| Plan Review Stops For Permit 05040736 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2006-06-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-06-20 |
Time |
11:39 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-06-20 |
Time |
11:39 |
Sent To |
|
|
| Notes |
| 2006-06-20 00:00:00 | REVISION 5/31/06 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2006-04-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-04-20 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-04-20 |
Time |
16:02 |
Sent To |
|
|
| Notes |
| 2006-04-20 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)PROVIDE SPECS FROM MANUFACTURER TO | | | SHOW THAT THE EXISTING ROOF SYSTEM HAS A | | | PEDESTRIAN SURFACE. | | | | | | 2.)IS THIS AREA DESIGNED AS A TERRACE? | | | IF NOT, PROVIDE DESIGN LOAD INFORMATION | | | FBC16. | | | | | | 3.)THE NOTE ON THE PLAN INDICATES THAT | | | THE NEW DOOR IS NOT AN EGRESS DOOR. | | | WHAT IS THE MEANS OF EGRESS FROM THIS | | | AREA?ONLY ONE IS SHOWN. | | | | | | 4.)PROVIDE DESIGN PRESSURE | | | REQUIREMENTS FOR THE DOOR. | | | | | | 5.)PROVIDE PRODUCT APPROVALS FOR THE | | | DOOR.FLORIDA STATE OR LOCAL PRODUCT | | | APPROVAL REQUIRED, FAC9B72. | | | WWW.FLORIDABUILDING.ORG. | | | | | | 6.)PROVIDE THE ELEVATION DIFFERENCE | | | BETWEEN THE TERRACE AND THE ADJOINING | | | SPACE (ACCESSIBLE ROUTE), | | | FBC11-4.1.6(1)(B). | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2006-01-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-01-13 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-01-13 |
Time |
16:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2005-06-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-06-29 |
Time |
16:05 |
Rev Time |
3.00 |
| Received By |
shill |
Date |
2005-06-29 |
Time |
16:05 |
Sent To |
|
|
| Notes |
| 2005-06-29 00:00:00 | ***PROVISO*** ROOFING PRODUCT APPROVALS | | | TO BE SUBMITTED WITH ROOF PERMIT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2005-06-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-06-29 |
Time |
13:26 |
Rev Time |
2.00 |
| Received By |
shill |
Date |
2005-06-29 |
Time |
07:34 |
Sent To |
|
|
| Notes |
| 2005-06-29 00:00:00 | ****CORRECTIONS**** | | | LOCAL PRODUCT APPROVAL | | | SUBMITTED BY ADVANCED ROOFING | | | 954-868-0063 | | | | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.) A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED, FS713.13. | | | | | | 2.)THE TESTING LAB IS NOT AN APPROVED | | | TESTING LABORATORY, FAC9B72.100(3). | | | | | | 3.)THE THIRD PARTY QUALITY ASSURANCE | | | ENTITY LISTED ON THE APPLICATION | | | (UNDERWRITERS LABORATORY) HAS AN | | | EXPIRATION DATE OF 6/30/2005.PRIOR TO | | | RESUBMITTAL, PLEASE CONFIRM THAT THEIR | | | APPROVAL WITH THE STATE IS CURRENT. | | | WWW.FLORIDABUILDING.ORG | | | | | | 4.)THE PREVIOUS SUBMITTAL PROVIDED A | | | DESIGN PRESSURE OF -263.8.THIS | | | SUBMITTAL GIVES A DP OF -321 FOR ZONE 3. | | | IT IS ACCEPTABLE TO INCREASE THE DP | | | REQUIREMENT, BUT I AM BRINGING THIS | | | DISCREPANCY TO YOUR ATTENTION. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-06-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-06-11 |
Time |
16:33 |
Rev Time |
2.50 |
| Received By |
shill |
Date |
2005-06-11 |
Time |
16:33 |
Sent To |
PC |
|
| Notes |
| 2005-06-11 00:00:00 | ****CORRECTIONS**** | | | ROOF SITE SPECIFIC PRODUCT APPROVAL | | | SUBMITTED BY ADVANCED ROOFING | | | 954-868-0063 | | | | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.) A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED, FS713.13. | | | | | | 2.)PLEASE COMPLETE ITEM #1 ON THE | | | APPLICATION FOR LOCAL PRODUCT APPROVAL, | | | FAC9B-72.040(2). | | | | | | 3.)THE THIRD PARTY QUALITY ASSURANCE | | | ENTITY LISTED ON THE APPLICATION | | | (EXTERIOR RESEARCH AND DESIGN, LLC) IS | | | NOT AN APPROVED ENTITY. | | | WWW.FLORIDABUILDING.ORG | | | | | | 4.)THE LETTER PREPARED BY ROBERT | | | NIEMINEN, PE DATED 5/27/05 GIVES A | | | DESIGN PRESSURE OF -263.8 FOR ZONE 3. | | | THE LETTER DATED 1/3/05 GIVES A SYSTEM | | | LIMITATION OF -262.5.IT APPEARS THAT | | | THE DP EXCEEDS THE TESTED SYSTEM | | | LIMITATION.PLEASE ADDRESS. | | | | | | 5.)SUBMIT THE EVALUATOR'S | | | CERTIFICATION OF INDEPENDENCE IN | | | CONFORMANCE WITH FAC9B72.110, | | | FAC9B72.040(5)(G). |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-05-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-05-13 |
