Received By rmcdouga Date 2005-06-28 Time 15:37 Sent To  
Notes
2005-06-28 00:00:00PROVISO
  
 A SEPARATE PERMIT IS REQUIRED FOR THE
 METAL ROOF ON THE COPULA.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-23 Cont ID  
Sent By rmcdouga Date 2005-05-23 Time 12:45 Rev Time 0.00
Received By rmcdouga Date 2005-05-23 Time 12:45 Sent To  
Notes
2005-05-23 00:00:00DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE OWNER OF RECORD FOR THE PROPERTY
 ON THE PERMIT APPLICATION DOES NOT MATCH
 THE COUNTY PROPERTY APPRAISER'S RECORDS.
 SUBMIT A COPY OF THE WARRANTY DEED WITH
 NEW OWNER.
  
 3) THE USP JL28 AND JL210 HANGERS
 SPECIFIED ON SHEET 5B ARE NOT DESIGNED
 OR TESTED TO BE USED WITH TAPCONS.
 SPECIFY AN APPROPRIATE MASONRY HANGER.
  
 4) SUBMIT THE STATE COVERSHEET WITH THE
 FL# FOR THE METAL ROOF PANELS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
  
 5) SUBMIT THE TEST REPORTS FOR THE
 PLASTRO/NANYA GLAZED DOORS, INCLUDING
 LARGE MISSLE IMPACT TESTING. SUBMIT THE
 INSTALLATION DRAWINGS FROM THE FLORIDA
 PRODUCT APPROVAL WEBSITE FOR THE DOORS
 THAT WILL BE USED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-12-25 Cont ID  
Sent By dpalmer Date 2005-12-25 Time 11:29 Rev Time 0.00
Received By dpalmer Date 2005-12-25 Time 11:24 Sent To  
Notes
2005-12-25 00:00:00REV STAMPED

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-12-05 Cont ID  
Sent By dpalmer Date 2005-12-05 Time 07:36 Rev Time 0.00
Received By dpalmer Date 2005-12-05 Time 07:32 Sent To  
Notes
2005-12-05 00:00:00**** UNSAT ****
  
  
 1)NOTE: PLEASE SEE MAIN PANEL INDICATES
 TWO POOL SUB PANELS?
 PLEASE LIST ACCORD AND PLEASE SHOW ALL
 PANELS ON PLANS AND LABEL.
 215.5
  
 2)NOTE: PLEASE SUBMIT PANEL SCHEDULES
 FOR NEW PANEL "B" AND "C".
 SHOW LOADS.
 215.5
  
 3)NOTE: PLEASE SEE ORIG PLANS WERE
 REDLINED FOR REQUIRED GFI PROTECTION TO
 BE INDICATED FOR WHIRLPOOL/JACUZZI TUB.
 680.24
 PLANS INDICATE A SPEACIAL PURPOSE
 CONNECTION, HOWEVER COULD NOT LOCATE ANY
 INDICATION ON PANEL SCHEDULE OR LOAD
 CALCS OF A JACUZZI TUB?
 PLEASE CORRELATE AND SHOW.
 215.5
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-04-26 Cont ID  
Sent By dpalmer Date 2005-04-26 Time 12:00 Rev Time 0.25
Received By dpalmer Date 2005-04-26 Time 12:00 Sent To M
Notes
2005-04-26 00:00:00REDLINED 680.24 FOR GFI PROTECTION ON
 JACUZZI.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-12-22 Cont ID  
Sent By adarroug Date 2005-12-22 Time 14:54 Rev Time 0.00
Received By adarroug Date 2005-12-22 Time 14:54 Sent To E
Notes
2005-12-22 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-11-23 Cont ID  
Sent By adarroug Date 2005-11-23 Time 14:27 Rev Time 0.00
Received By adarroug Date 2005-11-23 Time 14:27 Sent To E
Notes
2005-11-23 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-26 Cont ID  
Sent By adarroug Date 2005-04-26 Time 11:00 Rev Time 0.00
Received By adarroug Date 2005-04-26 Time 11:00 Sent To E
Notes
2005-04-26 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-23 Cont ID  
Sent By rmcdouga Date 2005-05-23 Time 12:45 Rev Time 0.00
Received By rmcdouga Date 2005-04-15 Time 11:04 Sent To  
Notes
2005-04-15 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-06-28 Cont ID  
Sent By pkrauss Date 2005-06-28 Time 09:12 Rev Time 0.30
Received By pkrauss Date 2005-06-28 Time 09:12 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-05-02 Cont ID  
Sent By prafter Date 2005-05-02 Time 08:24 Rev Time 0.50
Received By prafter Date 2005-05-02 Time 08:24 Sent To B
Notes
2005-05-02 00:00:00MECH. PLAN REVIEW:
  
 PROVISO:
 AHU REQUIRED TO HAVE AUX. DRAIN PAN
 UNDER UNIT. FBC/M 307.2.3.
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-04-29 Cont ID  
Sent By kstevens Date 2005-04-29 Time 11:37 Rev Time 0.25
Received By kstevens Date 2005-04-29 Time 11:36 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-04-25 Cont ID  
Sent By mmclean Date 2005-04-25 Time 17:14 Rev Time 0.00
Received By mmclean Date 2005-04-25 Time 17:14 Sent To I
Notes
2005-04-25 00:00:00MUST PULL SEPERATE PERMIT FOR
 POOL/SPA/DECK/SCREEN ENCLOSURE.