Plan Review Details - Permit 05040601
Plan Review Stops For Permit 05040601
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-11 Cont ID  
Sent By shill Date 2005-05-11 Time 09:31 Rev Time 1.00
Received By shill Date 2005-05-11 Time 09:31 Sent To  
Notes
2005-05-11 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)NO PLANS WERE SUBMITTED FOR THE
 BATHROOM.PLEASE SUBMIT.
  
 2.)PROVIDE PROOF OF CHANGE OF
 OCCUPANCY FROM R3 TO B; EGRESS,
 ACCESSIBILITY, FLOOR LOADING; FBC
 3401.2.2.
  
 3.) PROVIDE IMPACT FEE RECEIPT (CHANGE
 OF USE); 233-5025 (PALM BEACH COUNTY)
 FOR MORE INFORMATION.
  
 4.) PROVIDE FLOOR PLAN SHOWING WINDOWS
 AND SIZES TO BE INSTALLED.ARE ANY
 DOUBLE WINDOWS REQUIRING MULLIONS?
 MULLION PRODUCT APPROVAL REQUIRED.

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2005-04-20 Cont ID  
Sent By dpalmer Date 2005-04-20 Time 18:47 Rev Time 0.10
Received By dpalmer Date 2005-04-20 Time 18:47 Sent To  
Notes
2005-04-20 00:00:00NO ELECTRICAL PLANS SUBMITTED, NO
 ELECTRICAL MENTIONED IN SCOPE OF WORK
 AND NO ELECTRICAL PERMIT APPLIED FOR.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2005-05-05 Cont ID  
Sent By mwennerg Date 2005-05-05 Time 14:45 Rev Time 0.00
Received By mwennerg Date 2005-05-05 Time 14:45 Sent To  
Notes
2005-05-05 00:00:001) NO LIFE SAFETY PLANS SUBMITTED. IT
 DOESN'T APPEAR THAT THE SCOPE OF THIS
 WORK INVOLVES ANY LIFE SAFETY EQUIPMENT.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2005-04-11 Cont ID  
Sent By ptjomsto Date 2005-04-11 Time 13:59 Rev Time 0.00
Received By ptjomsto Date 2005-04-11 Time 13:59 Sent To  
Notes
2005-04-11 00:00:00HISTORIC APPROVED 4/11/05 BY E BOWERS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-08 Cont ID  
Sent By pkrauss Date 2005-06-08 Time 10:14 Rev Time 0.00
Received By pkrauss Date 2005-04-13 Time 11:07 Sent To  
Notes
2005-04-13 00:00:00TO "COMM" BD#47

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-06-08 Cont ID  
Sent By pkrauss Date 2005-06-08 Time 10:01 Rev Time 0.25
Received By pkrauss Date 2005-06-08 Time 10:00 Sent To  
Notes
2005-06-08 00:00:00NO MECHANICAL WORK OR CONTRACTOR
 INDICATED WITH PERMIT APPLICATION.
 PLEASE PROVIDE MECHANICAL
 INFORMATION/PLAN WITH MECHANICAL PERMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-05-26 Cont ID  
Sent By kstevens Date 2005-05-26 Time 17:31 Rev Time 1.00
Received By kstevens Date 2005-05-26 Time 17:31 Sent To M
Notes
2005-05-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
  
 1) THERE SEEMS TO BE A CHANGE OF
 OCCUPANCY FROM RESIDENTIAL TO
 COMMERCIAL. IF THIS IS THE CASE, THE
 FOLLOWING WILL BE REQUIRED.
 A. SUBMIT A FLOOR PLAN SHOWING ALL
 EXISTING FIXTURES. SECTION 104.2.1.
 B. PLEASE INDICATE THE OCCUPANCY OF THE
 BUILDING. WHAT TYPE OF BUSINESS WILL BE
 IN THE BUILDING.
 C. FOR BUSINESS OCCUPANCY A DRINKING
 FOUNTAIN IS REQUIRED. TABLE 403.1 -
 SUBMIT A DETAIL SHOW COMPLIANCE WITH
 SECTIONS 11-4.15 & ALL SUBSECTIONS AS
 WELL AS 11-4.1.3(10)(A) PROVISIONS FOR
 THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
 D. SUBMIT A DETAIL FOR TOILET/BATHROOM
 SHOWING COMPLIANCE WITH THE FOLLOWING
 SECTIONS. 11-4.16, 11-4.19, AND IF
 FIXTURES ARE PROVIDED 11-4.20 AND/OR
 11-4.21 AND 11-4.22 WITH ALL
 SUBSECTIONS.
 E. IF A KITCHEN/BREAKROOM SINK IS
 PROVIDED, SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS.
 D. AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THE BUILDING.
  
 INFORMATIONAL - ALL TRADES AND BUILDING
 SHALL BE BROUGHT UP TO CODE IF THERE IS
 A CHANGE OF OCCUPANCY. SEE SECTION 34 OF
 THE BUILDING CODE. MORE COMMENTS MAY BE
 FORTHCOMING WHEN PLANS ARE SUBMITTED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***