| 2005-05-02 00:00:00 | BUILDING PLAN REVIEW: PROVISO |
| | |
| | 1. SLAB AREA MUST HAVE TERMITE TREATMENT |
| | PRIOR TO POUR. SEE CODE BELOW: |
| | |
| | FBC104.2.6 CERTIFICATE OF PROTECTIVE |
| | TREATMENT FOR PREVENTION OF |
| | TERMITES. A WEATHER RESISTANT JOBSITE |
| | POSTING BOARD SHALL BE PROVIDED TO |
| | RECEIVE DUPLICATE TREATMENT |
| | CERTIFICATES AS EACH REQUIRED PROTECTIVE |
| | TREATMENT IS COMPLETED, PROVIDING A COPY |
| | FOR THE PERSON THE PERMIT IS |
| | ISSUED TO AND ANOTHER COPY FOR THE |
| | BUILDING PERMIT FILES.THE TREATMENT |
| | CERTIFICATE SHALL PROVIDE THE PRODUCT |
| | USED, IDENTITY OF THE APPLICATOR, |
| | TIME AND DATE OF THE TREATMENT, SITE |
| | LOCATION, AREA TREATED, CHEMICAL |
| | USED, PERCENT CONCENTRATION AND NUMBER |
| | OF GALLONS USED, TO ESTABLISH A |
| | VERIFIABLE RECORD OF PROTECTIVE |
| | TREATMENT.IF THE SOIL CHEMICAL BARRIER |
| | METHOD FOR TERMITE PREVENTION IS USED, |
| | FINAL EXTERIOR TREATMENT SHALL BE |
| | COMPLETED PRIOR TO FINAL BUILDING |
| | APPROVAL. |
| | |
| | 2. SLAB CODE REQUIREMENTS: |
| | |
| | FBC1909.1 MINIMUM THICKNESS. THE MINIMUM |
| | THICKNESS OF CONCRETE FLOOR SLABS |
| | SUPPORTED DIRECTLY ON THE GROUND SHALL |
| | BE NOT LESS THAN 3-1/2 INCHES (89 |
| | MM) UNLESS DESIGNED BY AN ARCHITECT OR |
| | ENGINEER. |
| | |
| | FBC1909.2 VAPOR RETARDER. A VAPOR |
| | RETARDER CONSISTING OF 6 MIL (0.152 MM) |
| | MINIMUM POLYETHYLENE WITH JOINTS LAPPED |
| | 6 INCHES (152 MM) AND SEALED, OR |
| | OTHER APPROVED MATERIALS HAVING A |
| | MAXIMUM PERM RATING OF 0.5 [2.873 X |
| | 10^-5MG/(PA ? S ? M^2)] SHALL BE |
| | INSTALLED UNDERNEATH THE SLAB. |
| | |
| | |
| | 3. FL BLDG 1909.3 (EXEPTION# 2) |
| | CONCRETE SLABS ON GRADE CONTAINING 6X6/ |
| | W1.4XW1.4 WELDED WIRE REINFORCEMENT |
| | FABRIC LOCATED IN THE MIDDLE TO THE |
| | UPPER 1/3RD OF THE SLAB SHALL BE SUP- |
| | PORTED BY APPROVED MATERIALS OR SUPPORTS |
| | AT SPACING NOT TO EXCEED 3 FT OR IN |
| | ACCORDANCE WITH MANUFACTURER'S SPEC. |
| | |
| | 4. FOOTER SHALL BE 18" X 12" WITH 3 #5 |
| | REBAR. |
| | |