Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-12-23 Cont ID  
Sent By rmcdouga Date 2005-12-23 Time 09:11 Rev Time 0.00
Received By rmcdouga Date 2005-12-23 Time 09:11 Sent To  
Notes
2005-12-23 00:00:00RESTAMPED PLANS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-06-28 Cont ID  
Sent By rmcdouga Date 2005-06-28 Time 13:25 Rev Time 0.00
Received By rmcdouga Date 2005-06-28 Time 13:25 Sent To  
Notes
2005-06-28 00:00:00PROVISO
  
 A SEPARATE PERMIT IS REQUIRED FOR THE
 METAL ROOF OF THE COPULA.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-06-20 Cont ID  
Sent By rmcdouga Date 2005-06-20 Time 14:29 Rev Time 0.00
Received By rmcdouga Date 2005-06-20 Time 14:29 Sent To  
Notes
2005-06-20 00:00:00DENIED
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE OWNER OF RECORD ON THE PERMIT
 APPLICATION IS DIFFERENT FROM THE OWNER
 LISTED WITH THE COUNTY PROPERTY
 APPRAISER. SUBMIT A RECORDED WARRANTY
 DEED FOR THE NEW OWNER.
  
 3) THE STATE PRODUCT APPROVAL SUBMITTED
 FOR THE METAL ROOF PANELS (FL 4504) FOR
 BARRIER METALS IS PENDING APPROVAL. IT
 MUST HAVE APPROVED STATUS BEFORE IT WILL
 BE ACCEPTED. THE NOA SUBMITTED WITH THIS
 COVER SHEET IS FOR A DIFFERENT COMPANY
 (JM METALS ROOFING MAN.). SEE COMMENT #3
 ON THE FIRST REVIEW.
  
 4) SUBMIT THE INSTALLATION DRAWINGS FOR
 THE 6'X 8' DOUBLE OUTSWING DOORS AT THE
 ENTRY. SEE COMMENT #4 ON THE FIRST
 REVIEW.
  
 5) SUBMIT STATE PRODUCT APPROVAL COVER
 SHEET WITH TEST REPORT AND INSTALLATION
 INSTRUCTIONS/DRAWINGS FOR THE SINGLE
 OUTSWING FRENCH DOOR (NON-IMPACT PER
 STORM PANEL SCHEDULE) AT THE MASTER
 SUITE. SEE COMMENT #4 FROM PREVIOUS
 REVIEW.
  
 IF YOU HAVE QUESTIONS, PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-16 Cont ID  
Sent By rmcdouga Date 2005-05-16 Time 08:48 Rev Time 0.00
Received By rmcdouga Date 2005-05-16 Time 07:14 Sent To  
Notes
2005-05-16 00:00:00DENIED
  
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE OWNER OF RECORD ON THE
 APPLICATION IS DIFFERENT FROM THE OWNER
 LISTED WITH THE COUNTY PROPERTY
 APPRAISER. SUBMIT A WARRANTY DEED FOR
 THE NEW OWNER.
  
 3) SUBMIT THE STATE PRODUCT APPROVAL
 COVER SHEET WITH THE FL # 1379 FOR THE
 METAL ROOF PANELS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
  
 4) SUBMIT ADDITIONAL INFORMATION FOR THE
 PLASTRO INC./NANYA PLASTICS CORP. DOORS.
 SUBMIT ALL 14 PAGES OF THE TEST REPORT #
 CTLA 932W (WHICH INCLUDES MISSLE IMPACT
 INFO). SUBMIT THE INSTALLATION DRAWINGS
 FOR THE 6'X 8' DOUBLE OUTSWING DOORS AT
 THE ENTRY AND THE SINGLE OUTSWING 8'
 DOOR AT THE MASTER BEDROOM. SEE THE PDF
 FILES ON THE STATE WEBSITE, DRAWINGS
 #99-07 AND #99-05.
  
 5) THE KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS IS FOR A
 DIFFERENT MODEL. SUBMIT CORRECT INFO.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-03-08 Cont ID  
Sent By dpalmer Date 2006-03-08 Time 13:06 Rev Time 0.00
Received By dpalmer Date 2006-03-08 Time 13:05 Sent To PC
Notes
2006-03-08 00:00:00REDLINED LOAD FOR DRYER, SHOWS 4.8KW,
 MIN REQUIRED 5.0 PER 220.18.
 LOAD IS OK FOR SERVICE, NO NEED TO
 REVISE PLANS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-12-25 Cont ID  
Sent By dpalmer Date 2005-12-25 Time 11:57 Rev Time 0.00
Received By dpalmer Date 2005-12-25 Time 11:42 Sent To  
Notes
2005-12-25 00:00:00REDLINED
  
 210.52 2' OF WALL.
 210.8A2 FOR GARAGE GFI RECEPTS.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-04-26 Cont ID  
Sent By dpalmer Date 2005-04-26 Time 12:20 Rev Time 0.25
Received By dpalmer Date 2005-04-26 Time 12:20 Sent To M
Notes
2005-04-26 00:00:00REDLINED.
 MISSING RECEPT ALONG GRT RM WALL. 210.52

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-03-04 Cont ID  
Sent By adarroug Date 2006-03-04 Time 17:04 Rev Time 0.00
Received By adarroug Date 2006-03-04 Time 17:04 Sent To E
Notes
2006-03-04 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-12-22 Cont ID  
Sent By adarroug Date 2005-12-22 Time 15:01 Rev Time 0.00
Received By adarroug Date 2005-12-22 Time 15:01 Sent To B
Notes
2005-12-22 00:00:00TO "RMCDOUGAL" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-12-22 Cont ID  
Sent By adarroug Date 2005-12-22 Time 14:57 Rev Time 0.00
Received By adarroug Date 2005-12-22 Time 14:57 Sent To E
Notes
2005-12-22 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-06-27 Cont ID  
Sent By adarroug Date 2005-06-27 Time 16:41 Rev Time 0.00
Received By adarroug Date 2005-06-27 Time 16:41 Sent To B
Notes
2005-06-27 00:00:00TO "RMCDOUGAL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-17 Cont ID  
Sent By shill Date 2005-06-17 Time 15:03 Rev Time 0.00
Received By shill Date 2005-06-17 Time 15:03 Sent To B
Notes
2005-06-17 00:00:00TO RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-26 Cont ID  
Sent By adarroug Date 2005-04-26 Time 10:46 Rev Time 0.00
Received By adarroug Date 2005-04-26 Time 10:46 Sent To E
Notes
2005-04-26 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-16 Cont ID  
Sent By rmcdouga Date 2005-05-16 Time 08:48 Rev Time 0.00
Received By rmcdouga Date 2005-04-15 Time 11:01 Sent To  
Notes
2005-04-15 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-04-27 Cont ID  
Sent By hmoser Date 2005-04-27 Time   Rev Time 0.00
Received By hmoser Date 2005-04-27 Time 17:12 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-04-29 Cont ID  
Sent By kstevens Date 2005-04-29 Time 10:39 Rev Time 0.25
Received By kstevens Date 2005-04-29 Time 10:39 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-04-25 Cont ID  
Sent By mmclean Date 2005-04-25 Time 18:08 Rev Time 0.00
Received By mmclean Date 2005-04-25 Time 18:08 Sent To I
Notes
2005-04-25 00:00:00MUST PULL A SEPERATE PERMIT FOR
 POOL/SPA/DECK/SCREEN ENCLOSURE.