Plan Review Details - Permit 05040757
Plan Review Stops For Permit 05040757
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-07-01 Cont ID  
Sent By lsmith Date 2005-07-01 Time 10:59 Rev Time 1.00
Received By lsmith Date 2005-07-01 Time 10:59 Sent To  
Notes
2005-07-01 00:00:00BUILDING PLAN REVIEW; PROVISO:
  
 VALUE OF POOL PER MARSHALL/SWIFT:
  
 DESCRIPTION OF WORK PER CONTRACT:
  
 33X27 POOL 3-5'6" WITH RAISED SPA &
 FOUNTAIN, GAS HEATER, ROCK WATERFALL,
 JANDY RS-8 SYSTEM & SURGE PROTECTOR,
 EXTRA UNDERWATER POOL LITE,
  
 TOTAL $45824.00NOTE:POOL PAVER DECK
 BY OTHERS & SEPARATE PERMIT IS REQUIRED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-07-01 Cont ID  
Sent By lsmith Date 2005-07-01 Time 09:56 Rev Time 0.25
Received By lsmith Date 2005-07-01 Time 09:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-06-02 Cont ID  
Sent By lsmith Date 2005-06-02 Time 12:50 Rev Time 0.50
Received By lsmith Date 2005-06-02 Time 12:50 Sent To  
Notes
2005-06-02 00:00:00BUILDING PLAN REVIEW: FAILED
  
 SEE PLUMBING NOTE #4 REGARDING VALUE.
  
  
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-05 Cont ID  
Sent By lsmith Date 2005-05-05 Time 08:15 Rev Time 0.50
Received By lsmith Date 2005-05-05 Time 08:15 Sent To  
Notes
2005-05-05 00:00:00BUILDING PLAN REVIEW: FAILED
  
 1. WHAT IS THE SQUARE FOOTAGE OF DECK.
 WHAT TYPE OF DECK.
  
 2. SEE PLUMBING NOTES REGARDING POOL
 VALUE.
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-06-02 Cont ID  
Sent By btrobaug Date 2005-06-02 Time 12:13 Rev Time 0.33
Received By btrobaug Date 2005-06-02 Time 12:06 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-04-22 Cont ID  
Sent By btrobaug Date 2005-04-22 Time 12:52 Rev Time 0.33
Received By btrobaug Date 2005-04-22 Time 12:45 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-06-07 Cont ID  
Sent By mjacobs Date 2005-06-07 Time 09:35 Rev Time 0.00
Received By mjacobs Date 2005-06-07 Time 09:35 Sent To P
Notes
2005-06-07 00:00:00SENT TO 'P' BOX.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-05-17 Cont ID  
Sent By adarroug Date 2005-05-17 Time 14:34 Rev Time 0.00
Received By adarroug Date 2005-05-17 Time 14:34 Sent To P
Notes
2005-05-17 00:00:00TO "KSTEVENS" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-21 Cont ID  
Sent By adarroug Date 2005-04-21 Time 17:04 Rev Time 0.00
Received By adarroug Date 2005-04-21 Time 17:03 Sent To E
Notes
2005-04-21 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-04-14 Cont ID  
Sent By adarroug Date 2005-04-14 Time 16:19 Rev Time 0.00
Received By adarroug Date 2005-04-14 Time 16:19 Sent To Z
Notes
2005-04-14 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-07-01 Cont ID  
Sent By kstevens Date 2005-07-01 Time 10:12 Rev Time 0.50
Received By kstevens Date 2005-07-01 Time 10:12 Sent To B1
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2005-06-22 Cont ID  
Sent By kstevens Date 2005-06-22 Time 07:57 Rev Time 0.50
Received By kstevens Date 2005-06-22 Time 07:57 Sent To B
Notes
2005-06-22 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 1. AS REQUIRED BY 104.3.1.1 OF THE CODE
 TWO OR MORE COPIES OF SPECIFICATIONS,
 AND OF DRAWINGS DRAWN TO SCALE WITH
 SUFFICIENT CLARITY AND DETAIL TO
 INDICATE THE NATURE AND CHARACTER OF THE
 WORK SHALL ACCOMPANY THE APPLICATION FOR
 A PERMIT. SECTION 104.2.1. HEATER
 SPECIFICATION SHEETS ARE UNCLEAR AND NOT
 LEGIBLE. SUBMIT SHEETS THAT CAN BE READ.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-06-01 Cont ID  
Sent By kstevens Date 2005-06-01 Time 19:19 Rev Time 0.50
Received By kstevens Date 2005-06-01 Time 19:19 Sent To E
Notes
2005-06-01 00:00:00DENIED
 REFERENCE: FBC-2001 424.4 SWIMMING POOLS
 FBC-2001 CHAPTER 1
  
