| 2005-04-20 00:00:00 | DENIED |
| | |
| | 1)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) THE PROPERTY APPRAISER'S DRAWING |
| | SHOWS THE SCREEN PORCH THAT IS BEING |
| | ENCLOSED TO BE 377 SQFT AND THE PLANS |
| | SPECIFY 261 SQFT. PLEASE CORRECT. THE |
| | PLANS WILL HAVE TO BE RESUBMITTED TO THE |
| | COUNTY FOR IMPACT FEES WITH THE CORRECT |
| | SQUARE FOOTAGE. |
| | |
| | 3) SUBMIT THE STATE PRODUCT APPROVAL |
| | COVER SHEETS OR LOCAL PRODUCT APPROVAL |
| | FOR THE JELD-WEN DOORS. |
| | |
| | 4) THE SH-701 (NON-IMPACT) WINDOWS ARE |
| | HI-LITED ON THE STATE PRODUCT APPROVAL |
| | COVER SHEET AND THE NOA THAT WAS |
| | SUBMITTED IS FOR THE SH-701 (IMPACT |
| | RESISTANT) WINDOWS. PLEASE CLARIFY. |
| | |
| | 5) SUBMIT AN INSTALLATION SCHEDULE AND |
| | KEY PLAN FOR THE STORM PANELS. SPECIFY |
| | THE MOUNT TYPE AND FASTENERS THAT WILL |
| | BE USED. |
| | |
| | 6) THE NOA THAT WAS SUBMITTED IS NOT THE |
| | ONE LISTED ON THE STATE WEBSITE FOR THIS |
| | STATE PRODUCT APPROVAL. NOA# 03-0421.13 |
| | IS LISTED FOR THE 0.050 ALUMINUM PANELS. |
| | |
| | 7) SUBMIT THE MANUFACTURER'S |
| | SPECIFICATIONS AND LISTING FOR THE |
| | PREFAB FIREPLACE AND CHIMNEY. |
| | |
| | 8) SHOW THE CHIMNEY ON THE ELEVATIONS |
| | AND SPECIFY THE HEIGHT ABOVE THE ROOF. |
| | SEE FBC 2804.2.4. |
| | |
| | 9) PROVIDE A SECTION DETAIL OF THE WOOD |
| | FRAME CHIMNEY. SPECIFY ALL MECHANICAL |
| | CONNECTIONS, FRAMING MATERIAL, SPACING, |
| | EXTERIOR COVERING, ROOF FRAMING THAT |
| | WILL SUPPORT IT, ETC. |
| | |
| | 10) SUBMIT ENERGY CALCULATION FORMS FOR |
| | THE ENCLOSED PORCH. |
| | |
| | 11) THE DRAWING INDEX ON SHEET A1 OF THE |
| | PLANS LISTS THE ELECTRIC PLAN ON SHEET |
| | E1. THERE WAS NO SHEET E1 SUBMITTED. |
| | |
| | 12) THE WALL SECTION ON D1 LISTS 2X6 |
| | WALLS WITH R-11 INSULATION. CHAPTER 13 |
| | SECTION 602. |
| | |
| | 13) PROVIDE A CONNECTOR SCHEDULE AND |
| | SPECIFY THE CONNECTOR LOAD CAPACITIES. |
| | REVIEW ALL OF THE CONNECTORS SPECIFIED |
| | IN THE WALL SECTION AND OPENING FRAMING |
| | AND SPECIFY CURRENTLY AVAIALABLE |
| | CONNECTORS WITH STATE PRODUCT APPROVALS. |
| | THE CONNECTORS THAT ARE SPECIFIED MUST |
| | BE LISTED IN THE MANUFACTURER'S CATALOG |
| | FOR THAT APPLICATION. SIMPSON L50 |
| | CONNECTORS ARE NOT FOR THE USE SHOWN ON |
| | THE PLANS. |
| | |
| | 14) SPECIFY THE MECHANICAL CONNECTORS |
| | FOR ATTACHING THE ROOF FRAMING TO THE |
| | WALLS AND EXISTING HEADER. |
| | |
| | 15) THE WALL SECTION AND THE WINDOW |
| | FRAMING DETAIL SPECIFY DIFFERENT ANCHORS |
| | AND LENGTHS. PLEASE CORRECT. SPECIFY AN |
| | ADEQUATE WASHER FOR THE ANCHOR BOLTS. |
| | |
| | 16) SPECIFY THE CEILING HEIGHT IN THE |
| | ENCLOSED PORCH. |
| | |
| | 17) SPECIFY THE CEILING FINISH. |
| | |
| | 18) SPECIFY THE SOFFIT FINISH AND THE |
| | ATTIC VENTILATION. FBC 2309.7 |
| | |
| | 19) THE BUCK AND WINDOW MULL DETAILS ON |
| | SHEET D1 ARE FOR MASONRY CONSTRUCTION |
| | AND THE ADDITION IS WOOD FRAME. |
| | |
| | 20) SPECIFY ON THE PLANS THAT ADEQUATE |
| | SUBSTRATE WILL BE INSTALLED FOR THE |
| | ATTACHMENT OF THE STORM PANELS. |
| | |
| | 21) SEPARATE PERMITS ARE REQUIRED FOR |
| | ELECTRIC AND MECHANICAL. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |
| | |
| | |