| Plan Review Stops For Permit 05040757 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2005-07-01 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2005-07-01 |
Time |
10:59 |
Rev Time |
1.00 |
| Received By |
lsmith |
Date |
2005-07-01 |
Time |
10:59 |
Sent To |
|
|
| Notes |
| 2005-07-01 00:00:00 | BUILDING PLAN REVIEW; PROVISO: | | | | | | VALUE OF POOL PER MARSHALL/SWIFT: | | | | | | DESCRIPTION OF WORK PER CONTRACT: | | | | | | 33X27 POOL 3-5'6" WITH RAISED SPA & | | | FOUNTAIN, GAS HEATER, ROCK WATERFALL, | | | JANDY RS-8 SYSTEM & SURGE PROTECTOR, | | | EXTRA UNDERWATER POOL LITE, | | | | | | TOTAL $45824.00NOTE:POOL PAVER DECK | | | BY OTHERS & SEPARATE PERMIT IS REQUIRED. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2005-07-01 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2005-07-01 |
Time |
09:56 |
Rev Time |
0.25 |
| Received By |
lsmith |
Date |
2005-07-01 |
Time |
09:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-06-02 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2005-06-02 |
Time |
12:50 |
Rev Time |
0.50 |
| Received By |
lsmith |
Date |
2005-06-02 |
Time |
12:50 |
Sent To |
|
|
| Notes |
| 2005-06-02 00:00:00 | BUILDING PLAN REVIEW: FAILED | | | | | | SEE PLUMBING NOTE #4 REGARDING VALUE. | | | | | | | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 805-6713 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-05-05 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2005-05-05 |
Time |
08:15 |
Rev Time |
0.50 |
| Received By |
lsmith |
Date |
2005-05-05 |
Time |
08:15 |
Sent To |
|
|
| Notes |
| 2005-05-05 00:00:00 | BUILDING PLAN REVIEW: FAILED | | | | | | 1. WHAT IS THE SQUARE FOOTAGE OF DECK. | | | WHAT TYPE OF DECK. | | | | | | 2. SEE PLUMBING NOTES REGARDING POOL | | | VALUE. | | | | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 805-6713 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2005-06-02 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-06-02 |
Time |
12:13 |
Rev Time |
0.33 |
| Received By |
btrobaug |
Date |
2005-06-02 |
Time |
12:06 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2005-04-22 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-04-22 |
Time |
12:52 |
Rev Time |
0.33 |
| Received By |
btrobaug |
Date |
2005-04-22 |
Time |
12:45 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-06-07 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-06-07 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2005-06-07 |
Time |
09:35 |
Sent To |
P |
|
| Notes |
| 2005-06-07 00:00:00 | SENT TO 'P' BOX. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-05-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-05-17 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-05-17 |
Time |
14:34 |
Sent To |
P |
|
| Notes |
| 2005-05-17 00:00:00 | TO "KSTEVENS" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-04-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-04-21 |
Time |
17:04 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-04-21 |
Time |
17:03 |
Sent To |
E |
|
| Notes |
| 2005-04-21 00:00:00 | TO "E" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-04-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-04-14 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-04-14 |
Time |
16:19 |
Sent To |
Z |
|
| Notes |
| 2005-04-14 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2005-07-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-07-01 |
Time |
10:12 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2005-07-01 |
Time |
10:12 |
Sent To |
B1 |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2005-06-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-06-22 |
Time |
07:57 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2005-06-22 |
Time |
07:57 |
Sent To |
B |
|
| Notes |
| 2005-06-22 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 1 | | | | | | 1. AS REQUIRED BY 104.3.1.1 OF THE CODE | | | TWO OR MORE COPIES OF SPECIFICATIONS, | | | AND OF DRAWINGS DRAWN TO SCALE WITH | | | SUFFICIENT CLARITY AND DETAIL TO | | | INDICATE THE NATURE AND CHARACTER OF THE | | | WORK SHALL ACCOMPANY THE APPLICATION FOR | | | A PERMIT. SECTION 104.2.1. HEATER | | | SPECIFICATION SHEETS ARE UNCLEAR AND NOT | | | LEGIBLE. SUBMIT SHEETS THAT CAN BE READ. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2005-06-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-06-01 |
Time |
19:19 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2005-06-01 |
Time |
19:19 |
Sent To |
E |
|
| Notes |
| 2005-06-01 00:00:00 | DENIED | | | REFERENCE: FBC-2001 424.4 SWIMMING POOLS | | | FBC-2001 CHAPTER 1 | | | | | | A. FROM PREVIOUS REVIEW: | | | 2) FBC-2001 424.2.14.1 SWIMMING POOL | | | WATER HEATERS SHALL BEAR THE LABEL OF A | | | RECOGNIZED TESTING AGENCY. MANUFACTURE | | | SHEETS REQUIRED. (SUBMITTAL) | | | 3) FBC-2001 424.2.14.2 WATER RETENTION, | | | PROVIDE A POSITIVE MEANS OF RETAINING | | | WATER IN THE HEATER WHEN PUMP IS SHUT | | | OFF. (MANUF. CUT SHEETS SUBMITTAL) | | | 4) 104.6.5 BUILDING PERMIT VALUATION. IF | | | IN THE OPINION OF THE BUILDING OFFICIAL | | | THE CLAIMED VALUATION OF BUILDING, AL- | | | TERATION, STRUCTURE, ELECTRICAL, GAS, | | | MECHANICAL OR PLUMBING SYSTEMS APPEARS | | | TO BE UNDERESTIMATED ON THE APPLICATION, | | | THE PERMIT SHALL BE DENIED, UNLESS THE | | | APPLICANT CAN SHOW DETAILED ESTIMATES | | | AND/OR BONA FIDED SIGNED CONTRACTS (EX- | | | CLUDING LAND VALUE) TO MEET THE APPROVAL | | | OF THE BUILDING OFFICIAL. FOR PERMITTING | | | PURPOSES, VALUATION FOR BUILDINGS AND | | | SYSTEMS SHALL BE FOUND IN MARSHALL AND | | | SWIFT OR THE SOUTHERN BUILDING CODE | | | CONGRESS INTERNATIONAL VALUATION TABLES, | | | LATEST EDITION, AND SHALL BE BASED ON | | | TOTAL REPLACEMENT VALUE TO INCLUDE | | | STRUCTURAL, ELECTRIC, PLUMBING, MECHAN- | | | ICAL, INTERIOR FINISH, NORMAL SITE WORK | | | (EXCAVATION AND BACKFILL FOR BUILDINGS), | | | ARCHITECTURAL AND DESIGN FEES, OVERHEAD | | | AND PROFIT, EXCLUDING ONLY LAND VALUE. - | | | THE VALUE OF $22,000 FOR THE POOL, SPA, | | | HEATER, ROCK WATERFALL, EXTRA PUMPS, | | | DECK ECT. IS NOT A PROPER VALUATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-04-28 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-04-28 |
Time |
16:37 |
Rev Time |
0.75 |
| Received By |
kstevens |
Date |
2005-04-28 |
Time |
16:37 |
Sent To |
B1 |
|
| Notes |
| 2005-04-28 00:00:00 | DENIED | | | REFERENCE: FBC-2001 424.4 SWIMMING POOLS | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT 1 POOL LAYOUT INDICATES NO VACUUM | | | LINE, AS WELL AS THE EQUIPMENT LAYOUT | | | LEGEND ON SHT 2, BUT POOL SPECIFICATS | | | INDICATE A VACUUM LINE. PLEASE CORRELATE | | | PLANS. SECTION 104.2.1. | | | 2) FBC-2001 424.2.14.1 SWIMMING POOL | | | WATER HEATERS SHALL BEAR THE LABEL OF A | | | RECOGNIZED TESTING AGENCY. MANUFACTURE | | | SHEETS REQUIRED. (SUBMITTAL) | | | 3) FBC-2001 424.2.14.2 WATER RETENTION, | | | PROVIDE A POSITIVE MEANS OF RETAINING | | | WATER IN THE HEATER WHEN PUMP IS SHUT | | | OFF. (MANUF. CUT SHEETS SUBMITTAL) | | | 4) 104.6.5 BUILDING PERMIT VALUATION. IF | | | IN THE OPINION OF THE BUILDING OFFICIAL | | | THE CLAIMED VALUATION OF BUILDING, AL- | | | TERATION, STRUCTURE, ELECTRICAL, GAS, | | | MECHANICAL OR PLUMBING SYSTEMS APPEARS | | | TO BE UNDERESTIMATED ON THE APPLICATION, | | | THE PERMIT SHALL BE DENIED, UNLESS THE | | | APPLICANT CAN SHOW DETAILED ESTIMATES | | | AND/OR BONA FIDED SIGNED CONTRACTS (EX- | | | CLUDING LAND VALUE) TO MEET THE APPROVAL | | | OF THE BUILDING OFFICIAL. FOR PERMITTING | | | PURPOSES, VALUATION FOR BUILDINGS AND | | | SYSTEMS SHALL BE FOUND IN MARSHALL AND | | | SWIFT OR THE SOUTHERN BUILDING CODE | | | CONGRESS INTERNATIONAL VALUATION TABLES, | | | LATEST EDITION, AND SHALL BE BASED ON | | | TOTAL REPLACEMENT VALUE TO INCLUDE | | | STRUCTURAL, ELECTRIC, PLUMBING, MECHAN- | | | ICAL, INTERIOR FINISH, NORMAL SITE WORK | | | (EXCAVATION AND BACKFILL FOR BUILDINGS), | | | ARCHITECTURAL AND DESIGN FEES, OVERHEAD | | | AND PROFIT, EXCLUDING ONLY LAND VALUE. - | | | THE VALUE OF $20,000 FOR THE POOL, SPA, | | | HEATER, ROCK WATERFALL, EXTRA PUMPS, | | | DECK ECT. IS NOT A PROPER VALUATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2005-04-20 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-04-20 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-04-20 |
Time |
11:43 |
Sent To |
I |
|
| Notes |
|
|