| 2005-04-20 00:00:00 | ******** UNSAT *********** |
| | |
| | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS FOR NEW AND CORRELATE WITH |
| | SUBMITTED PANEL SCHEDULE. |
| | PLEASE INCLUDE ALL CONDUCTOR SIZES FOR |
| | BRANCH CIRCUITS. |
| | 215.5,310.16,240.4 |
| | |
| | 2)NOTE: PLEASE SEE 424.3B FOR MIN OCP FO |
| | AHU/RTU 125%. |
| | |
| | 3)NOTE: PLEASE SEE RISER DIAGRAM |
| | ATTACHED TO PLANS SEEM TO INDICATE AN |
| | ENTIRE NEW SERVICE? |
| | IF SO, PLEASE INCLUDE ALL INFORMATION |
| | FOR A NEW INSTALLATION. IF EXISTING, |
| | PLEASE INDICATE. |
| | 215.5 |
| | PLEASE SEE SEC'S SHOWN DO NOT MEET 240.3 |
| | PLEASE SEE MIN SIZING OF SEC'S FOR |
| | DEVICES RATED OVER 800A'S TO MEET OR |
| | EXCEED OCP/DEVICE. |
| | GROUNDING ELECTRODE SYSTEM ? 250.50 |
| | AIC RATINGS FOR ALL. 110.9 |
| | |
| | 4)NOTE: PLEASE SEE FBC 104.2.1 |
| | ALL PLANS/DRAWING ARE REQUIRED TO HAVE |
| | THE PRINTED NAME AND SIGNATURE OF PERSON |
| | RESPONSIBLE FOR PLANS. |
| | |
| | 5)NOTE: PLEASE SEE FAC 61G1-16.004 AND |
| | FS 481.219 FOR ARCHITECTUAL FIRM AND |
| | MISSING INFORMATION REQUIRED ON TITLE |
| | BLOCKS. |
| | THIS IS REQUIRED ON ALL SHEETS AND FOR |
| | ALL TRADES WHEATHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | 6)NOTE: PLEASE SEE ALL CONTINUOUS LOADS |
| | ARE TO BE SHOWN AT 125%. |
| | LIGHTING/LARGEST MOTOR. |
| | 215.3,230.42 ETC. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF OLD SHOULD BE SUBMITTED FOR |
| | REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |