Plan Review Details - Permit 05040559
Plan Review Stops For Permit 05040559
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-04-25 Cont ID  
Sent By mwennerg Date 2005-04-25 Time 15:59 Rev Time 0.00
Received By mwennerg Date 2005-04-25 Time 15:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-04-13 Cont ID  
Sent By mwennerg Date 2005-04-13 Time 11:16 Rev Time 0.00
Received By mwennerg Date 2005-04-13 Time 11:16 Sent To  
Notes
2005-04-13 00:00:001) FIRE ALARM SYSTEM IS TO BE MONITORED
 BY A UL LISTED CENTRAL STATION SERVICE.
  
 2) PLEASE PROVIDE PRODUCT APPROVAL
 INFORMATION SHEETS ON ALL FIRE ALARM
 EQUIPMENT.
  
 3) FIRE ALARM SYSTEM SHALL BE CLASS A OR
 FULLY ADDRESSABLE.
  
 4) DUCT SMOKE DETECTORS SHALL BE WIRED
 INTO FIRE ALARM SYSTEM SO AS TO CAUSE A
 GENERAL FIRE ALARM WHEN ACTIVATED.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910 OR 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-22 Cont ID  
Sent By adarroug Date 2005-04-22 Time 13:28 Rev Time 0.00
Received By adarroug Date 2005-04-22 Time 13:28 Sent To FIRE
Notes
2005-04-22 00:00:00TO "F" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-04-11 Cont ID  
Sent By adarroug Date 2005-04-11 Time 08:13 Rev Time 0.00
Received By adarroug Date 2005-04-11 Time 08:13 Sent To FIRE
Notes
2005-04-11 00:00:00TO "F" BOX