Plan Review Details - Permit 05040610
Plan Review Stops For Permit 05040610
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-07-06 Cont ID  
Sent By lsmith Date 2005-07-06 Time 11:30 Rev Time 1.00
Received By lsmith Date 2005-07-06 Time 11:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-06-08 Cont ID  
Sent By lsmith Date 2005-06-08 Time 08:28 Rev Time 0.25
Received By lsmith Date 2005-06-08 Time 08:28 Sent To  
Notes
2005-06-08 00:00:00BUILDING PLAN REVIEW: FAILED
  
 COMMENTS FROM PLUMBING & ELECTRIC HAVE
 NOT BEEN CORRECTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-04-26 Cont ID  
Sent By lsmith Date 2005-04-26 Time 08:36 Rev Time 0.50
Received By lsmith Date 2005-04-26 Time 08:36 Sent To  
Notes
2005-04-26 00:00:00BUILDING PLAN REVIEW: FAILED
  
 SEE NOTES FROM PLUMBING & ELECTRIC.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-07-06 Cont ID  
Sent By jleahy Date 2005-07-06 Time 07:02 Rev Time 0.30
Received By jleahy Date 2005-07-02 Time 07:02 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-06-01 Cont ID  
Sent By jleahy Date 2005-06-01 Time 10:53 Rev Time 0.30
Received By jleahy Date 2005-06-01 Time 10:53 Sent To P
Notes
2005-06-01 00:00:00SAME COMMENTS AS BEFOREJLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-04-16 Cont ID  
Sent By jleahy Date 2005-04-16 Time 21:31 Rev Time 0.30
Received By jleahy Date 2005-04-16 Time 21:30 Sent To M
Notes
2005-04-16 00:00:00NEED BRANCH CIRCUIT NUMBERS
  
 NEED TO SHOW GFI PROTECTION
  
 NEED PANEL SCHEDULE, SIZE OF PANEL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-30 Cont ID  
Sent By adarroug Date 2005-06-30 Time 14:23 Rev Time 0.00
Received By adarroug Date 2005-06-30 Time 14:23 Sent To E
Notes
2005-06-30 00:00:00TO "JLEAHY" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-19 Cont ID  
Sent By adarroug Date 2005-05-19 Time 11:13 Rev Time 0.00
Received By adarroug Date 2005-05-19 Time 11:13 Sent To E
Notes
2005-05-19 00:00:00TO "JLEAHY" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-04-12 Cont ID  
Sent By adarroug Date 2005-04-12 Time 17:22 Rev Time 0.00
Received By adarroug Date 2005-04-12 Time 17:22 Sent To E
Notes
2005-04-12 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-04-22 Cont ID  
Sent By pkrauss Date 2005-04-22 Time 11:08 Rev Time 0.20
Received By pkrauss Date 2005-04-22 Time 11:06 Sent To B
Notes
2005-04-22 00:00:00NO MECHANICAL WORK OR CONTRACTOR
 INDICATED WITH BUILDING PERMIT
 APPLICATION.PLEASE PROVIDE PLANS &
 EQUIPMENT SCHEDULE WITH MECHANICAL
 PERMIT APPLICATION SHOULD ANY MECHANICAL
 WORK BE REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-07-01 Cont ID  
Sent By jleech Date 2005-07-01 Time 14:01 Rev Time 0.50
Received By jleech Date 2005-07-01 Time 14:01 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-06-07 Cont ID  
Sent By jleech Date 2005-06-07 Time 19:10 Rev Time 0.75
Received By jleech Date 2005-06-07 Time 19:10 Sent To B
Notes
2005-06-07 00:00:00DENIED;
 1.NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR DESIGH. 2ND REQUEST
 2.A SEPAATE GAS PERMIT IS REQUIRED. 2ND
 REQUEST.
 3.SHOW REGULATORST TYPELOCATION AND
 SHOW SHUT OFF VALVES UP STREAM OF
 REGULATORS.
 4.POOL HEATER WOULD BE THE LONGEST RUN.
 PERMIT 05010301 GAS PERMIT FOR POOL
 HEATER IS 120' THAT WOULD BE YOUR
 LONGEST RUN.
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-04-21 Cont ID  
Sent By kstevens Date 2005-04-21 Time 13:39 Rev Time 0.50
Received By kstevens Date 2005-04-21 Time 13:39 Sent To M
Notes
2005-04-21 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FBC-2001 FUEL GAS
  
 1) ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 SECTION 104.2.1.
 2) A SEPARATE GAS PERMIT IS REQUIRED.
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR A GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2005-07-06 Cont ID  
Sent By lsmith Date 2005-07-06 Time 11:30 Rev Time 0.00
Received By lsmith Date 2005-07-06 Time 11:30 Sent To  
Notes
2005-07-06 00:00:00ALL INTERIOR WORK NO ZONING REVIEW
 REQUIRED LS