Plan Review Details - Permit 05040418
Plan Review Stops For Permit 05040418
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-10-13 Cont ID  
Sent By jwitmer Date 2005-10-13 Time 10:44 Rev Time 1.77
Received By jwitmer Date 2005-10-13 Time 10:23 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-09-15 Cont ID  
Sent By jwitmer Date 2005-09-15 Time 12:24 Rev Time 1.25
Received By jwitmer Date 2005-09-15 Time 12:24 Sent To  
Notes
2005-09-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05040418
 ADD: 1800 N FLORIDA MANGO RD
 CONT: CARTER & BURGESS
 TEL: (754)247-0047
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 PLAN REVIEW
 3RD REVIEW
 ACTION: DENIED
  
 *******CONTRACTOR TO SET MEETING WITH
 J WITMER (561)805-6715*************
  
 ALL ITEMS LISTED BELOW ARE CONTRACTOR
 ITEMS TO FOLLOW UP ON!!!!!!!!!!!!!!!!
  
  
  
 1)PROVIDE NOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 NO PERMIT APPLICATION ONLY A SUBMITTAL
 SHEET, SUBMITTAL SHEET INDICATES
 RENOVATIONS & REMODELING SHOWROOMS &
 SOME OFFICES. PLANS INDICATE EXTERIOR
 WORK A NEW FACADE, RAMPS STAIRS AND
 LOADING DOCK, ARE THESE ITEMS TO BE
 INCLUDEDUNDER THIS PERMIT.
  
 3) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) STOREFRONT A1.3
 DOORS
 WINDOWS
 MULLIONS
 B) HANDRAILS
 C) ROOFING ASSEMBLIES
 D) STORM SHUTTERS
  
 4) 1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
 5)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-07-28 Cont ID  
Sent By jwitmer Date 2005-07-28 Time 07:39 Rev Time 0.77
Received By jwitmer Date 2005-07-28 Time 07:38 Sent To  
Notes
2005-07-28 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05040418
 ADD: 1800 N FLORIDA MANGO RD
 CONT: CARTER & BURGESS
 TEL: (754)247-0047
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 PLAN REVIEW
 2ND REVIEW
 ACTION: DENIED
  
 1)PROVIDE NOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 NO PERMIT APPLICATION ONLY A SUBMITTAL
 SHEET, SUBMITTAL SHEET INDICATES
 RENOVATIONS & REMODELING SHOWROOMS &
 SOME OFFICES. PLANS INDICATE EXTERIOR
 WORK A NEW FACADE, RAMPS STAIRS AND
 LOADING DOCK, ARE THESE ITEMS TO BE
 INCLUDEDUNDER THIS PERMIT.
  
 3) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) STOREFRONT A1.3
 DOORS
 WINDOWS
 MULLIONS
 B) HANDRAILS
 C) ROOFING ASSEMBLIES
 D) STORM SHUTTERS
  
 4) 1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
 5)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-06 Cont ID  
Sent By jwitmer Date 2005-05-06 Time 10:58 Rev Time 3.33
Received By jwitmer Date 2005-05-06 Time 10:58 Sent To  
Notes
2005-05-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05040418
 ADD: 1800 N FLORIDA MANGO RD
 CONT: CARTER & BURGESS
 TEL: (754)247-0047
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 PLAN REVIEW
 1ST REVIEW
 ACTION: DENIED
  
 1)PROVIDE NOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 NO PERMIT APPLICATION ONLY A SUBMITTAL
 SHEET, SUBMITTAL SHEET INDICATES
 RENOVATIONS & REMODELING SHOWROOMS &
 SOME OFFICES. PLANS INDICATE EXTERIOR
 WORK A NEW FACADE, RAMPS STAIRS AND
 LOADING DOCK, ARE THESE ITEMS TO BE
 INCLUDEDUNDER THIS PERMIT.
  
 3)FBC* F102.2.4ROOF COVERINGS, ON
 BUILDINGS LOCATED IN THE FIRE DISTRICT,
 SHALL CONFORM TO THE REQUIREMENTS OF
 CLASS A OR B ROOF COVERINGS, AS DEFINED
 IN FBC 1505.ANNOTATE THE PLANS TO
 DEMONSTRATE COMPLIANCE.
  
