Plan Review Details - Permit 05040279
Plan Review Stops For Permit 05040279
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-09 Cont ID  
Sent By shill Date 2005-05-09 Time 10:53 Rev Time 0.50
Received By shill Date 2005-05-09 Time 10:52 Sent To PC
Notes
2005-05-09 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)FBC104.2.1, THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN IS TO BE ON THE PLANS.
  
 2.)THE SCOPE OF WORK IS NOT CLEAR.
 PROVIDE A EXISTING/DEMOLITION PLAN.
 PLUMBING IN THE CONCRETE SLAB CANNOT
 CHANGE LOCATION WITHOUT AN ENGINEER'S
 SPECIFICATION.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-04-11 Cont ID  
Sent By dpalmer Date 2005-04-11 Time 13:22 Rev Time 0.25
Received By dpalmer Date 2005-04-11 Time 13:22 Sent To  
Notes
2005-04-11 00:00:00*****UNSAT *****
  
 1)NOTE: PLEASE PROVIDE LAYOUT FOR NEW
 KITCHEN/BATHS SHOWING EITHER EXISTING OR
 NEW FOR ELECTRICAL . 210.52C1-5, 210.8A6
 210.70, 210.52D,210.11C3
 DRAWING SHOWS LAYOUT FOR ENTIRE UNIT,
 PLEASE IDENTIFY AREAS AND LOCATION OF
 WORK TO BE DONE.
  
 2)NOTE: PLEASE SEE FBC 104.2.1, WHICH
 REQUIRES THE PRINTED NAME AND SIGNATURE
 OF PERSON RESPONSIBLE FOR PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-04-14 Cont ID  
Sent By mwennerg Date 2005-04-14 Time 12:52 Rev Time 0.00
Received By mwennerg Date 2005-04-14 Time 12:52 Sent To  
Notes
2005-04-14 00:00:001) SMOKE DETECTORS TO BE HARD WIRED TO
 THE BUILDING ELECTRIC CONNECTED IN A
 MANNER WHERE THE ACTIVATION OF ONE
 DETECTOR WILL OPERATE ALL DETECTORS.
  
 2) SEPARATE SHOP DRAWINGS FOR THE FIRE
 ALARM AND OR FIRE SPRINKLER REMODELS ARE
 REQUIRED IF APPLICABLE.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-09 Cont ID  
Sent By shill Date 2005-05-09 Time 10:56 Rev Time 0.00
Received By shill Date 2005-04-05 Time 11:33 Sent To  
Notes
2005-04-05 00:00:00TO "COMM" BD#11

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-05-09 Cont ID  
Sent By kstevens Date 2005-05-09 Time 08:55 Rev Time 0.50
Received By kstevens Date 2005-05-09 Time 08:55 Sent To  
Notes
2005-05-09 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 1) MORE INFORMATION IS REQUIRED.
 APPLICATION DESCRIPTION OF PROJECT
 STATES "REPLACE KITCHEN, BATHS,
 FLOORING" BUT DOES NOT SPECIFICALLY
 INDICATE WHAT WORK WILL BE DONE IN THE
 BATHS AND KITCHEN. SUBMIT AN EXISTING
 FLOOR PLAN ALONG WITH A PROPOSED FLOOR
 PLAN TO GIVE AN INDICATION OF WHAT WORK
 WILL BE DONE. SECTION 104.2.1.
 2) IF PLUMBING FIXTURE LOCATIONS HAVE
 BEEN CHANGED, OR IF FIXTURES HAVE BEEN
 DELETED, A SANITARY AND A WATER RISER
 DIAGRAM IN ISOMETRIC FORM SHALL BE
 REQUIRED. SECTION 104.3.1.1.
 3) ALL INFORMATION, DRAWINGS.
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 SECTION 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]