Plan Review Details - Permit 05040447
Plan Review Stops For Permit 05040447
Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2007-04-04 Cont ID  
Sent By rmcdouga Date 2007-04-04 Time 18:03 Rev Time 0.00
Received By rmcdouga Date 2007-04-04 Time 17:22 Sent To  
Notes
2007-04-04 18:04:27PROCESSED REVISIONS TO PLANS

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2007-04-02 Cont ID  
Sent By rmcdouga Date 2007-04-02 Time 12:55 Rev Time 0.00
Received By rmcdouga Date 2007-04-02 Time 12:26 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2007-03-26 Cont ID  
Sent By rmcdouga Date 2007-03-26 Time 19:02 Rev Time 0.00
Received By rmcdouga Date 2007-03-26 Time 19:01 Sent To  
Notes
2007-03-27 07:59:44REVISION IS DENIED BY BUILDING
  
 1) BOTH SETS OF PLANS SUBMITTED FOR REVISION ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE DESIGNER OF
 RECORD WHOSE NAME APPEARS IN THE TITLE BLOCK. SEE FS,
 481 AND FBC 106.1 AS AMENDED BY THE CITY OF WPB.
  
 2) CLARIFY THE DESCRIPTION OF WORK. THE PLANS INDICATE
 A PORCH/BALCONY ADDITION AND OTHER EXTERIOR WORK. THE
 ORIGINAL PERMIT APPLICATION WORK DESCRIPTION INDICATES
 THAT NO EXTERIOR WORK IS TO BE DONE AT THIS TIME.
 PLEASE CLARIFY. IF THIS WORK IS TO BE DONE, PROVIDE A
 LETTER FROM THE CONTRACTOR AND SPECIFY IT ON THE
 REVISION FORM.
  
 3) IF THE REVISED SCOPE OF WORK WILL INCREASE THE TOTAL
 VALUE OF THE WORK SPECIFIED ON THE PLANS TO MORE THAN
 $40,000.00, INDICATE THE TOTAL AMOUNT ON THE SUBMITTAL
 FORMAND INFORM THE INTAKE CLERK TO GENERATE A RECEIPT
 SO THAT ANY ADDITIONAL PERMIT FEES CAN BE PAID.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status N Date 2006-12-18 Cont ID  
Sent By rmcdouga Date 2006-12-18 Time 10:31 Rev Time 0.00
Received By rmcdouga Date 2006-12-18 Time 10:31 Sent To  
Notes
2006-12-18 11:11:03RESTAMP DENIED
  
 1) A LETTER FORM THE OWNER TERMINATING THE CONTRACTOR
 (BLAKEMAN CONSTRUCTION) WAS INCLUDED WITH THE PLANS
 SUBMITTED FOR RESTAMP. THE PERMIT AND PLANS ON FILE
 WITH THE CITY BELONG TO THE ORIGINAL CONTRACTOR AND CAN
 NOT BE TRANSFERED TO ANOTHER CONTRACTOR WITHOUT HIS
 WRITTEN PERMISSION. THE RESTAMP REQUEST FOR THIS PERMIT
 IS REQUIRED TO MADE BY THE CONTRACTOR OF RECORD.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-05-02 Cont ID  
Sent By alange Date 2006-05-02 Time 08:17 Rev Time 0.50
Received By alange Date 2006-05-02 Time 08:17 Sent To  
Notes
2006-05-02 00:00:00REV OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-04-13 Cont ID  
Sent By alange Date 2006-04-13 Time 09:56 Rev Time 0.75
Received By alange Date 2006-04-13 Time 09:56 Sent To  
Notes
2006-04-13 00:00:00DENIED
  
 SUBMIT TWO ORIGONAL SIGNED AND SEALED
 SETS OF PLANS.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-04-13 Cont ID  
Sent By alange Date 2006-04-13 Time 09:55 Rev Time 0.75
Received By alange Date 2006-04-13 Time 09:55 Sent To  
Notes
2006-04-13 00:00:00SRUCTURAL REVISION OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-06-01 Cont ID  
Sent By alange Date 2005-06-01 Time 11:08 Rev Time 1.00
Received By alange Date 2005-06-01 Time 10:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-03 Cont ID  
Sent By alange Date 2005-05-03 Time 11:17 Rev Time 1.00
Received By alange Date 2005-05-03 Time 10:34 Sent To Z
Notes
2005-05-03 00:00:00DENIED
  
 1.ARCHITECTS SEAL AND SIGNATURE
 MISSING FROMA-1.
  
