Plan Review Details - Permit 05040736
Plan Review Stops For Permit 05040736
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2006-06-20 Cont ID  
Sent By shill Date 2006-06-20 Time 11:39 Rev Time 0.00
Received By shill Date 2006-06-20 Time 11:39 Sent To  
Notes
2006-06-20 00:00:00REVISION 5/31/06

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2006-04-20 Cont ID  
Sent By shill Date 2006-04-20 Time 16:02 Rev Time 0.00
Received By shill Date 2006-04-20 Time 16:02 Sent To  
Notes
2006-04-20 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)PROVIDE SPECS FROM MANUFACTURER TO
 SHOW THAT THE EXISTING ROOF SYSTEM HAS A
 PEDESTRIAN SURFACE.
  
 2.)IS THIS AREA DESIGNED AS A TERRACE?
 IF NOT, PROVIDE DESIGN LOAD INFORMATION
 FBC16.
  
 3.)THE NOTE ON THE PLAN INDICATES THAT
 THE NEW DOOR IS NOT AN EGRESS DOOR.
 WHAT IS THE MEANS OF EGRESS FROM THIS
 AREA?ONLY ONE IS SHOWN.
  
 4.)PROVIDE DESIGN PRESSURE
 REQUIREMENTS FOR THE DOOR.
  
 5.)PROVIDE PRODUCT APPROVALS FOR THE
 DOOR.FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED, FAC9B72.
 WWW.FLORIDABUILDING.ORG.
  
 6.)PROVIDE THE ELEVATION DIFFERENCE
 BETWEEN THE TERRACE AND THE ADJOINING
 SPACE (ACCESSIBLE ROUTE),
 FBC11-4.1.6(1)(B).
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-01-13 Cont ID  
Sent By shill Date 2006-01-13 Time 16:32 Rev Time 0.00
Received By shill Date 2006-01-13 Time 16:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-06-29 Cont ID  
Sent By shill Date 2005-06-29 Time 16:05 Rev Time 3.00
Received By shill Date 2005-06-29 Time 16:05 Sent To  
Notes
2005-06-29 00:00:00***PROVISO*** ROOFING PRODUCT APPROVALS
 TO BE SUBMITTED WITH ROOF PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-06-29 Cont ID  
Sent By shill Date 2005-06-29 Time 13:26 Rev Time 2.00
Received By shill Date 2005-06-29 Time 07:34 Sent To  
Notes
2005-06-29 00:00:00****CORRECTIONS****
 LOCAL PRODUCT APPROVAL
 SUBMITTED BY ADVANCED ROOFING
 954-868-0063
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.)THE TESTING LAB IS NOT AN APPROVED
 TESTING LABORATORY, FAC9B72.100(3).
  
 3.)THE THIRD PARTY QUALITY ASSURANCE
 ENTITY LISTED ON THE APPLICATION
 (UNDERWRITERS LABORATORY) HAS AN
 EXPIRATION DATE OF 6/30/2005.PRIOR TO
 RESUBMITTAL, PLEASE CONFIRM THAT THEIR
 APPROVAL WITH THE STATE IS CURRENT.
 WWW.FLORIDABUILDING.ORG
  
 4.)THE PREVIOUS SUBMITTAL PROVIDED A
 DESIGN PRESSURE OF -263.8.THIS
 SUBMITTAL GIVES A DP OF -321 FOR ZONE 3.
 IT IS ACCEPTABLE TO INCREASE THE DP
 REQUIREMENT, BUT I AM BRINGING THIS
 DISCREPANCY TO YOUR ATTENTION.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-06-11 Cont ID  
Sent By shill Date 2005-06-11 Time 16:33 Rev Time 2.50
Received By shill Date 2005-06-11 Time 16:33 Sent To PC
Notes
2005-06-11 00:00:00****CORRECTIONS****
 ROOF SITE SPECIFIC PRODUCT APPROVAL
 SUBMITTED BY ADVANCED ROOFING
 954-868-0063
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.)PLEASE COMPLETE ITEM #1 ON THE
 APPLICATION FOR LOCAL PRODUCT APPROVAL,
 FAC9B-72.040(2).
  
 3.)THE THIRD PARTY QUALITY ASSURANCE
 ENTITY LISTED ON THE APPLICATION
 (EXTERIOR RESEARCH AND DESIGN, LLC) IS
 NOT AN APPROVED ENTITY.
 WWW.FLORIDABUILDING.ORG
  
 4.)THE LETTER PREPARED BY ROBERT
 NIEMINEN, PE DATED 5/27/05 GIVES A
 DESIGN PRESSURE OF -263.8 FOR ZONE 3.
 THE LETTER DATED 1/3/05 GIVES A SYSTEM
 LIMITATION OF -262.5.IT APPEARS THAT
 THE DP EXCEEDS THE TESTED SYSTEM
 LIMITATION.PLEASE ADDRESS.
  
 5.)SUBMIT THE EVALUATOR'S
 CERTIFICATION OF INDEPENDENCE IN
 CONFORMANCE WITH FAC9B72.110,
 FAC9B72.040(5)(G).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-13 Cont ID  
Sent By shill Date 2005-05-13 Time 10:59 Rev Time 3.00
Received By shill Date 2005-05-12 Time 20:51 Sent To  
Notes
2005-05-13 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)EACH DRAWING SHEET IS TO HAVE A
 TITLE BLOCK WITH ALL INFORMATION
 REQUIRED BY FAC61G1-16.003, .004.THE
 INDEX SHEET FOR THE SPECIFICATIONS
 SHOULD ALSO INCLUDE A TITLE BLOCK.SOME
 DRAWING SHEETS WERE NOT SEALED OR DATED.
  
 3.)PROVIDE DESIGN PRESSURES FOR THE
 ROOFS.PLEASE NOTE THAT THE ?KRAVIS:
 REROOF OUTLINE SPECIFICATION &
 CRITERIA?, WALKWAY & CANOPY ROOFS
 SPECIFY 140MPH, AND LATER STATES ?TO
 MEET MIAMI-DADE CODE CRITERIA FOR
 MAXIMUM WIND UPLIFT RESISTANCE.?
 MIAMI-DADE IS IN THE 146MPH ZONE.
  
 4.)HAS AN INDEPENDENT INSPECTOR OR
 ENGINEER BEEN RETAINED TO SUPERVISE THIS
 WORK?IF THIS HAS NOT BEEN DONE, PLEASE
 CONSIDER THIS TO EXPEDITE INSPECTIONS.
 PLEASE ADVISE.
  
 5.)SEPARATE PERMITS REQUIRED (ROOFING,
 ELECTRIC, MECHANICAL).
  
 6.)PLEASE INDICATE WHICH APPROVED
 ASSEMBLY YOU ARE USING ON THE NOAS.IF
 YOU ARE USING MORE THAN ONE ASSEMBLY,
 INDICATE LOCATION. CODE COMPLIANCE FOR
 THE NOAS SUBMITTED HAS NOT BEEN
 DETERMINED PENDING ROOF DESIGN PRESSURES
 AND INDICATION OF APPROVED ASSEMBLY.
  
 7.)IS MECHANICAL FASTENING THROUGH THE
 STRUCTURAL DECK PROPOSED FOR THE REROOF?
 TESTING AND ENGINEERING MAY BE REQUIRED;
 SEE NOAS.
  
 8.)THE REROOF SPECIFICATION SPECIFIES
 ROOFING OVER EXISTING TEMPORARY
 MEMBRANES.THE NOAS SUBMITTED ARE FOR
 REROOFS.A SEPARATE NOA IS REQUIRED FOR
 RECOVER.IF THE METHOD OF INSTALLATION
 CONFLICTS WITH THE MANUFACTURER?S
 SPECIFICATIONS, A LOCAL PRODUCT APPROVAL
 WILL BE REQUIRED FAC9B-72.
  
 9.)VARIOUS SHEETS, ?NEW PEEL & STICK
 LAYER?, LOUVERS, AND STANDING SEAM METAL
 SPECIFIED.PROVIDE PRODUCT APPROVALS,
 FAC9B72.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-12-31 Cont ID  
Sent By dpalmer Date 2005-12-31 Time 18:57 Rev Time 0.00
Received By dpalmer Date 2005-12-31 Time 18:37 Sent To I
Notes
2005-12-31 00:00:00IN ELEC FOR REVIEW, FROM INCOMING.
 **** NOTES****
  
 STAMPED LIGHTNING PROTECTION SYSTEM,
 SUBMITTED FOR BONDED LIGHTNING.
 NO OTHER ELECTRICAL PLANS SUBMITTED FOR
 REVIEW.
 ANY DISCONNECTING FOR RE-ROOF AND
 RE-CONNECTS TO BE FEILD VERIFIED FOR ALL
 ELECTRICAL ON ROOF TO BE BROUGHT UP TO
 CURRENT CODE FOR SIZE, STRAPPING,
 SUPPORT STEC.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-06-30 Cont ID  
Sent By dpalmer Date 2005-06-30 Time 17:04 Rev Time 1.00
Received By dpalmer Date 2005-06-30 Time 12:05 Sent To  
Notes
2005-06-30 00:00:00******** UNSAT *******
  
 1)NOTE: PLEASE SEE ELECTRICAL PLANS FOR
 LIGHTNING PROTECTION SYSTEM MUST CONTAIN
 THE PRINTED NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR PLANS AND DESIGN.
 FBC 104.2.1
  
 2)NOTE: PLEASE SEE MISSING CERTIFICATE
 OF AUTHORIZATION # ON TITLE BLOCKS OF
 PLANS.
 PLEASE SEE FAC 61G1-16.004 AND FS
 481.219. THIS WAS REQUESTED ON PREVIOUS
 REVIEW AND IS REQUIRED PER ABOVE.
 THIS IS REQUIRED ON ALL SHEETS AND FOR
 ALL TRADES WHEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S). THIS MAY BE
 PRINTED, STAMPED ETC ON EXISTING SHEETS.
  
 3)NOTE: PLEASE SEE SHEETS WHICH NOTE
 EXISTING ELECTRICAL TO REMAIN WHICH IS
 SHOWN ON PICS TOBE VIOLATIONS OF NEC
 WILL BE REQUIRED TO BROUGHT UP TO CODE.
 THIS WILL BE A FIELD VERIFICATION AND IS
 ONLY NOTED FOR INFORMATION.
 PLANS WILL BE REDLINED AND NOTED FOR
 THIS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-04-25 Cont ID  
Sent By dpalmer Date 2005-04-25 Time 19:28 Rev Time 0.30
Received By dpalmer Date 2005-04-25 Time 19:24 Sent To  
Notes
2005-04-25 00:00:00******* UNSAT **********
  
 1)NOTE: PLEASE SEE NOE ELECTRICAL PLANS
 FOR PROPOSED WORK WAS SUBMITTED, HOWEVER
 AND ELECTRICAL PERMIT IS BEING
 REQUESTED.
 PLEASE SUBMIT ELECTRICAL DETAILS FOR
 ELECTRICAL WORK BEING APPLIED FOR.
 PLEASE SUBMIT SIGNED, SEALED PLANS BY A
 FL REG PE. FS 471.003.
 215.5
  
 2)NOTE: PLEASE SEE FS 481.229 WHICH
 REQUIRES PLANS TO BE SIGNED, DATED AND
 SEALED FOR WORK OVER $25K FOR COMMERCIAL
 BLDG.
 PLEASE ALSO SEE PLANS WHICH CONTAIN A
 TITLE BLOCK FOR AN ARCHITECTUAL FIRM ARE
 REQUIRED TO BE SIGNED, DATED AND SEALED
 BY SAID FIRM.
 TITLE BLOCK SHALL CONTAIN ALL
 INFORMATION AS SET-FORTH IN FAC
 61G1-16.004 , FS 481.219, 481.221
 PLEASE ALSO SEE ANY SHEETS BEING SIGNED
 AND SEALED, MUST CONTAIN A TITLE BLOCK
 AS STATED ABOVE.
  
