Plan Review Details - Permit 05040310
Plan Review Stops For Permit 05040310
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-10 Cont ID  
Sent By shill Date 2005-05-10 Time 15:18 Rev Time 1.00
Received By shill Date 2005-05-10 Time 15:18 Sent To  
Notes
2005-05-10 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)DETAIL C-E4 DOES NOT HAVE
 DIMENSIONS FOR THE FOOTING UNDER THE
 GENERATOR.NO STEEL IS SHOWN.PLEASE
 PROVIDE WEIGHT AND SIZE OF GENERATOR.
 E4, TOP LEFT CORNER, REFERS TO A
 "136'X52"X66" GENERATOR" AND A 6000
 GALLON FUEL TANK.REALLY 6000 GALLONS
 AND 136 FEET?
  
 2.)CONFIRM THAT THE CONCRETE CAN BEAR
 THE WEIGHT (AS OF YET UNDETERMINED) OF
 THE GENERATOR.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-04-25 Cont ID  
Sent By dpalmer Date 2005-04-25 Time 08:18 Rev Time 3.00
Received By dpalmer Date 2005-04-20 Time 20:03 Sent To  
Notes
2005-04-25 00:00:00********** UNSAT *************
  
 1)NOTE: PLEASE SUBMIT MANUFACTURE CUT
 SHEETS FOR GENERATOR, SUB BASE TANK .
  
 2)NOTE: PLEASE SEE OTHER REVIEWER NOTES
 PERTAINING TO 6000 GALLON FUEL TANK.
  
 3)NOTE: PLEASE SEE FIRE ALARM
 SYSTEM/WORK TO BE UNDER A SEPARATE
 PERMIT.
 PLEASE ALSO SEE LIGHTING PROTECTION IS
 ALSO REAUIRED TO BE UNDER A SEPARATE
 PERMIT.
  
 4)NOTE: PLEASE CORRELATE BUS RATINGS AND
 PANEL RATINGS OF NUMEROUS PANELS.
 \PLEASE SEE PANELS SHOWN AS 100A AND
 225A, 600A AND 500A, 600A AND 400A ETC
 ETC.
  
 5)NOTE: PLEASE CORRELATE OCP , LOAD ON
 EQ SHOWN AT 536A'S ON 225A BUS AND 600A
 MLO?? SEE RATING OF ATS-EQ, PANEL EQ,
 OCP AT MSB ETC.
 PLEASE SEE 310.15,240.4,215.5 ETC.
 NEC 2002
  
 6)NOTE: PLEASE CORRELATE RISER AND PANEL
 SCHEDULE FOR MSB, ONE SHOWS MLO AND THE
 OTHER INDICATES A MCB?
 PLEASE SEE A MCB IS REQUIRED.
 230.71
  
 7)NOTE: PLEASE SEE 620.23,620.24 FOR MIN
 CIRCUITS REQUIRED IN ELEV MACHINE RMS.
  
 8)NOTE: PLEASE CORRELATE ELECTRICAL ROOM
 LAYOUTS. PLEASE SEE "E-4".
 215.5
  
 9)NOTE: PLEASE SEE EGD, PLEASE EXPLAIN
 HOW POWER IS COMING DIRECTLY FROM GEN.
 AND DOES NOT SEEM TO GO THROUGH ANY
 TRANSFER SWITCH??
  
 10)NOTE: PLEASE SUBMIT A COPY OF
 CONTRACT TO VERIFY VALUE FOR SCOPE OF
 WORK SHOWN. PLEASE SEE FBC 104.6.5,
 VALUE FOR SCOPE OF WORK IS BASED ON ALL
 LABOR AND MATERIALS, EVEN IF OWNER
 SUPPLIED.
  
 11)NOTE: PLEASE SEE ELECTRICAL ROOM IS
 SHOWN AS MAINT/STORAGE ROOM. PLEASE SEE
 THIS IS REQUIRED DEDICATED ELECTRICAL
 SPACE PER 110.26 AND SHALL NOT HAVE ANY
 MAINT/ STORAGE .
  
 PLEASE SEE ONE SET OF PLANS HAVE MANY OF
 THE ABOVE ITEMS REDLINED.
  
 PLEASE SEE COMMMENTS FROM OTHER
 REVIEWERS WHICH WILL HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETS AND INSERT ONLY NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
 6)NOTE: PLEASE
2005-04-22 00:00:00ELECTRICAL TO BE DENIED, NOTES TO
 FOLLOW.
2005-04-20 00:00:00IN ELEC FOR REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-05-04 Cont ID  
Sent By mwennerg Date 2005-05-04 Time 10:10 Rev Time 0.00
Received By mwennerg Date 2005-05-04 Time 10:10 Sent To  
Notes
2005-05-04 00:00:001) PLEASE PROVIDE PRODUCT CUT SHEETS
 REGARDING THE GENERATOR AND ASSOCIATED
 FUEL.
  
 2) NFPA 704 MARKINGS ARE REQUIRED TO BE
 POSTED ON OR IN THE VICINITY OF THE FUEL
 TANK.
  
 3) PROTECTION OF THE GENERATOR AND FUEL
 TANK MAY BE REQUIRED IF SUBJECT TO
 MECHANICAL DAMAGE.
  
 4) SEPARATE SHOP DRAWING AND PERMIT IS
 REQUIRED FOR FIRE ALARM SYSTEM REMODEL.
  
 5) ALL PRECAUTIONS AND STANDARDS
 REGARDING STATIC ELECTRICITY TO BE
 COMPLIED WITH.
  
 6) PLEASE PROVIDE INFORMATION PERTAINING
 TO VENT PIPE LOCATION AND DIAMETER.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910 OR 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2005-04-06 Time 15:42 Sent To  
Notes
2005-04-06 00:00:00TO "COMM" BD#54

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-05-26 Cont ID  
Sent By hmoser Date 2005-05-26 Time 17:08 Rev Time 0.00
Received By hmoser Date 2005-05-26 Time 16:51 Sent To  
Notes
2005-05-26 00:00:00PLAN DENIED
 1) PLEASE PROVIDE A COPY OF THE
 MANUFACTURERS INSTALLATION INSTRUCTIONS
 ON THE GENERATOR.
 2) PLEASE PROVIDE MORE INFORMATION ON
 FUEL TANK.
 1- WHAT TYPE OF FUEL.
 2- WHERE IS THE FILL TAP.
 3- IS FUEL TANK SEPARATE FRON
 GENERATOR
 3) PLEASE SHOW TERMINATION OF EXHAUST ON
 PLANS
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
  
  

Review Stop P PLUMBING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-04-18 Cont ID  
Sent By ebowers Date 2005-04-18 Time 09:57 Rev Time 0.00
Received By ebowers Date 2005-04-18 Time 09:56 Sent To I
Notes
2005-04-18 00:00:00NEEDS TO ADD LANDSCAPING AROUND
 ENCLOSURE; LANDSCAPING PLAN REQUIRED