 4) FBC* F102.2.7ARCHITECTURAL TRIM, ON
 BUILDINGS LOCATED IN THE FIRE DISTRICT,
 SHALL BE CONSTRUCTED OF APPROVED
 NON-COMBUSTIBLE MATERIALS OR FIRE
 RETARDANT TREATED WOOD.ANNOTATE THE
 PLANS TO DEMONSTRATE COMPLIANCE.
  
 5)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) STOREFRONT A1.3
 DOORS
 WINDOWS
 MULLIONS
 B) HANDRAILS
 C) ROOFING ASSEMBLIES
  
 6) 1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
 7)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8)1025.1 SINGLE EXIT FOR MERCANTILE IS
 LIMITED AT 2250 SQ FT, INDICATE THE
 SECOND EXIT, IF THROUGH THE OFFICE
 (BUSINESS) PROVIDE THE LOCATION FOR
 CLEAR PATH, MEANS OF EGRESS. ALSO
 INDICATE EXIT LIGHTING.
  
 9) IT APPEARS THAT THE EXIT DOORS FOR
 THE MERCANTILE OCCUPANCY ARE HORIZONTAL
 SLIDING DOORS, DOORS TO COMPLY WITH:
 10112.4.SHOW COMPLIANCE.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-09-03 Cont ID  
Sent By dpalmer Date 2005-09-03 Time 16:41 Rev Time 0.33
Received By dpalmer Date 2005-09-03 Time 16:29 Sent To  
Notes
2005-09-03 00:00:00** REDLINED PLANS**
  
 PLANS REFERENCE WRONG ELECTRICAL CODE.
 WE ARE UNDER THE 2002 NEC.
  
 KEY NOTE ON E-1.0 #4 MENTIONS EXT/EM
 LTS WIRED TO A-17.
 PLEASE SEE 700.12E, WHICHREQUIRES THE
 BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
  
 BOTH ABOVE REDLINED, NO CORRECTIONS
 NEEDED AT THIS TIME. IF PLANS HAVE
 REVISIONS DIRING CONSTRUCTION, PLEASE
 MAKE CORRECTIONS AT THAT TIME.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-07-12 Cont ID  
Sent By dpalmer Date 2005-07-12 Time 16:34 Rev Time 0.00
Received By dpalmer Date 2005-07-12 Time 16:17 Sent To  
Notes
2005-07-12 00:00:00IN ELEC FOR REVIEW.
 ************* UNSAT 2ND REVIEW *******
  
 PLEASE SEE PLAN HAVE ONLY BEEN SUBMITTED
 FOR "PLAN REVIEW" ONLY AND NOT FOT
 PERMIT.
  
 ************************************
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1)NOTE: NOTE #1 NO, PLEASE SHOW
 CIRCUITING AND CORRELATE WITH PANEL
 SCHEDULE. PLEASE SEE A NOTE WAS ADDED TO
 COMPLY WITH NEC 2005 700.12E.
 PLEASE SEE FBC 104.2.1 WHICH STATES THE
 TECHNICAL CODES SHALL NOT BE QUOTED FOR
 INFORMATION REQUIRED ON PLANS.
 PLEASE SEE NEW NOTE:
 PLEASE SEE PLANS MENTIONS 2005 NEC, WE
 ARE CURRENTLY UNDER THE 2002 NEC.
  
 2)NOTE: NOTE #2 OK.
  
 3)NOTE: NOTE #3 NO, ? IT IS UNCLEAR
 WHERE "SHOWROOM" WINDOW RECEPTS ARE?
 SHEET A2.0 SHOWS WINDOWS ON ELEVATION.
 PLEASE SEE 210.62,220.12
  
 4)NOTE: NOTE #4 OK, HOWEVER PLEASE SEE
 PREVIOUS NOTE FOR ADJUSTMENT PER 220.12
  
 5)NOTE: NOTE #5 OK, NEW MAIN SHOWN.
  
 6)NOTE: NOTE #6 NO, PLEASE SEE EQUIPMENT
 GROUNDING CONDUCTOR STILL BEING SHOWN
 BEFORE FIRST MEANS OF DISCONNECT(S).
 250.6,250.24.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE COPY OF OLD/VOIDED
 SHEETS FOR REFERENCE ONLY.
  
 PLEASE SEE PLANS HAVE ONLY BEEN
 SUBMITTED FOR "PLAN REVIEW".
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-04-21 Cont ID  
Sent By dpalmer Date 2005-04-21 Time 12:51 Rev Time 1.00
Received By dpalmer Date 2005-04-20 Time 20:06 Sent To  
Notes
2005-04-21 00:00:00********* UNSAT ***********
  
 PLEASE SEE PLANS ONLY SUBMITTED FOR
 "PLAN REVIEW " AT THIS TIME AND NOT
 SUBMITTED FOR PERMIT.
  
 1)NOTE: PLEASE INCLUDE ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULES
 TO BE SUBMITTED.
 PLEASE ALSO SEE 700.12E FOR CIRCUITING
 OF EM/EXT LTS
 215.5
  
 2)NOTE: PLEASE PLACE AREA DESIGNATIONS
 ON PLANS.
  
 3)NOTE: PLEASE SEE 210.62 FOR POSSIBLE
 "SHOW WINDOW" RECEPTS REQUIRED AND
 PLEASE ALSO SEE 210.12 FOR LOAD
 CALCULATIONS.
  
 4 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINUOUS LOADS
 AT 125% PER 215.3,230.42
  
 5)NOTE: PLEASE SEE NEW A/C DISC'S
 ATTACHED TO GUTTER NOW APPEAR TO MAINS
 4OF 5 AND 5OF 5?
 PLEASE LABEL IF INDEED THIS IS THE CASE.
  
 6)NOTE: PLEASE SEE 250.6,250.24,
 EQUIPMENT GROUNDING CONDUCTORS ARE ONLY
 INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.
  
 7)NOTE: PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 PLEASE ONLY SUBMIT ONE SET OF OLD SHEETS
 FOR REFERENCE.
  
 PLEASE BESURE TO SEE ANY POSSSIBLE
 COMMENTS FROM OTHER REVIEWER(S) WHICH
 MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
2005-04-20 00:00:00IN ELEC FOR REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2005-10-13 Cont ID  
Sent By mwennerg Date 2005-10-13 Time 11:19 Rev Time 0.00
Received By mwennerg Date 2005-10-13 Time 11:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2005-10-07 Cont ID  
Sent By mcarsill Date 2005-09-12 Time 12:57 Rev Time 0.00
Received By mwennerg Date 2005-09-12 Time 12:52 Sent To  
Notes
2005-09-12 00:00:001. SEPERATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEM MODIFICATIONS.
  
 2. NO EMERGENCY LIGHTS OR EXIT SIGNS
 SHOWN IN EXISTING WAREHOUSE. IF
 EXISTING ENSURE PROPER FUNCTION, IF
 NONE, PLEASE INSTALL.
  
 3. CARE SHOULD BE TAKEN NOT TO PAINT
 ANY OF THE REQUIRED FIRE SPRINKLER
 HEADS DURING PAINTING OPERATIONS.
  
 4. BUILDING ADDRESS REQUIRED ON
 PROPER ELEVATION. A MINIMUM OF AT
 LEAST 6" HIGH NUMBERS ARE REQUIRED.
  
 5. NEW HANDRAILS AND GUARDRAILS TO
 MEET THE PRESCRIPTIVE STRENGTH
 REQUIREMENTS OF BUILDING AND FIRE
 CODE REQUIREMENTS.
  
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
  
 804-4709 PHONE
 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-08-02 Cont ID  
Sent By mwennerg Date 2005-08-02 Time 14:42 Rev Time 0.00
Received By mwennerg Date 2005-08-02 Time 14:42 Sent To  
Notes
2005-08-02 00:00:00PLAN REVIEW ONLY- OK

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-05-04 Cont ID  
Sent By mwennerg Date 2005-05-04 Time 11:20 Rev Time 0.00
Received By mwennerg Date 2005-05-04 Time 11:20 Sent To  
Notes
2005-05-04 00:00:001) ALL CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 2) LIFE SAFETY, NFPA 101, 2003 EDITION
 SHALL BE COMPLIED WITH.
  
 3) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODELS.
  
 4) EXTERIOR STAIRS LOCATED AT THE SOUTH
 SIDE OF THE BUILDING ARE REQUIRED TO
 HAVE HANDRAILS ON BOTH SIDES.
  
 5) DOES THE SHOWROOM MEET CRITERIA TO
 ALLOW FOR A SINGLE EXIT?
  
 6) ADDITIONAL EXIT SIGNS MAY BE REQUIRED
 IFNECESSARY AT THE TIME OF THE FIELD
 INSPECTION.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910 OR 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-10-05 Cont ID  
Sent By adarroug Date 2005-10-05 Time 17:57 Rev Time 0.00
Received By adarroug Date 2005-10-05 Time 17:57 Sent To B
Notes
2005-10-05 00:00:00TO "JWITMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-30 Cont ID  
Sent By adarroug Date 2005-08-30 Time 09:19 Rev Time 0.00
Received By adarroug Date 2005-08-30 Time 09:19 Sent To  
Notes
2005-08-30 00:00:00TO "COMM" BD#20

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-05 Cont ID  
Sent By adarroug Date 2005-07-05 Time 15:30 Rev Time 0.00
Received By adarroug Date 2005-07-05 Time 15:30 Sent To  
Notes
2005-07-12 00:00:00TO "COMM" BD#11
2005-07-05 00:00:00WAITING FOR SPACE ON "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-26 Cont ID  
Sent By kstevens Date 2005-05-26 Time 16:39 Rev Time 0.00
Received By kstevens Date 2005-04-07 Time 15:16 Sent To  
Notes
2005-04-07 00:00:00TO "COMM" BD#58

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-09-14 Cont ID  
Sent By pkrauss Date 2005-09-14 Time 11:21 Rev Time 0.40
Received By pkrauss Date 2005-09-14 Time 11:18 Sent To  
Notes
2005-09-14 00:00:00PROVISO:
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR WITH
 NOTIFICATION REQUIRED PER 2001 FBC(M)
 606.2.1 & 606.4.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-07-25 Cont ID  
Sent By pkrauss Date 2005-07-25 Time 09:04 Rev Time 0.40
Received By pkrauss Date 2005-07-25 Time 09:04 Sent To  
Notes
2005-07-25 00:00:00PLAN CHECK ONLY*******APPROVED

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-05-23 Cont ID  
Sent By pkrauss Date 2005-05-23 Time 12:55 Rev Time 0.55
Received By pkrauss Date 2005-05-23 Time 11:22 Sent To  
Notes
2005-05-23 00:00:00DENIED:PLAN CHECK ONLY
  
 1.PLAN SHEET M2., RTU CURB DETAIL DOES
 NOT INDICATE THE REQUIRED HEIGHT OF THE
 CURB.PER 2001 FBC 1511.7, A MINIMUM OF
 8" ABOVE THE ROOF SURFACE IS REQUIRED.
  
 2.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS.
  
 3.INDICATE ACCESS TO EQUIPMENT LOCATED
 ON THE ROOF.PRE 2001 FBC/M 306.5,
 WHERE ACCESS TO EQUIPMENT LOCATED ON
 ROOFS IS GREATER THAN 16 FT, A PERMANENT
 MEANS OF ACCESS IS REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-08-05 Cont ID  
Sent By kstevens Date 2005-08-05 Time 07:19 Rev Time 0.50
Received By kstevens Date 2005-08-05 Time 07:19 Sent To  
Notes
2005-08-05 00:00:00CONNECTING TO EXISTING SANT. AND WATER

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-05-26 Cont ID  
Sent By kstevens Date 2005-05-26 Time 16:38 Rev Time 0.74
Received By kstevens Date 2005-05-26 Time 16:38 Sent To  
Notes
2005-05-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
  
 1. PER TABLE 403.1 A DRINKING FOUNTAIN
 AND A SERVICE SINK ARE REQUIRED. PLEASE
 INDICATE IF THESE FIXTURES ARE EXISTING.
 2. SHT CVR CODE IN EFFECT IS FBC-2001
 NOT 2003 AS SHOWN. PLEASE CORRECT
 APPLICABLE CODES. SECTION 104.2.1.
 3. SHTS A1.2 AND A1.3 (DETAIL #2) THE
 FOLLOWING INFORMATION SHALL BE INDICATED
 TO SHOW COMPLIANCE WITH SECTION 11-4.24
 AND ALL SUBSECTIONS:
 A. KNEE CLEARANCE 11-4.24.3
 B. SINK DEPTH 11-4.24.4
 C. CLEAR FLOOR SPACE 11-4.24.5 SHALL BE
 FORWARD APPROACH AND EXTEND MAXIMUM 19"
 UNDERNEATH THE SINK.
 D. EXPOSED PIPES AND SURFACES 11-4.24.6
 E. FAUCETS 11-4.24.7
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  