 3)NOTE: IF LIGHTNING PROTECTION SYSTEM
 IS GOING TO BE INSTALLED AND UNDER THE
 RESPONSIBLITY AND PERMIT OF ELECTRICAL
 CONTRACTOR SIGNED ON APPLICATION, THEN
 COMPLETE PLANS FOR INSTALLATIOON SHOWING
 ALL DETAILS AND INSTALLATION OF SYSTEM
 PER NFPA-780 SHALL BE SUBMITTED.
 IF LIGHTING PROTECTION SYSTEM WILL BE A
 SEPARATE PERMIT/PLANS, PLEASE REMOVE
 FROM APPLICATION AND FROM PROPOSED WORK
 ON DRAWINGS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-01-04 Cont ID  
Sent By mwennerg Date 2006-01-04 Time 09:16 Rev Time 0.00
Received By mwennerg Date 2006-01-04 Time 09:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-07-15 Cont ID  
Sent By mwennerg Date 2005-07-15 Time 15:31 Rev Time 0.00
Received By mwennerg Date 2005-07-15 Time 15:31 Sent To  
Notes
2005-07-15 00:00:00******DENIED******
  
 1) PLEASE SEE OTHER REVIEW COMMENTS IN
 REGARDS TO FBC, FS AND FAC REQUIREMENTS
 AND MAKE CORRECTIONS.
  
 2) WILL THIS WORK IMPACT EXISTING LIFE
 SAFETY EQUIPMENT? THIS COMMENT WAS NOT
 ADDRESSED FROM LAST REVIEW.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 805-6722 OR 835-2951

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-05-12 Cont ID  
Sent By mwennerg Date 2005-05-12 Time 14:26 Rev Time 0.00
Received By mwennerg Date 2005-05-12 Time 14:26 Sent To  
Notes
2005-05-12 00:00:001) PLEASE REFER TO OTHER COMMENTS IN
 REGARDS TO REQUIREMENTS FOR COMMERCIAL
 BUILDINGS.
  
 2) PLEASE SUBMIT ADDITIONAL INFORMATION
 AND DETAILS REGARDING THE NEW LIGHTNING
 PROTECTION SYSTEM.
  
 3) WILL THIS WORK IMPACT ANY EXISTING
 LIFE SAFETY EQUIPMENT ON OR NEAR THE
 ROOF?
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910 OR 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-06-15 Cont ID  
Sent By adarroug Date 2006-06-15 Time 09:59 Rev Time 0.00
Received By adarroug Date 2006-06-15 Time 09:59 Sent To P
Notes
2006-06-15 00:00:00TO "PSHCMITZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-05-26 Cont ID  
Sent By adarroug Date 2006-05-26 Time 14:22 Rev Time 0.00
Received By adarroug Date 2006-05-26 Time 14:22 Sent To P
Notes
2006-05-26 00:00:00TO "MPERSON" DESK/REV-PER "RBROWN"