 2. SP DATA. NOTE BUILDING IS IN FLOOD
 ZONE "A" NOT B.
  
 3.PLEASE SUBMIT 2 COPIES OF A SOILS
 REPORT.
  
 4. PLEASE SUBMIT 2 COPIES OF PRODUCT
 APPROVALS FOR FRENCH DOORS AND STRAPS
 AND TIE-DOWNS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-03-13 Cont ID  
Sent By btrobaug Date 2007-03-13 Time 15:14 Rev Time 0.50
Received By btrobaug Date 2007-03-13 Time 14:00 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status N Date 2006-05-01 Cont ID  
Sent By btrobaug Date 2006-05-01 Time 09:48 Rev Time 0.25
Received By btrobaug Date 2006-05-01 Time 09:47 Sent To B
Notes
2006-05-01 00:00:00 
 NO ELECTRICAL PLANS SUBMITTED WITH THIS
 REVISION.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-03-13 Cont ID  
Sent By btrobaug Date 2006-04-17 Time 13:46 Rev Time 0.50
Received By btrobaug Date 2006-04-17 Time 13:06 Sent To PC
Notes
2006-04-17 00:00:00 

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-04-12 Cont ID  
Sent By btrobaug Date 2006-04-12 Time 12:22 Rev Time 1.00
Received By btrobaug Date 2006-04-11 Time 18:14 Sent To B
Notes
2006-04-12 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE TOTAL COMPUTED LOADS ON THE LOAD
 SUMMARY OF 178+92 EXCEED THE EXISTING
 SERVICE SIZE.
  
 2} 210.8(A)(6) KITCHENS -WHERE THE
 RECEPTACLES ARE INSTALLED TO SERVE THE
 COUNTERTOP SURFACES. REQUIRED GFI'S
  
 3} A RECEPTACLE MUST BE ADDED AT THE
 FRONT OF THE DWELLING PER 210.52(E).
  
 4} PLEASE NOTE THAT A RECEPTACLE AND
 LIGHT FIXTURE MUST BE ADDED IN THE ATTIC
 IF NONE EXISTS, FOR THE EQUIPMENT
 SERVICING PER 210.63 AND 210.70.
  
 5} THE ARCHITECT MUST SIGN AND SEAL BOTH
 SETS OF PLANS PER 481 FS.
  
 INCREASE THE APPLICATION VALUE TO
 REFLECT THE ADDITIONAL WIRING LABOR AND
 MATERIAL PER FBC 108.3.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-05-26 Cont ID  
Sent By btrobaug Date 2005-05-26 Time 14:01 Rev Time 0.50
Received By btrobaug Date 2005-05-26 Time 13:52 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-04-07 Cont ID  
Sent By btrobaug Date 2005-04-07 Time 17:31 Rev Time 0.50
Received By btrobaug Date 2005-04-07 Time 17:21 Sent To M
Notes
2005-04-07 00:00:00 
 THE ELECTRICAL PLAN AS REVIEWED WILL
 PASS. HOWEVER THE ARCHITECT MUST SIGN
 THE PLANS, INITIALS ARE NOT ACCEPTABLE
 PER FAC.61G1-16.004.
 ALSO A.1 ON ONE SET DID NOT GET SEALED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2005-04-07 Cont ID  
Sent By spalmer Date 2005-04-07 Time 10:27 Rev Time 0.15
Received By spalmer Date 2005-04-07 Time 10:27 Sent To  
Notes
2005-04-07 00:00:00OKAY PER FREDERICKE MITTNER

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2007-03-13 Cont ID  
Sent By adarroug Date 2007-03-13 Time 11:00 Rev Time 0.00
Received By adarroug Date 2007-03-13 Time 11:00 Sent To E
Notes
2007-03-13 11:00:58TO "BTROBAUB" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2007-02-28 Cont ID  
Sent By adarroug Date 2007-02-28 Time 14:35 Rev Time 0.00
Received By adarroug Date 2007-02-28 Time 14:35 Sent To Z
Notes
2007-02-28 14:35:39TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2006-12-04 Cont ID  
Sent By adarroug Date 2006-12-04 Time 10:53 Rev Time 0.00
Received By adarroug Date 2006-12-04 Time 10:53 Sent To B
Notes
2006-12-04 10:53:55PLANS GIVIN TO "LMARTINEZ" FOR RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-11-30 Cont ID  
Sent By adarroug Date 2006-11-30 Time 10:48 Rev Time 0.00
Received By adarroug Date 2006-11-30 Time 10:48 Sent To B
Notes
2006-11-30 10:48:58TO "ALANGE" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-05-19 Cont ID  
Sent By adarroug Date 2006-05-19 Time 11:34 Rev Time 0.00
Received By adarroug Date 2006-05-19 Time 11:34 Sent To B
Notes
2006-05-19 00:00:00TO "ALANGE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-04-28 Cont ID  
Sent By adarroug Date 2006-04-28 Time 16:02 Rev Time 0.00
Received By adarroug Date 2006-04-28 Time 16:02 Sent To E
Notes
2006-04-28 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-04-24 Cont ID  
Sent By adarroug Date 2006-04-24 Time 09:53 Rev Time 0.00
Received By adarroug Date 2006-04-24 Time 09:53 Sent To M
Notes
2006-04-24 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-04-17 Cont ID  
Sent By adarroug Date 2006-04-17 Time 11:02 Rev Time 0.00
Received By adarroug Date 2006-04-17 Time 11:02 Sent To Z
Notes
2006-04-17 00:00:00TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-04-10 Cont ID  
Sent By adarroug Date 2006-04-10 Time 09:39 Rev Time 0.00
Received By adarroug Date 2006-04-10 Time 09:39 Sent To E
Notes
2006-04-10 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-04-05 Cont ID  
Sent By adarroug Date 2006-04-05 Time 11:25 Rev Time 0.00
Received By adarroug Date 2006-04-05 Time 11:25 Sent To B
Notes
2006-04-05 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-03-22 Cont ID  
Sent By dpalmer Date 2006-03-22 Time 13:04 Rev Time 0.00
Received By dpalmer Date 2006-03-22 Time 13:02 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-05-26 Cont ID  
Sent By adarroug Date 2005-05-26 Time 11:40 Rev Time 0.00
Received By adarroug Date 2005-05-26 Time 11:40 Sent To E
Notes
2005-05-26 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-18 Cont ID  
Sent By adarroug Date 2005-05-18 Time 14:24 Rev Time 0.00
Received By adarroug Date 2005-05-18 Time 14:24 Sent To Z
Notes
2005-05-18 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-03 Cont ID  
Sent By alange Date 2005-05-03 Time 11:17 Rev Time 0.00
Received By alange Date 2005-04-07 Time 13:58 Sent To  
Notes
2005-04-07 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 7 Status N Date 2007-03-26 Cont ID  
Sent By hmoser Date 2007-03-26 Time 09:38 Rev Time 0.00
Received By hmoser Date 2007-03-26 Time 09:43 Sent To B
Notes
2007-03-26 09:41:553/26/07
 MECHANICAL REVISON NOT REQUIRED .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2006-05-23 Cont ID  
Sent By tgordon Date 2006-05-23 Time 15:31 Rev Time 0.15
Received By tgordon Date 2006-05-23 Time 15:31 Sent To  
Notes
2006-05-23 00:00:00REVISION TO E-CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2006-05-22 Cont ID  
Sent By tgordon Date 2006-05-22 Time 10:23 Rev Time 0.30
Received By tgordon Date 2006-05-22 Time 10:23 Sent To  
Notes
2006-05-22 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS SUBMITTED ARE
 CALLING FOR 5 KW ELECTRIC HEATERS,
 MECHANICAL PLANS ON FILE ARE CALLING FOR
 10 KW ELECTRIC HEATERS, PLEASE CORRECT.
  
 2) ENERGY CAL'S. NEED TO BE SIGNED BY
 OWNER/AGENT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-05-01 Cont ID  
Sent By pkrauss Date 2006-05-01 Time 08:08 Rev Time 0.00
Received By pkrauss Date 2006-05-01 Time 08:08 Sent To  
Notes
2006-05-01 00:00:00LETTER FROM THE ARCHITECT SUBMITTED
 RELEASING HIS RESPONSIBLTY OF THE
 MECHANICAL PLANS TO BERKUN-AIR.THE
 SIGNED, SEALED LETTER IS FILED WITH
 MECHANICAL PERMIT 05080401

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-04-26 Cont ID  
Sent By tgordon Date 2006-04-26 Time 13:48 Rev Time 0.45
Received By tgordon Date 2006-04-26 Time 13:48 Sent To  
Notes
2006-04-26 00:00:00*** DENIED ***
 1) ORIGINAL MECHANICAL PLANS WERE SEALED
 BY AN ARCHITECT (EDWARD V. MCINTYRE) SO
 ONLY HE CAN MAKE REVISIONS, UNLESS YOU
 OBTAIN A SEALED LETTER OF RELEASE FROM
 HIM.
  
