Plan Review Details - Permit 05040584
Plan Review Stops For Permit 05040584
Review Stop G GAS REVIEW
Rev No 1 Status P Date 2005-04-21 Cont ID  
Sent By kstevens Date 2005-04-21 Time 08:32 Rev Time 0.50
Received By kstevens Date 2005-04-21 Time 08:32 Sent To  
Notes
2005-04-21 00:00:00 
  
 PER N. MELICK MANUFACTURE INFO
 NOT REQUIRED FOR 1 & 2 FAMILY HOMES.
 JULY 17, 2002 OFFICAL INTERPRETATION.
 THE FIELD INSPECTOR SHALL VERIFY THE
 INSTALLED EQUIPMENT INPUT DOES NOT EX-
 CEED THE PIPE SIZING.
  
 IF DRYER ROOM IS A CONFINED SPACE,
 OPENINGS REQUIRED PER SECTION 304.3.1 0R
 SECTION 304.3.2 SHALL BE INSTALLED.
 MINIMUM 1,000 CUBIC FEET REQUIRED. -
 MINIMUM 2,000 CUBIC FEET FOR WATER
 HEATER REQUIRED.
  
  
  
  
  
  
  
  
  
  
 .

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-04-12 Cont ID  
Sent By adarroug Date 2005-04-12 Time 08:37 Rev Time 0.00
Received By adarroug Date 2005-04-12 Time 08:37 Sent To G
Notes
2005-04-12 00:00:00TO "G" BOX