Plan Review Details - Permit 05040125
Plan Review Stops For Permit 05040125
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-06-17 Cont ID  
Sent By alange Date 2005-06-17 Time 09:05 Rev Time 1.00
Received By alange Date 2005-06-17 Time 09:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-05-31 Cont ID  
Sent By alange Date 2005-05-31 Time 10:13 Rev Time 0.50
Received By alange Date 2005-05-31 Time 10:13 Sent To  
Notes
2005-05-31 00:00:00DENIED
  
 1.EXTERIOR DOORS AND ROOFING REQUIRE
 PRODUCT APPROVALS.PLEASE SUBMIT TWO
 COPIES OF PRODUCT APPROVALS WITH QUALITY
 ASSURANCE WITH THE FOLLOWING ATTACHED.
 NOTE:ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING TO BE ATTACHED.TOWN AND
 COUNTRY SHUTTERS AND PGT SGD-70 ARE
 MISSING STATE APPROVALS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-02 Cont ID  
Sent By alange Date 2005-05-02 Time 13:59 Rev Time 1.25
Received By alange Date 2005-05-02 Time 13:09 Sent To  
Notes
2005-05-02 00:00:00DENIED
  
 1.EXTERIOR DOORS AND ROOFING REQUIRE
 PRODUCT APPROVALS.PLEASE SUBMIT TWO
 COPIES OF PRODUCT APPROVALS WITH QUALITY
 ASSURANCE WITH THE FOLLOWING ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2. NOTE SEE RED LINE NOTES ON PLANS FOR
 BATHROOM DOOR SIZE AND SEPERATE PERMITS
 FOR FENCING, POOL AND DRIVEWAY.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-05-26 Cont ID  
Sent By btrobaug Date 2005-05-26 Time 14:33 Rev Time 0.50
Received By btrobaug Date 2005-05-26 Time 14:03 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-04-07 Cont ID  
Sent By btrobaug Date 2005-04-07 Time 14:05 Rev Time 0.75
Received By btrobaug Date 2005-04-07 Time 12:44 Sent To M
Notes
2005-04-07 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} HOW IS THE "EXISTING" 100 AMP
 SUB-PANEL, LOCATED AT THE GUEST
 HOUSE,FED AND GROUNDED. ITS NOT SHOWN ON
 THE RISER DIAGRAM. IS IT A SEPERATE
 SERVICE?
  
 2} PLEASE SUBMIT LOAD CALCULATIONS PER
 ARTICLE 220 PART II, 220.30 OR 220.31.
  
 3} IF AN EMERGENCY SYSTEM SUPPLIED BY A
 GENERATOR IS TO BE PART OF THIS PERMIT,
 PLEASE SUBMIT THE FOLLOWING.
 A) MFGR'S SPECS.
 B) INDICATE THE PRIME MOVER, AND HOW
 STORED.
 C) FEEDER CONDUCTOR SIZE. SEE 445.13.
 D) THE CONDUIT CONNECTING THE METER AND
 PANEL MUST BE REMOVED PER 700.6.
 E) INDICATE FRAME GROUND.
  
 4} THE HALL IN THE HOUSE NEEDS A
 RECEPTACLE PER 210.52(H).
  
 5} THE SMOKE DETECTOR IN THE KITCHEN
 MUST BE REMOVED OR BE PE TYPE.
 SEE8-4.1.2 NFPA-72.
  
 IF THERE ARE ANYQUESTIO0NS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-07 Cont ID  
Sent By shill Date 2005-06-07 Time 16:35 Rev Time 0.00
Received By shill Date 2005-06-07 Time 16:35 Sent To B
Notes
2005-06-07 00:00:00TO AL DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-17 Cont ID  
Sent By adarroug Date 2005-05-17 Time 11:42 Rev Time 0.00
Received By adarroug Date 2005-05-17 Time 11:42 Sent To E
Notes
2005-05-17 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-02 Cont ID  
Sent By alange Date 2005-05-02 Time 13:59 Rev Time 0.00
Received By alange Date 2005-04-04 Time 13:11 Sent To  
Notes
2005-04-04 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-04-08 Cont ID  
Sent By prafter Date 2005-04-08 Time 09:55 Rev Time 0.50
Received By prafter Date 2005-04-08 Time 09:55 Sent To P
Notes
2005-04-08 00:00:00MECH. PLAN REVIEW.
  
 PROVIDE A/C PLANS AND EQIPMENT
 INFORMATION AT A/C PERMIT TIME.
  
 PAT RAFTER 805/6728 OR8056719 PATTY
 KRAUSS.
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-04-18 Cont ID  
Sent By kstevens Date 2005-04-18 Time 17:50 Rev Time 0.50
Received By kstevens Date 2005-04-18 Time 17:50 Sent To B
Notes
2005-04-18 00:00:00NO PLUMBING PLANS SUBMITTED -
 INFORMATIONAL, A MINIMUM 60" FININSHED
 MEASUREMENT REQUIRED FOR THE WATER
 CLOSET AND BIDET FIXTURES IN ROOM. IT
 SEEMS THAT THIS ROOM WILL BE TOO SMALL,
 AS IT SEEMS TO BE ONLY 52". SECTION
 405.3.1.