Plan Review Details - Permit 05040706
Plan Review Stops For Permit 05040706
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-07-21 Cont ID  
Sent By mjacobs Date 2005-07-21 Time 18:16 Rev Time 0.75
Received By mjacobs Date 2005-07-21 Time 17:55 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-07-18 Cont ID  
Sent By mjacobs Date 2005-07-18 Time 09:41 Rev Time 2.00
Received By mjacobs Date 2005-07-18 Time 06:43 Sent To PC
Notes
2005-07-18 00:00:00BUILDING PLAN REVIEW
 PERMIT:05040706
 ADD:7102 EAGLE TERRACE
 CONT:CRIBB CONSTRUCTION
 TEL: (561)689-6900
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW:3RD
 ACTION:DENIED
  
 1) B/RM #3 ON SHEET A-2. DOES NOT MEET
 THE MINIMUM REQUIREMENTS. EVERY
 HABITABLE ROOM SHALL HAVE ONE OR MORE
 WINDOWS, TO AFFORD ADQUATE LIGHT AND
 VENTILATION.FBC. SEC 1203.1.
 SHOW HOW THIS WILL BE ACHIVED.
  
 2) SUBMIT PRODUCT APPROVALS FOR THE
 ROOFING PRODUCTS TO BE USED ON THE ROOF.
 PLEASE INDICATE WHICH WINDOW WILL BE
 USED.
  
 3)THE ENERGY EFFICIENTY FORM INDICATES
 USING R-5.0 INSULATION ON THE MASONARY
 WALL, HOWEVER THE PLANS SHOWS R-4.2.
 CLARIFY WHICH ONE WILL BE USED.
  
 BUILDING PLAN REVIEW
 MYRON JACOBS
 TEL: (561)805-6726
 FAX: (561)659-8026
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-06-20 Cont ID  
Sent By mjacobs Date 2005-06-20 Time 14:04 Rev Time 1.25
Received By mjacobs Date 2005-06-20 Time 14:01 Sent To PC
Notes
2005-06-20 00:00:00BUILDING PLAN REVIEW
 PERMIT:05040706
 ADD:7102 EAGLE TERRACE
 CONT:CRIBB CINSTRUCTION
 TEL: (561)689-6900
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW:2ND
 ACTION:DENIED
  
 1) 713.13 F.S.A NOTICE OFCOMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.NOTE: THE NOTICE OF COMMENCEMENT
 MUST BERE-RECORDED IF THE DESCRIBED
 IMPROVEMENTOR CONSTRUCTION IS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING.
  
 2) IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 3) FBC 13-103.1.2BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHITECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 4)PROVIDE EMERGENCY EGRESS WINDOW IN
 SLEEPING ROOMS WITH A MINIMUM NET CLEAR
 OPENING HEIGHT OF 24INCHES,NET CLEAR
 OPENING WIDTH OF 20 INCHES AND NET CLEAR
 OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR
 OPENINGS ARE PERMITTED TO HAVE A NET
 CLEAR OPENING OF 5.0 SQ.FT. SILL HEIGHT
 SHALL NOT BE MORE THAN 44 INCHES ABOVE
 THE FLOOR. 1997 SBC 1005.4
 B/RM #3 SHEET A-2.
  
 5) PROVIDE PRODUCT APPROVALS FOR DOORS/
 ROOFING MATERIALS/WINDOWS ETC.
 PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6) INDICATE IF DOORS AND WINDOWS WILL BE
 IMPACT OR IF STORM SHUTTERS WILL BE
 USED. SUBMIT PRODUCT APPROVALS FOR
 EITHER METHOD WHICH WILL BE USED.
  
 7)BASE ON THE SBCCI BUILDING VALUATION
 DATA THE PROJECT VALUE HAS BEEN CHANGED
 TO $32,631.
 420 SQ.FT. X 76.96 =$32,323.
 ADDITIONAL PERMIT FEES ARE DUE $414.72
 BEFORE PERMIT ISSUED.
  
 BUILDING PLAN REVIEW
 MYRON JACOBS
 TEL: (561)805-6726
 FAX: (561)659-8026
 [email protected]
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-16 Cont ID  
Sent By mjacobs Date 2005-05-16 Time 08:50 Rev Time 2.25
Received By mjacobs Date 2005-05-13 Time 17:06 Sent To PC
Notes
2005-05-13 00:00:00BUILDING PLAN REVIEW
 PERMIT:05040706
 ADD:7102 EAGLE TERRACE
 CONT:CRIBB CINSTRUCTION
 TEL: (561)689-6900
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW:1ST
 ACTION:DENIED
  
 1) 713.13 F.S.A NOTICE OFCOMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.NOTE: THE NOTICE OF COMMENCEMENT
 MUST BERE-RECORDED IF THE DESCRIBED
 IMPROVEMENTOR CONSTRUCTION IS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING.
  
 2) IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 3) FBC 13-103.1.2BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHITECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 4)PROVIDE EMERGENCY EGRESS WINDOW IN
 SLEEPING ROOMS WITH A MINIMUM NET CLEAR
 OPENING HEIGHT OF 24INCHES,NET CLEAR
 OPENING WIDTH OF 20 INCHES AND NET CLEAR
 OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR
 OPENINGS ARE PERMITTED TO HAVE A NET
 CLEAR OPENING OF 5.0 SQ.FT. SILL HEIGHT
 SHALL NOT BE MORE THAN 44 INCHES ABOVE
 THE FLOOR. 1997 SBC 1005.4
 B/RM #3 SHEET A-2.
  
 5) PLEASE GIVE MORE INFORMATION ON THE
 NUSERY. IS IT FOR KIDS OR PLANTS?
  
 6) PROVIDE PRODUCT APPROVALS FOR DOORS/
 ROOFING MATERIALS/WINDOWS ETC.
 PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 7) INDICATE IF DOORS AND WINDOWS WILL BE
 IMPACT OR IF STORM SHUTTERS WILL BE
 USED. SUBMIT PRODUCT APPROVALS FOR
 EITHER METHOD WHICH WILL BE USED.
  
 8)BASE ON THE SBCCI BUILDING VALUATION
 DATA THE PROJECT VALUE HAS BEEN CHANGED
 TO $32,631.
 420 SQ.FT. X 76.96 =$32,323.
 ADDITIONAL PERMIT FEES ARE DUE $414.72
 BEFORE PERMIT ISSUED.
  
 BUILDING PLAN REVIEW
 MYRON JACOBS
 TEL: (561)805-6726
 FAX: (561)659-8026
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-06-17 Cont ID  
Sent By dpalmer Date 2005-06-17 Time 07:12 Rev Time 0.25
Received By dpalmer Date 2005-06-17 Time 07:12 Sent To B
Notes
2005-06-17 00:00:00REDLINED 410.8

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-04-21 Cont ID  
Sent By dpalmer Date 2005-04-21 Time 17:00 Rev Time 0.25
Received By dpalmer Date 2005-04-21 Time 17:00 Sent To M
Notes
2005-04-21 00:00:00******** UNSAT ********
  
 1)NOTE: PLEASE SHOW RECEPTS SPACED PER
 210.52
  
 2)NOTE: PLEASE SHOW MEANS OF EGRESS
 LIGHTING PER 210.70, LS 101 5-8
  
 3)NOTE: PLEASE SEE 210.12 FOR ARC FAULT
 PROTECTION REQUIRED FOR NEW ELECTRICAL
 WORK.
  
 4)NOTE: PLEASE VERIFY NEW OR EXISTING
 SD'S REQUIRED PER NFPA-72 8-1.4.1.6.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-07-21 Cont ID  
Sent By adarroug Date 2005-07-21 Time 15:35 Rev Time 0.00
Received By adarroug Date 2005-07-21 Time 15:35 Sent To B
Notes
2005-07-21 00:00:00TO "MJACOBS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-07-15 Cont ID  
Sent By adarroug Date 2005-07-15 Time 14:24 Rev Time 0.00
Received By adarroug Date 2005-07-15 Time 14:24 Sent To B
Notes
2005-07-15 00:00:00TO "MJACOBS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-06-15 Cont ID  
Sent By shill Date 2005-06-15 Time 13:33 Rev Time 0.00
Received By shill Date 2005-06-15 Time 13:33 Sent To E
Notes
2005-06-15 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-08 Cont ID  
Sent By shill Date 2005-06-08 Time 09:33 Rev Time 0.00
Received By shill Date 2005-06-08 Time 09:33 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-19 Cont ID  
Sent By adarroug Date 2005-04-19 Time 13:57 Rev Time 0.00
Received By adarroug Date 2005-04-19 Time 13:57 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-16 Cont ID  
Sent By mjacobs Date 2005-05-16 Time 08:51 Rev Time 0.00
Received By mjacobs Date 2005-04-13 Time 09:58 Sent To  
Notes
2005-04-13 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-04-22 Cont ID  
Sent By pkrauss Date 2005-04-22 Time 12:58 Rev Time 0.25
Received By pkrauss Date 2005-04-22 Time 12:55 Sent To P
Notes
2005-04-22 00:00:00NO MECHANICAL PLANS OR CONTRACTOR
 INDICATED WITH BUILDING PERMIT
 APPLICATION.PROVIDE PLANS, EQUIPMENT
 INFORMATION AND A COMPLETED FORM 600C OR
 ENERGY CALCULATIONS WITH MECHANICAL
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-04-25 Cont ID  
Sent By jleech Date 2005-04-25 Time 11:22 Rev Time 0.25
Received By jleech Date 2005-04-25 Time 11:22 Sent To B
Notes
2005-04-25 00:00:00NO PLUMBING IN THIS ADDITION

Review Stop Z ZONING
Rev No 2 Status P Date 2005-06-14 Cont ID  
Sent By mmclean Date 2005-06-14 Time 18:37 Rev Time 0.00
Received By mmclean Date 2005-06-14 Time 18:36 Sent To I
Notes
2005-06-14 00:00:00APPROVING, MEETS ALL THE ZONING
 REQUIREMENT.
  
 PROVISO:** NEED CLARIFICATION ON WHETHER
 THE ADDITION IS AN OFFICE/ROOM ADDITION
 (AS WRITTEN ON APPLICATION OR SITTING
 ROOM/STORAGE (AS DRAWN/WRITTEN ON FLOOR
 PLANS***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-04-18 Cont ID  
Sent By mmclean Date 2005-04-18 Time 16:22 Rev Time 0.00
Received By mmclean Date 2005-04-18 Time 16:22 Sent To I
Notes
2005-04-18 00:00:00DENIED,
 1. MUST SHOW THE SETBACK OF THE NEW
 ADDITION FROM PROPERTY LINE ON SITEPLAN
 (2) COPY.
  
 MICHELLE MCLEAN
 ZONING TECH
 805-6720