| 2005-07-07 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| | |
| | 2- SHEET T1: A) UPDATE GENERAL NOTES. |
| | SEE COMMENTS ON PLANS. |
| | |
| | B) DESIGN PARAMETERS: WHY MIN. SOIL |
| | BEARING PRESSURE IS : NA?. |
| | |
| | 3- PROVIDE COMPLETE SPECS FOR BBQ WHICH |
| | IS SPECIFICALLY DESIGNED FOR A PORCH. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | |
| | 4- PROVIDE COMPLETE INFORMATION FOR |
| | SHUTTERS OR APPLY FOR SEPARATE PERMIT. |
| | |
| | 5- SPECIFY SAFETY GLASS FOR WINDOWS AT |
| | HER AND HIS BATH. SEE PLANS AND SEC. |
| | 2405.2.1(2) |
| | |
| | 6- PROVIDE COMPLETE SPECS AND UL LISTING |
| | FOR PORCH FIREPLACE. SEC. 2806 FBC 2001. |
| | |
| | 7- SHEET A3: A) TRUSS ANCHOR SCHEDULE: |
| | CONNECTOR THD210 IS A WOOD TO WOOD |
| | CONNECTOR. REVISE AS REQUIRED. SEE |
| | CATALOGUE FOR PROPER MASONRY CONNECTOR. |
| | |
| | B) ALL CONNECTORS TO SPECIFY SIZE AND |
| | NUMBER OF NAILS AS SHOWN ON LATEST |
| | CATALOGUE WHICH WAS REVISED TO COMPLY |
| | WITH SEC. 1609.4.3 FBC 2001. OTHERWISE |
| | PROVIDE TESTING AND ENGINEERING FOR SIZE |
| | AND NUMBER OF NAILS THAT DIFFER FROM |
| | THOSE ALREADY TESTED AND PUBLISHED BY |
| | MANUFACTURER. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | C) CLARIFY WHY USING ONLY AN F CONNECTOR |
| | TO SUPPORT END OF GIRDER TRUSS ABOVE |
| | BEDROOM #3 ENTRY. SEE PLAN FOR COMMENTS. |
| | SPECIFY CALCULATED UPLIFT. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 8- PROVIDE FLORIDA OR APPLY FOR LOCAL |
| | PRODUCT APPROVAL FOR: |
| | A) SLIDING GLASS DOORS. (CLARIFY IF |
| | USING IMPACT DOORS OR NOT). |
| | |
| | B) WINDOW MULLIONS REQUIRED FOR LARGE |
| | FIXED WINDOWS AT LIVING ROOM. CLEARLY |
| | SPECIFY SIZE AND ANCHORS TO BE USED. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | ALSO, CLEARLY SPECIFY MULLION SIZE AND |
| | FASTENERS FOR OTHER MULLIONS. |
| | |
| | C) CASEMENT WINDOWS DADE COUNTY NOA THAT |
| | MATCHES ONE SUBMITTED FOR FLORIDA |
| | PRODUCT APPROVAL. |
| | NOTE: ASSEMBLIESSUBMITTED ALSO NEED TO |
| | MATCH THOSE SHOWN ON PLANS. |
| | |
| | D) CASEMENT WINDOW WITH IMPACT GLASS AS |
| | SHOWN ON BREAKFAST AREA TO PROVIDE |
| | EMERGENCY EGRESS. |
| | |
| | 9- OWES $360.70 FOR ADDITIONAL GUEST |
| | SUITE VALUATION AND RADON FEES. |
| | |
| | 10- REVISE ENERGY CALCULATIONS TO |
| | INCLUDE GUEST SUITE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT (561)805-6712. |
| | |