 A. FROM PREVIOUS REVIEW:
 2) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 3) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUF. CUT SHEETS SUBMITTAL)
 4) 104.6.5 BUILDING PERMIT VALUATION. IF
 IN THE OPINION OF THE BUILDING OFFICIAL
 THE CLAIMED VALUATION OF BUILDING, AL-
 TERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION,
 THE PERMIT SHALL BE DENIED, UNLESS THE
 APPLICANT CAN SHOW DETAILED ESTIMATES
 AND/OR BONA FIDED SIGNED CONTRACTS (EX-
 CLUDING LAND VALUE) TO MEET THE APPROVAL
 OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION FOR BUILDINGS AND
 SYSTEMS SHALL BE FOUND IN MARSHALL AND
 SWIFT OR THE SOUTHERN BUILDING CODE
 CONGRESS INTERNATIONAL VALUATION TABLES,
 LATEST EDITION, AND SHALL BE BASED ON
 TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING, MECHAN-
 ICAL, INTERIOR FINISH, NORMAL SITE WORK
 (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, OVERHEAD
 AND PROFIT, EXCLUDING ONLY LAND VALUE. -
 THE VALUE OF $22,000 FOR THE POOL, SPA,
 HEATER, ROCK WATERFALL, EXTRA PUMPS,
 DECK ECT. IS NOT A PROPER VALUATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-04-28 Cont ID  
Sent By kstevens Date 2005-04-28 Time 16:37 Rev Time 0.75
Received By kstevens Date 2005-04-28 Time 16:37 Sent To B1
Notes
2005-04-28 00:00:00DENIED
 REFERENCE: FBC-2001 424.4 SWIMMING POOLS
 FBC-2001 CHAPTER 1
  
 1) SHT 1 POOL LAYOUT INDICATES NO VACUUM
 LINE, AS WELL AS THE EQUIPMENT LAYOUT
 LEGEND ON SHT 2, BUT POOL SPECIFICATS
 INDICATE A VACUUM LINE. PLEASE CORRELATE
 PLANS. SECTION 104.2.1.
 2) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 3) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUF. CUT SHEETS SUBMITTAL)
 4) 104.6.5 BUILDING PERMIT VALUATION. IF
 IN THE OPINION OF THE BUILDING OFFICIAL
 THE CLAIMED VALUATION OF BUILDING, AL-
 TERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION,
 THE PERMIT SHALL BE DENIED, UNLESS THE
 APPLICANT CAN SHOW DETAILED ESTIMATES
 AND/OR BONA FIDED SIGNED CONTRACTS (EX-
 CLUDING LAND VALUE) TO MEET THE APPROVAL
 OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION FOR BUILDINGS AND
 SYSTEMS SHALL BE FOUND IN MARSHALL AND
 SWIFT OR THE SOUTHERN BUILDING CODE
 CONGRESS INTERNATIONAL VALUATION TABLES,
 LATEST EDITION, AND SHALL BE BASED ON
 TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING, MECHAN-
 ICAL, INTERIOR FINISH, NORMAL SITE WORK
 (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, OVERHEAD
 AND PROFIT, EXCLUDING ONLY LAND VALUE. -
 THE VALUE OF $20,000 FOR THE POOL, SPA,
 HEATER, ROCK WATERFALL, EXTRA PUMPS,
 DECK ECT. IS NOT A PROPER VALUATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2005-04-20 Cont ID  
Sent By mmclean Date 2005-04-20 Time 11:43 Rev Time 0.00
Received By mmclean Date 2005-04-20 Time 11:43 Sent To I
Notes
***NONE***