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-04-18 Cont ID  
Sent By adarroug Date 2006-04-18 Time 09:37 Rev Time 0.00
Received By adarroug Date 2006-04-18 Time 09:37 Sent To B
Notes
2006-04-18 00:00:00TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-01-13 Cont ID  
Sent By adarroug Date 2006-01-13 Time 08:59 Rev Time 0.00
Received By adarroug Date 2006-01-13 Time 08:59 Sent To B
Notes
2006-01-13 00:00:00TO "SHILL" DESK/RESUB-NEW SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-12-05 Cont ID  
Sent By adarroug Date 2005-12-05 Time 16:42 Rev Time 0.00
Received By adarroug Date 2005-12-05 Time 16:42 Sent To  
Notes
2006-01-03 00:00:00TO "COMM" BD#42
2005-12-05 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-20 Cont ID  
Sent By shill Date 2005-06-20 Time 13:17 Rev Time 0.00
Received By shill Date 2005-06-20 Time 13:17 Sent To  
Notes
2005-06-22 00:00:00TO "COMM" BD#44
2005-06-20 00:00:00WAITING FOR COMM BOARD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-04-18 Cont ID  
Sent By adarroug Date 2005-04-18 Time 10:32 Rev Time 0.00
Received By adarroug Date 2005-04-18 Time 10:32 Sent To  
Notes
2005-04-18 00:00:00TO "COMM" BD#64

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-01-09 Cont ID  
Sent By pkrauss Date 2006-01-09 Time 07:49 Rev Time 0.00
Received By pkrauss Date 2006-01-09 Time 06:51 Sent To  
Notes
2006-01-09 00:00:00PROVISO:
  
 SMOKE EVAC TEST REQUIRED AT FINAL
 INPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-07-19 Cont ID  
Sent By hmoser Date 2005-07-19 Time 11:20 Rev Time 0.00
Received By hmoser Date 2005-07-19 Time 11:19 Sent To  
Notes
2005-07-19 00:00:00PLAN DENIED
 COMMENTS WERE NOT ANCERED FROM LAST
 REVIEWS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-05-20 Cont ID  
Sent By pkrauss Date 2005-05-20 Time 07:15 Rev Time 0.55
Received By pkrauss Date 2005-05-20 Time 07:15 Sent To  
Notes
2005-05-20 00:00:00DENIED:
 1.PLANS ARE TO BE SIGNED, SEALED AND
 DATED IS ACCORDANCE WITH FS471.025 FAC
 61G15-23.002 (2).
  
 2.INDICATE IF THE EXISTING CURBS ARE
 TO BE REPLACED OR RE-USED.PROVIDE
 DETAILS FOR ANY NEW INSTALLATIONS.
  
 3.PROVIDE A SCHEDULE OF EQUIPMENT THAT
 WILL BE REMOVED FOR RE-ROOFING PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-06-16 Cont ID  
Sent By pschmitz Date 2006-06-16 Time 15:22 Rev Time 0.00
Received By pschmitz Date 2006-06-16 Time 15:22 Sent To PC
Notes
2006-06-16 00:00:00THIS PLUMBING PLAN REVIEW DELETED TRENCH
 DRAIN, ONLY.

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-06-14 Cont ID  
Sent By pschmitz Date 2006-06-14 Time 09:13 Rev Time 0.00
Received By pschmitz Date 2006-06-14 Time 09:13 Sent To PC
Notes
2006-06-14 00:00:00RETURN TO CONTRACTOR PER CRAIG MONOHAN
 FOR THE MOOST CURRENT REVISION 5-31-06
 DELETING TRENCH DRAINS.
 QUESTIONS 561-805-6692PES

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-06-09 Cont ID  
Sent By mperson Date 2006-06-09 Time 13:09 Rev Time 1.25
Received By mperson Date 2006-06-09 Time 13:09 Sent To B
Notes
2006-06-09 00:00:00REVISION: ADD TRENCH DRAIN TO TIE INTO
 EXISTING STORM SYSTEM, AND WORK ON
 CONDENSATE
  
 NOTE: SEPERATE PLUMBING PERMIT REQUIRED
 REFERENCE PERMIT #05040736 AND SHEETS
 SKH-22A THROUGH SKH-22E ON PLUMBING
 PERMIT APPLICATION.