 2) YOU WILL NEED TO INCREASE THE VALUE
 OF THE WORK ON YOUR PERMIT #05080401.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-05-30 Cont ID  
Sent By pkrauss Date 2005-05-30 Time 18:08 Rev Time 0.25
Received By pkrauss Date 2005-05-30 Time 17:58 Sent To B
Notes
2005-05-30 00:00:00PLANS INDICATE EQUIPMENT IS EXISTING;
 RELOCATION OF GRILLES PER PLAN A.7
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-04-08 Cont ID  
Sent By prafter Date 2005-04-08 Time 10:27 Rev Time 0.50
Received By prafter Date 2005-04-08 Time 10:27 Sent To P
Notes
2005-04-08 00:00:00MECH. PLAN REVIEW.
  
 PLEASE PROVIDE INFORMATION ON A/C WORK,
 A/C PLANS, EQUIPMENT INFORMATION AND
 VALUE OF JOB.
  
 PAT RAFTER 805/6728 OR 805/6719 PATTY
 KRUSS.
 PLEASE CALL IF THEAR ANY QUESTION.

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-04-20 Cont ID  
Sent By kstevens Date 2005-04-20 Time 16:34 Rev Time 0.33
Received By kstevens Date 2005-04-20 Time 16:34 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 6 Status P Date 2007-04-04 Cont ID  
Sent By jroach Date 2007-04-04 Time 16:59 Rev Time 0.00
Received By jroach Date 2007-04-04 Time 16:59 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status F Date 2007-03-12 Cont ID  
Sent By jroach Date 2007-03-12 Time 18:30 Rev Time 0.00
Received By jroach Date 2007-03-12 Time 18:29 Sent To I
Notes
2007-03-12 18:31:43***REVISION FAILED***
  
 1) PLEASE CLARIFY THE PROPOSED CHANGES.THE PERMIT
 APPLICATION INDICATES NO EXTERIOR CHANGES, HOWEVER, THE
 SITE PLAN SHOWS A PORCH ADDITION.IS THIS A PART OF
 THE REVISION?
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 4 Status N Date 2006-04-27 Cont ID  
Sent By mmclean Date 2006-04-27 Time 14:46 Rev Time 0.00
Received By mmclean Date 2006-04-27 Time 14:46 Sent To I
Notes
2006-04-27 00:00:00NO CHANGES AFFECTED THE ZONING REVIEW.
 05051881 (FENCE PERMIT WILL BE REVIEWED
 SEPERATELY)

Review Stop Z ZONING
Rev No 3 Status F Date 2006-04-06 Cont ID  
Sent By mmclean Date 2006-04-06 Time 10:47 Rev Time 0.00
Received By mmclean Date 2006-04-06 Time 10:47 Sent To I
Notes
2006-04-06 00:00:00DENIED,
 1. NEED TO SEPERATE THE FENCE PERMIT
 FROM THE REVISION (SUBMITTED 3/21/06)
 2. MUST RETURN THE PERMIT APPLICATON
 WITH THE EASEMENT APPROVAL FROM THE CITY
 OF WEST PALM BEACH.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 2 Status P Date 2005-05-25 Cont ID  
Sent By mmclean Date 2005-05-25 Time 15:28 Rev Time 0.00
Received By mmclean Date 2005-05-25 Time 15:28 Sent To I
Notes
2005-05-25 00:00:00MUST PULL SEPERATE PERMIT FOR GATE/FENCE
 WITH UTILITY EASEMENT FROM THE CITY OF
 WEST PALM BEACH.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-05-03 Cont ID  
Sent By mmclean Date 2005-05-03 Time 17:07 Rev Time 0.00
Received By mmclean Date 2005-05-03 Time 17:07 Sent To  
Notes
2005-05-03 00:00:00DENIED,
 1. MUST PROVIDE SETBACKS FOR
 FRONT/SIDE/REAR OF EXISTING STRUCTURE
 AND SETBACK FOR ADDITION.
 2. FENCE/GATE CAN ONLY BE A MAX OF 4FT
 WITHIN THE FRONT SETBACK (25FT) AND MAX
 6FT BEYOND THE 25FT FRONT SETBACK.
 3. MUST PULL A SEPERATE PERMIT FOR
 FENCE/GATE AND PROVIDE THE CITY OF WEST
 PALM BEACH UTILITY EASEMENT APPROVAL.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720