Time |
10:59 |
Rev Time |
3.00 |
| Received By |
shill |
Date |
2005-05-12 |
Time |
20:51 |
Sent To |
|
|
| Notes |
| 2005-05-13 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.) A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2.)EACH DRAWING SHEET IS TO HAVE A | | | TITLE BLOCK WITH ALL INFORMATION | | | REQUIRED BY FAC61G1-16.003, .004.THE | | | INDEX SHEET FOR THE SPECIFICATIONS | | | SHOULD ALSO INCLUDE A TITLE BLOCK.SOME | | | DRAWING SHEETS WERE NOT SEALED OR DATED. | | | | | | 3.)PROVIDE DESIGN PRESSURES FOR THE | | | ROOFS.PLEASE NOTE THAT THE ?KRAVIS: | | | REROOF OUTLINE SPECIFICATION & | | | CRITERIA?, WALKWAY & CANOPY ROOFS | | | SPECIFY 140MPH, AND LATER STATES ?TO | | | MEET MIAMI-DADE CODE CRITERIA FOR | | | MAXIMUM WIND UPLIFT RESISTANCE.? | | | MIAMI-DADE IS IN THE 146MPH ZONE. | | | | | | 4.)HAS AN INDEPENDENT INSPECTOR OR | | | ENGINEER BEEN RETAINED TO SUPERVISE THIS | | | WORK?IF THIS HAS NOT BEEN DONE, PLEASE | | | CONSIDER THIS TO EXPEDITE INSPECTIONS. | | | PLEASE ADVISE. | | | | | | 5.)SEPARATE PERMITS REQUIRED (ROOFING, | | | ELECTRIC, MECHANICAL). | | | | | | 6.)PLEASE INDICATE WHICH APPROVED | | | ASSEMBLY YOU ARE USING ON THE NOAS.IF | | | YOU ARE USING MORE THAN ONE ASSEMBLY, | | | INDICATE LOCATION. CODE COMPLIANCE FOR | | | THE NOAS SUBMITTED HAS NOT BEEN | | | DETERMINED PENDING ROOF DESIGN PRESSURES | | | AND INDICATION OF APPROVED ASSEMBLY. | | | | | | 7.)IS MECHANICAL FASTENING THROUGH THE | | | STRUCTURAL DECK PROPOSED FOR THE REROOF? | | | TESTING AND ENGINEERING MAY BE REQUIRED; | | | SEE NOAS. | | | | | | 8.)THE REROOF SPECIFICATION SPECIFIES | | | ROOFING OVER EXISTING TEMPORARY | | | MEMBRANES.THE NOAS SUBMITTED ARE FOR | | | REROOFS.A SEPARATE NOA IS REQUIRED FOR | | | RECOVER.IF THE METHOD OF INSTALLATION | | | CONFLICTS WITH THE MANUFACTURER?S | | | SPECIFICATIONS, A LOCAL PRODUCT APPROVAL | | | WILL BE REQUIRED FAC9B-72. | | | | | | 9.)VARIOUS SHEETS, ?NEW PEEL & STICK | | | LAYER?, LOUVERS, AND STANDING SEAM METAL | | | SPECIFIED.PROVIDE PRODUCT APPROVALS, | | | FAC9B72. | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2005-12-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-12-31 |
Time |
18:57 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-12-31 |
Time |
18:37 |
Sent To |
I |
|
| Notes |
| 2005-12-31 00:00:00 | IN ELEC FOR REVIEW, FROM INCOMING. | | | **** NOTES**** | | | | | | STAMPED LIGHTNING PROTECTION SYSTEM, | | | SUBMITTED FOR BONDED LIGHTNING. | | | NO OTHER ELECTRICAL PLANS SUBMITTED FOR | | | REVIEW. | | | ANY DISCONNECTING FOR RE-ROOF AND | | | RE-CONNECTS TO BE FEILD VERIFIED FOR ALL | | | ELECTRICAL ON ROOF TO BE BROUGHT UP TO | | | CURRENT CODE FOR SIZE, STRAPPING, | | | SUPPORT STEC. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2005-06-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-06-30 |
Time |
17:04 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2005-06-30 |
Time |
12:05 |
Sent To |
|
|
| Notes |
| 2005-06-30 00:00:00 | ******** UNSAT ******* | | | | | | 1)NOTE: PLEASE SEE ELECTRICAL PLANS FOR | | | LIGHTNING PROTECTION SYSTEM MUST CONTAIN | | | THE PRINTED NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR PLANS AND DESIGN. | | | FBC 104.2.1 | | | | | | 2)NOTE: PLEASE SEE MISSING CERTIFICATE | | | OF AUTHORIZATION # ON TITLE BLOCKS OF | | | PLANS. | | | PLEASE SEE FAC 61G1-16.004 AND FS | | | 481.219. THIS WAS REQUESTED ON PREVIOUS | | | REVIEW AND IS REQUIRED PER ABOVE. | | | THIS IS REQUIRED ON ALL SHEETS AND FOR | | | ALL TRADES WHEATHER OR NOT COMMENT IS | | | MADE BY OTHER REVIEWER(S). THIS MAY BE | | | PRINTED, STAMPED ETC ON EXISTING SHEETS. | | | | | | 3)NOTE: PLEASE SEE SHEETS WHICH NOTE | | | EXISTING ELECTRICAL TO REMAIN WHICH IS | | | SHOWN ON PICS TOBE VIOLATIONS OF NEC | | | WILL BE REQUIRED TO BROUGHT UP TO CODE. | | | THIS WILL BE A FIELD VERIFICATION AND IS | | | ONLY NOTED FOR INFORMATION. | | | PLANS WILL BE REDLINED AND NOTED FOR | | | THIS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-04-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-04-25 |
