| 2005-05-06 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| | |
| | 2- SOIL TEST REPORT RECOMMENDS 18" MIN. |
| | WIDTH FOR FOOTING. FOUNDATION PLAN CALLS |
| | FOR 16". REVISE AS REQUIRED. |
| | |
| | 3- 45 DEGREE WINDOW ON BEDROOM #3 AT |
| | ZERO LOT LINE WALL IS NOT ALLOWED BY |
| | TABLE 600 FBC 2001. NO OPENINGS ALLOWED. |
| | |
| | 4- PROVIDE NOTE ON DEN ROOM STATING THAT |
| | ROOM IS NOT ALLOWED TO BE USED FOR |
| | SLEEPING PURPOSES. OTHERWISE, NEED TO |
| | COMPLY WITH EGRESS REQUIREMENTS OF |
| | SECTION 1005.4 FBC 2001. |
| | |
| | 5- NEED RECORDED EGRESS EASEMENT WHEN |
| | USING THE ZERO LOT SIDE FOR EGRESS. SEE |
| | ATTACHED REQUIREMENTS AND SAMPLE. |
| | |
| | 6- PROVIDE DETAIL/SPECS FOR CEILING |
| | INSTALLATION AT ENTRY AND REAR PORCHES. |
| | SPECIFY FASTENERS TYPE AND SPACING. SEE |
| | ASTM C-926 AND ASTM C-1063. |
| | SEC. 2504.2 FBC 2001. |
| | |
| | 7- SPECIFY SUPPORTS AND SPACING FOR WWM |
| | IN CONCRETE SLAB. SEE EXCEPTION IN SEC. |
| | 1909.3 FOR LOCATION OF WWM AND REVISE |
| | NOTE ON FOUNDATION NOTE AS REQUIRED. |
| | |
| | 8- SPECIFY FOOTINGS FOR ENTRY COLUMNS. |
| | SEC. 104.2.1.2 CITY AMENDEMNTS TO FBC. |
| | |
| | 9- SHEET A-5.0: A) ROOF NAILING ZONE |
| | DIAPHRAGM IS MISSING ZONE #3. SEE FIGURE |
| | 1606.2(C) FBC 2001.. |
| | |
| | B) DETAIL 3 SPECIFIES HGUS 28-2 SIMPSON |
| | CONNECTOR. NEED TO SPECIFY WOOD TO |
| | MASONRY CONNECTOR. REVISE AS REQUIRED. |
| | |
| | C) DETAIL 1 AND 2: REVISE TYPE OF NAILS. |
| | SEE SIMPSON CATALOGUE. |
| | |
| | 10- REVISE/UPDATE TRUSS ANCHOR SCHEDULE |
| | TO MATCH LATEST MANUFACTURER CATALOGUE |
| | THAT WAS REVISED TO COMPLY WITH SECTION |
| | 1609.4.3 FBC 2001. OTHERWISE, PROVIDE |
| | COMPLETE ENGINEERING CALCULATIONS FOR |
| | TYPE AND NUMBER OF FASTENERS THAT DIFFER |
| | FROM THOSE TESTED AND PUBLISHED BY THE |
| | MANUFACTURER. |
| | |
| | 11- RIGHT SIDE ELEVATION DOESN'T MATCH |
| | PLANS. BATHROOM #2 NEED TO SHOW GLASS |
| | BLOCK. |
| | ALSO, SHOW GLASS BLOCK ON LEFT SIDE |
| | ELEVATION. |
| | |
| | 12- CLARIFY IF USING DOORS AND WINDOWS |
| | WITH IMPACT GLASS OR IF STORM SHUTTERS |
| | ARE GOING TO BE USED. THEN, PROVIDE |
| | COMPLETE INFORMATION FOR EITHER METHOD. |
| | |
| | 13- PROVIDE FLORIDA/LOCAL PRODUCT |
| | APPROVAL FOR:A) 1 HOUR FIRE RATED |
| | ASSEMBLY AT EMERGENCY EGRESS OPENING. |
| | |
| | B) SLIDING GLASS DOORS: DRAWINGS |
| | SUBMITTED DON'T CORRESPOND TO DADE |
| | COUNTY NOA. NEED DRAWING NO 4340. |
| | |
| | C) PROVIDE PRODUCT APPROVAL FOR 12'-0" |
| | WIDE SLIDING GLASS DOORS. SEE PLANS. |
| | |
| | D) SIMPSON TRUSS CONNECTORS SPECIFIED ON |
| | PLANS. SOME PRODUCT APPROVALS SUBMITED |
| | ARE FOR CONNECTORS NOT SPECIFIED ON |
| | PLANS. |
| | |
| | 14- SHEET D-1: A) CONNECTORS CS-16 X, |
| | HTS-20 SHOWN ON DETAILS 3, 4 AND 5 ARE |
| | WOOD TO WOOD CONNECTORS. NEED TO SPECIFY |
| | CONNECTORS THAT ARE DESIGNED FOR MASONRY |
| | APPLICATIONS. SEE SIMPSON CATALOGUE FOR |
| | PROPER CONNECTOR SPECS AND PROPER TYPE |
| | AND NUMBER OF FASTENERS. REVISE AS REQ'D |
| | |
| | |
| | B) REVISE TYPE AND NUMBER OF NAILS |
| | SPECIFIED ON DETAIL #4 FOR CONNECTOR |
| | HUS26. SEE SIMPSON CATALOGUE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |