| Plan Review Stops For Permit 05040742 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2005-06-15 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-06-15 |
Time |
09:25 |
Rev Time |
1.50 |
| Received By |
alange |
Date |
2005-06-15 |
Time |
07:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-05-09 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-05-09 |
Time |
11:03 |
Rev Time |
1.66 |
| Received By |
alange |
Date |
2005-05-09 |
Time |
09:13 |
Sent To |
|
|
| Notes |
| 2005-05-09 00:00:00 | DENIED | | | | | | 1.PLEASE SIGN OWNER/AGENT ON ENERGY | | | CALCS. | | | | | | 2.SUBMIT TWO COPIES OF PRODUCT | | | APPROVALS FOR WINDOW MULLIONS. | | | ALL PRODUCT APPROVALS SUBMITTED REQUIRE | | | THE FOLLOWING TO BE ATTACHED. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | ANY QUESTIONS CALL ME. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2006-04-17 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-04-17 |
Time |
10:02 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-04-17 |
Time |
06:34 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-03-28 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-03-28 |
Time |
06:50 |
Rev Time |
0.33 |
| Received By |
btrobaug |
Date |
2006-03-28 |
Time |
06:44 |
Sent To |
PC |
|
| Notes |
| 2006-03-28 00:00:00 | | | | | | | ALL CHANGES TO THE PLAN MUST BE MADE BY | | | THE DESIGNER OF RECORD (ENGINEER) PER | | | ARTICLE 471 FLORIDA STATUTED. | | | WHITE OUT ON THE PLAN IS NOT ACCEPTABLE. | | | RETURN THE PLANS TO THE ENGINEER TO BE | | | REDRAWN AND RESUBMIT FOR REVIEW. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2005-04-29 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-04-29 |
Time |
12:18 |
Rev Time |
0.33 |
| Received By |
btrobaug |
Date |
2005-04-29 |
Time |
11:58 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2005-04-13 |
|
|
Cont ID |
|
| Sent By |
spalmer |
Date |
2005-04-13 |
Time |
11:42 |
Rev Time |
0.15 |
| Received By |
spalmer |
Date |
2005-04-13 |
Time |
11:42 |
Sent To |
|
|
| Notes |
| 2005-04-13 00:00:00 | OKAY PER NEELAM FATIMA |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-04-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-04-12 |
Time |
16:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-04-12 |
Time |
16:11 |
Sent To |
E |
|
| Notes |
| 2006-04-12 00:00:00 | TO "BTROBAUG" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-03-24 |
|
|
Cont ID |
|
| Sent By |
spalmer |
Date |
2006-03-24 |
Time |
17:40 |
Rev Time |
0.00 |
| Received By |
spalmer |
Date |
2006-03-24 |
Time |
17:40 |
Sent To |
E |
|
| Notes |
| 2006-03-24 00:00:00 | TO BT DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-05-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-05-27 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-05-27 |
Time |
11:11 |
Sent To |
M |
|
| Notes |
| 2005-05-27 00:00:00 | TO "PKRAUSS" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-04-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-04-27 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-04-27 |
Time |
16:32 |
Sent To |
E |
|
| Notes |
| 2005-04-27 00:00:00 | TO "E" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-05-09 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-05-09 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2005-04-15 |
Time |
10:15 |
Sent To |
|
|
| Notes |
| 2005-04-15 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2005-05-28 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2005-05-28 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2005-05-28 |
Time |
10:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-05-02 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2005-05-02 |
Time |
|
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2005-05-02 |
Time |
14:59 |
Sent To |
B |
|
| Notes |
| 2005-05-02 00:00:00 | PLAN DENIED | | | 1) YOU CAN NOT TIE 12IN.DUCT IN A 12X8 | | | CAN. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2005-06-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-06-14 |
Time |
06:55 |
Rev Time |
0.25 |
| Received By |
kstevens |
Date |
2005-06-14 |
Time |
06:54 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-05-02 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-05-02 |
Time |
13:38 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2005-05-02 |
Time |
13:38 |
Sent To |
M |
|
| Notes |
| 2005-05-02 00:00:00 | DENIED | | | REFERENCE; FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT A1 SANITARY RISER DIAGRAM DOES | | | NOT MEET CODE REQUIREMENTS: | | | A. TRAP REQUIRED FOR SHOWER SEC 1002.1 | | | B. SHOW ALL PIPE SIZES TABLE 710.1(1) | | | C. WASH MACHINE TRAP SHALL CONNECT LOW | | | ON THE STACK FOR STANDPIPE. SECTION | | | 1002.1 (SEE RED LINE CORRECTIONS ON ONE | | | SET OF PLANS). | | | 2) INFORMATIONAL THE CLEANOUT OPPOSITE | | | OF THE W/C IS NOT REQUIRED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2005-04-26 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-04-26 |
Time |
18:02 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-04-26 |
Time |
18:02 |
Sent To |
I |
|
| Notes |
|
|