Time |
19:28 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-04-25 |
Time |
19:24 |
Sent To |
|
|
| Notes |
| 2005-04-25 00:00:00 | ******* UNSAT ********** | | | | | | 1)NOTE: PLEASE SEE NOE ELECTRICAL PLANS | | | FOR PROPOSED WORK WAS SUBMITTED, HOWEVER | | | AND ELECTRICAL PERMIT IS BEING | | | REQUESTED. | | | PLEASE SUBMIT ELECTRICAL DETAILS FOR | | | ELECTRICAL WORK BEING APPLIED FOR. | | | PLEASE SUBMIT SIGNED, SEALED PLANS BY A | | | FL REG PE. FS 471.003. | | | 215.5 | | | | | | 2)NOTE: PLEASE SEE FS 481.229 WHICH | | | REQUIRES PLANS TO BE SIGNED, DATED AND | | | SEALED FOR WORK OVER $25K FOR COMMERCIAL | | | BLDG. | | | PLEASE ALSO SEE PLANS WHICH CONTAIN A | | | TITLE BLOCK FOR AN ARCHITECTUAL FIRM ARE | | | REQUIRED TO BE SIGNED, DATED AND SEALED | | | BY SAID FIRM. | | | TITLE BLOCK SHALL CONTAIN ALL | | | INFORMATION AS SET-FORTH IN FAC | | | 61G1-16.004 , FS 481.219, 481.221 | | | PLEASE ALSO SEE ANY SHEETS BEING SIGNED | | | AND SEALED, MUST CONTAIN A TITLE BLOCK | | | AS STATED ABOVE. | | | | | | 3)NOTE: IF LIGHTNING PROTECTION SYSTEM | | | IS GOING TO BE INSTALLED AND UNDER THE | | | RESPONSIBLITY AND PERMIT OF ELECTRICAL | | | CONTRACTOR SIGNED ON APPLICATION, THEN | | | COMPLETE PLANS FOR INSTALLATIOON SHOWING | | | ALL DETAILS AND INSTALLATION OF SYSTEM | | | PER NFPA-780 SHALL BE SUBMITTED. | | | IF LIGHTING PROTECTION SYSTEM WILL BE A | | | SEPARATE PERMIT/PLANS, PLEASE REMOVE | | | FROM APPLICATION AND FROM PROPOSED WORK | | | ON DRAWINGS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2006-01-04 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-01-04 |
Time |
09:16 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-01-04 |
Time |
09:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2005-07-15 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-07-15 |
Time |
15:31 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-07-15 |
Time |
15:31 |
Sent To |
|
|
| Notes |
| 2005-07-15 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE SEE OTHER REVIEW COMMENTS IN | | | REGARDS TO FBC, FS AND FAC REQUIREMENTS | | | AND MAKE CORRECTIONS. | | | | | | 2) WILL THIS WORK IMPACT EXISTING LIFE | | | SAFETY EQUIPMENT? THIS COMMENT WAS NOT | | | ADDRESSED FROM LAST REVIEW. | | | | | | | | | MIKE WENNERGREN, CAPTAIN | | | WPBFR(561) 805-6722 OR 835-2951 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-05-12 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-05-12 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-05-12 |
Time |
14:26 |
Sent To |
|
|
| Notes |
| 2005-05-12 00:00:00 | 1) PLEASE REFER TO OTHER COMMENTS IN | | | REGARDS TO REQUIREMENTS FOR COMMERCIAL | | | BUILDINGS. | | | | | | 2) PLEASE SUBMIT ADDITIONAL INFORMATION | | | AND DETAILS REGARDING THE NEW LIGHTNING | | | PROTECTION SYSTEM. | | | | | | 3) WILL THIS WORK IMPACT ANY EXISTING | | | LIFE SAFETY EQUIPMENT ON OR NEAR THE | | | ROOF? | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 835-2910 OR 805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2006-06-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-15 |
Time |
09:59 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-15 |
Time |
09:59 |
Sent To |
P |
|
| Notes |
| 2006-06-15 00:00:00 | TO "PSHCMITZ" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2006-05-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-26 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-26 |
Time |
14:22 |
Sent To |
P |
|
| Notes |
| 2006-05-26 00:00:00 | TO "MPERSON" DESK/REV-PER "RBROWN" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-04-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-04-18 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-04-18 |
Time |
09:37 |
Sent To |
B |
|
| Notes |
| 2006-04-18 00:00:00 | TO "SHILL" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-01-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-01-13 |
Time |
08:59 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-01-13 |
Time |
08:59 |
Sent To |
B |
|
| Notes |
| 2006-01-13 00:00:00 | TO "SHILL" DESK/RESUB-NEW SHEETS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-12-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-12-05 |
Time |
16:42 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-12-05 |
Time |
16:42 |
Sent To |
|
|
| Notes |
| 2006-01-03 00:00:00 | TO "COMM" BD#42 | | 2005-12-05 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-06-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-06-20 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-06-20 |
Time |
13:17 |
Sent To |
|
|
| Notes |
| 2005-06-22 00:00:00 | TO "COMM" BD#44 | | 2005-06-20 00:00:00 | WAITING FOR COMM BOARD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-04-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-04-18 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-04-18 |
Time |
10:32 |
Sent To |
|
|
| Notes |
| 2005-04-18 00:00:00 | TO "COMM" BD#64 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2006-01-09 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-01-09 |
Time |
07:49 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-01-09 |
Time |
06:51 |
Sent To |
|
|
| Notes |
| 2006-01-09 00:00:00 | PROVISO: | | | | | | SMOKE EVAC TEST REQUIRED AT FINAL | | | INPECTION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2005-07-19 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2005-07-19 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2005-07-19 |
Time |
11:19 |
Sent To |
|
|
| Notes |
| 2005-07-19 00:00:00 | PLAN DENIED | | | COMMENTS WERE NOT ANCERED FROM LAST | | | REVIEWS. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-05-20 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-05-20 |
Time |
07:15 |
Rev Time |
0.55 |
| Received By |
pkrauss |
Date |
2005-05-20 |
Time |
07:15 |
Sent To |
|
|
| Notes |
| 2005-05-20 00:00:00 | DENIED: | | | 1.PLANS ARE TO BE SIGNED, SEALED AND | | | DATED IS ACCORDANCE WITH FS471.025 FAC | | | 61G15-23.002 (2). | | | | | | 2.INDICATE IF THE EXISTING CURBS ARE | | | TO BE REPLACED OR RE-USED.PROVIDE | | | DETAILS FOR ANY NEW INSTALLATIONS. | | | | | | 3.PROVIDE A SCHEDULE OF EQUIPMENT THAT | | | WILL BE REMOVED FOR RE-ROOFING PROCESS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2006-06-16 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-06-16 |
Time |
15:22 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-06-16 |
Time |
15:22 |
Sent To |
PC |
|
| Notes |
| 2006-06-16 00:00:00 | THIS PLUMBING PLAN REVIEW DELETED TRENCH | | | DRAIN, ONLY. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2006-06-14 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-06-14 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-06-14 |
Time |
09:13 |
Sent To |
PC |
|
| Notes |
| 2006-06-14 00:00:00 | RETURN TO CONTRACTOR PER CRAIG MONOHAN | | | FOR THE MOOST CURRENT REVISION 5-31-06 | | | DELETING TRENCH DRAINS. | | | QUESTIONS 561-805-6692PES |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2006-06-09 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-06-09 |
Time |
13:09 |
Rev Time |
1.25 |
| Received By |
mperson |
Date |
2006-06-09 |
Time |
13:09 |
Sent To |
B |
|
| Notes |
| 2006-06-09 00:00:00 | REVISION: ADD TRENCH DRAIN TO TIE INTO | | | EXISTING STORM SYSTEM, AND WORK ON | | | CONDENSATE | | | | | | NOTE: SEPERATE PLUMBING PERMIT REQUIRED | | | REFERENCE PERMIT #05040736 AND SHEETS | | | SKH-22A THROUGH SKH-22E ON PLUMBING | | | PERMIT APPLICATION. |
|
|